background image

8 Configuration

Installation manual

35

EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685229-1D – 2022.10

#

Code

Description

[5.6]

[6-0D]

Heat up mode

:

▪ 0: 

Reheat 

only

:  Only  reheat

operation is allowed.

▪ 1: 

Sc reheat

: The domestic

hot water tank is heated according to a
schedule  and  between  the  scheduled
heat  up  cycles,  reheat  operation  is
allowed.

▪ 2: 

Schedule  only

:  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

See the operation manual for more details.

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank

 > 

Heat up mode

 > 

Reheat only

.

Settings for Reheat only mode

During Reheat only mode, the tank setpoint can be set on the user
interface.  The  maximum  allowed  temperature  is  determined  by  the
following setting:

#

Code

Description

[5.8]

[6-0E]

Maximum

:

The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.

The maximum temperature is NOT
applicable during disinfection function.
See disinfection function.

To set the heat pump ON hysteresis:

#

Code

Description

[5.9]

[6-00]

Heat pump ON hysteresis

▪ 2°C~40°C

Settings for Schedule only mode and Sc reheat mode

Comfort setpoint

Only  applicable  when  domestic  hot  water  preparation  is 

Schedule

only

 or 

Sc reheat

. When programming the schedule, you

can make use of the comfort setpoint as a preset value. When you
later  want  to  change  the  storage  setpoint,  you  only  have  to  do  it  in
one place.

The  tank  will  heat  up  until  the 

storage  comfort  temperature

  has

been  reached.  It  is  the  higher  desired  temperature  when  a  storage
comfort action is scheduled.

Additionally, a storage stop can be programmed. This feature puts a
stop  to  tank  heating  even  if  the  setpoint  has  NOT  been  reached.
Only  program  a  storage  stop  when  tank  heating  is  absolutely
undesirable.

#

Code

Description

[5.2]

[6-0A]

Comfort setpoint

:

▪ 30°C~[6‑0E]°C

Eco setpoint

The 

storage  economic  temperature

  denotes  the  lower  desired

tank  temperature.  It  is  the  desired  temperature  when  a  storage
economic action is scheduled (preferably during day).

#

Code

Description

[5.3]

[6-0B]

Eco setpoint

:

▪ 30°C~min(50,[6‑0E])°C

Reheat setpoint

Desired reheat tank temperature

, used:

▪ in 

Schedule 

reheat

  mode,  during  reheat  mode:  the

guaranteed  minimum  tank  temperature  is  set  by  the 

Reheat

setpoint

  minus  the  reheat  hysteresis.  If  the  tank  temperature

drops below this value, the tank is heated up.

▪ during  storage  comfort,  to  prioritize  the  domestic  hot  water

preparation.  When  the  tank  temperature  rises  above  this  value,
domestic  hot  water  preparation  and  space  heating/cooling  are
executed sequentially.

#

Code

Description

[5.4]

[6-0C]

Reheat setpoint

:

▪ 30°C~min(50,[6‑0E])°C

Hysteresis (reheat hysteresis)

Applicable  when  domestic  hot  water  preparation  is  scheduled
+reheat.  When  the  tank  temperature  drops  below  the  reheat
temperature minus the reheat hysteresis temperature, the tank heats
up to the reheat temperature.

#

Code

Description

[5.A]

[6-08]

Reheat hysteresis

▪ 2°C~20°C

8.3

Weather-dependent curve

8.3.1

What is a weather-dependent curve?

Weather-dependent operation

The unit operates 'weather dependent' if the desired leaving water or
tank  temperature  is  determined  automatically  by  the  outdoor
temperature.  It  therefore  is  connected  to  a  temperature  sensor  on
the  North  wall  of  the  building.  If  the  outdoor  temperature  drops  or
rises, the unit compensates instantly. Thus, the unit does not have to
wait  for  feedback  by  the  thermostat  to  increase  or  decrease  the
temperature  of  the  leaving  water  or  tank.  Because  it  reacts  more
quickly,  it  prevents  high  rises  and  drops  of  the  indoor  temperature
and water temperature at tap points.

