5 Piping installation

Installation manual

12

EBLA04~E23V3 + EDLA04~E23V3

Daikin Altherma 3 M

4P685229-1D – 2022.10

2

2

2

1

3.55 N.m

a

a

Speed nut

5

Piping installation

5.1

Preparing water piping

NOTICE

In  case  of  plastic  pipes,  make  sure  they  are  fully  oxygen
diffusion  tight  according  to  DIN  4726.  The  diffusion  of
oxygen into the piping can lead to excessive corrosion.

NOTICE

Water circuit requirements.

 Make sure to comply with the

water  pressure  and  water  temperature  requirements
below.  For  additional  water  circuit  requirements,  see  the
installer reference guide.

Water pressure.

 The maximum water pressure is 4 bar. Provide

adequate  safeguards  in  the  water  circuit  to  ensure  that  the
maximum pressure is NOT exceeded.

Water  temperature.

  All  installed  piping  and  piping  accessories

(valve, 

connections,…) 

MUST 

withstand 

the 

following

temperatures:

INFORMATION

The  following  figure  is  an  example  and  may  NOT
completely match your system layout

65°C (*)

M

M

89°C (*)

EXAMPLE

(*) Maximum temperature for piping and accessories

5.1.1

To check the water volume and flow rate

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  higher  than
the minimum water volume, the internal water volume of the outdoor
unit NOT included:

If…

Then the minimum water

volume is…

Cooling operation

10 l

Heating/defrost operation and…

Preheating on the tank is possible.

This is possible in the following
cases:

▪ EKHWP* tank + booster heater

▪ EKHWS*D* tank + booster heater

+ DHW pump

0 l

Preheating on the tank is not
possible, but a backup heater
(internal or external) is present.

10 l

Preheating on the tank is not
possible, there is no backup heater,
and…

The return flow temperature is
>15°C

20 l

The return flow temperature is
≤15°C

50 l

NOTICE

Never  use  less  water  than  the  minimum  water  volume.  It
may cause the unit to malfunction.

NOTICE

When  circulation  in  each  space  heating/cooling  loop  is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves  are  closed  or  the  overpressure  bypass  valve  is
installed in front of the space heating/cooling loop.

Minimum flow rate

Check  that  the  minimum  flow  rate  (required  during  defrost/backup
heater operation