Advantage

Weather-dependent operation reduces energy consumption.

Weather-dependent curve

To  be  able  to  compensate  for  differences  in  temperature,  the  unit
relies on its weather-dependent curve. This curve defines how much
the  temperature  of  the  tank  or  leaving  water  must  be  at  different
outdoor  temperatures.  Because  the  slope  of  the  curve  depends  on
local  circumstances  such  as  climate  and  the  insulation  of  the
building, the curve can be adjusted by an installer or user.

Types of weather-dependent curve

There are 2 types of weather-dependent curves:

▪ 2-points curve

▪ Slope-offset curve

Which type of curve you use to make adjustments, depends on your
personal  preference.  See 

"8.3.4  Using  weather-dependent

curves"

 [

4

 37].

Availability

The weather-dependent curve is available for:

▪ Main zone - Heating

Summary of Contents for EBLA08E23V3

Page 1: ...therma 3 M English Installation manual Daikin Altherma 3 M EBLA04E2V3 EBLA06E2V3 EBLA08E2V3 EBLA04E23V3 EBLA06E23V3 EBLA08E23V3 EDLA04E2V3 EDLA06E2V3 EDLA08E2V3 EDLA04E23V3 EDLA06E23V3 EDLA08E23V3 htt...

Page 2: ...ne ovat muutettuina 14 15 16 17 18 19 v platn m zn n kako je izmijenjeno amandmanima s m dos t saik rendelkez seit z p niejszymi zmianami cu amendamentele respective kakor je bilo spremenjeno 20 21 22...

Page 3: ...tila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvu...

Page 4: ...6 1105 Pressure Equipment Safety Regulations 2016 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS...

Page 5: ...ated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q H...

Page 6: ...sistance of the compressor 29 8 Configuration 29 8 1 Overview Configuration 29 8 1 1 To access the most used commands 30 8 2 Configuration wizard 31 8 2 1 Configuration wizard Language 31 8 2 2 Config...

Page 7: ...o as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater WARNING M...

Page 8: ...ok for optional equipment f Energy label g WLAN cartridge h User interface front plate rear plate screws and wall plugs i Unit mounting plate j Vibration dampers k Cable tie l Bolts nuts washers and s...

Page 9: ...r unit is NEVER snowed up d c c a b a Snow cover or shed b Pedestal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the...

Page 10: ...unit does NOT protrude 4 Remove the protective cardboard and instruction sheet a b a Protective cardboard b Instruction sheet 4 2 3 To provide drainage Make sure that condensation water can be evacua...

Page 11: ...the switch box During the installation you will need access to the inside of the outdoor unit To have easier front access rotate the switch box out of the unit as follows Prerequisite The front plate...

Page 12: ...s EKHWP tank booster heater EKHWS D tank booster heater DHW pump 0 l Preheating on the tank is not possible but a backup heater internal or external is present 10 l Preheating on the tank is not possi...

Page 13: ...side of the unit in place using a spanner to provide extra leverage 1 Connect the shut off valve with integrated filter to the outdoor unit water inlet using thread sealant b a b d c 2 1 a Water OUT s...

Page 14: ...p off the glycol container causes the concentration of water to increase The glycol concentration is then lower than assumed As a result the hydraulic components might freeze up after all Take prevent...

Page 15: ...al regulations may differ and shall be followed 6 Electrical installation DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables CAUTION Do NOT push or place redundant...

Page 16: ...mostat type For the additional zone 3 A Ext thermostat type 3 9 read only Control Item Description Heat pump convector There are different controllers and setups possible for the heat pump convectors...

Page 17: ...e guide D Wireless gateway Flow switch See installation manual of the flow switch Wires 2 0 5 mm Location extra components The following illustration shows the location of the extra components that yo...

Page 18: ...power supply contact Wires 2 0 75 1 25 mm Maximum length 50 m Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum ap...

Page 19: ...upply Wires 3V 1N 230 V 2 GND 9 3 Backup heater WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION...

Page 20: ...setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than...

Page 21: ...voltage cables should be at least 50 mm 1 On the backup heater kit connect the LV and HV cables to the appropriate terminals as shown in the illustration below 1 9 8 7 6 10 2 X15M F1B LV HV 2 On the...

Page 22: ...in this topic supersedes that of the instruction sheet delivered with the bypass valve kit Wires 3 0 75 mm The components of the bypass valve kit are as follows You only need B and D A B C D 1 Integra...

Page 23: ...Required for operation Delivered with the unit as accessory X5M 180 11 121516 Installing the user interface and connecting the user interface cable to it You need the following user interface accesso...

Page 24: ...USB memory stick if any 2 Push the rear plate on each of the 4 spots where the snap fits are located 6 3 6 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zo...

Page 25: ...e ties to the cable tie mountings 6 3 8 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedul...

Page 26: ...tration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required X2M 7 A4P Y2 180 X2M YC Y2 A4P...

Page 27: ...free contact shall ensure the minimum applicable load of 15 V DC 10 mA 1 Access the electrical connections See 6 3 1 To connect the electrical wiring to the outdoor unit 417 2 Connect the safety ther...

Page 28: ...wiring to the outdoor unit 417 2 Connect the wiring as follows X5M 4 X5M 3 X5M 10 X5M 9 X5M 6 X5M 5 1 2 S4S S10S S11S 180 X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mount...

Page 29: ...ation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 M then the unit will not break down Use a 500 V mega tester when measuring ins...

Page 30: ...sing settings via the code in the overview field settings Code For example C 07 See also To access the installer settings 430 8 5 Menu structure Overview installer settings 439 8 1 1 To access the mos...

Page 31: ...l volume Tank with booster heater installed at the side of the tank with a volume of 150 l or 180 l EKHWS E big volume Tank with booster heater installed at the side of the tank with a volume of 200 l...

Page 32: ...he number of water zones must be set INFORMATION Mixing station If your system layout contains 2 LWT zones you need to install a mixing station in front of the main LWT zone Code Description 4 4 7 02...

Page 33: ...A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you change one chec...

Page 34: ...weather dependent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence o...

Page 35: ...en a storage economic action is scheduled preferably during day Code Description 5 3 6 0B Eco setpoint 30 C min 50 6 0E C Reheat setpoint Desired reheat tank temperature used in Schedule reheat mode d...

Page 36: ...different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature is heated increasi...

Page 37: ...nk Restriction Only available to installers 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum a...

Page 38: ...licable in external room thermostat control For more info about the functionality see 8 4 1 Main zone 437 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2...

Page 39: ...oiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installe...

Page 40: ...ing to the applicable legislation The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and ha...

Page 41: ...n of the pump will start Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To chan...

Page 42: ...se make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him...

Page 43: ...t pressure sensor S1PH High pressure switch A1 Water IN screw connection male 1 A2 Water OUT screw connection male 1 Thermistors hydro module b Drain valve water circuit R1T Outlet water heat exchange...

Page 44: ...ors hydro module b Drain valve water circuit R1T Outlet water heat exchanger c Expansion vessel R3T Refrigerant liquid side d Flow sensor R4T Inlet water e Plate heat exchanger f Automatic air purge v...

Page 45: ...valve Y1S Solenoid valve 4 way valve Z C Noise filter ferrite core Z F Noise filter NOTES 1 When operating do not short circuit protection device s S1PH and Q1L 2 Colours BLK black RED red BLU blue WH...

Page 46: ...Grid feed in S6S S9S Digital power limitation inputs S10S S11S Low voltage Smart Grid contact SS1 A4P Selector switch TR1 Power supply transformer X4M Terminal strip booster heater power supply X8M Te...

Page 47: ...or wireless On OFF thermostat Only for wireless On OFF thermostat Only for Only for Hydro module Internal backup heater Translation of text on wiring diagram English Translation 1 Connection diagram 1...

Page 48: ...core signal 2 core signal 2 core Flow switch signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor oor or ambient Only for KRTETS WLAN cartridge Optional part for EWA EWYA signal 2 cor...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...4P685229 1D 2022 10 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: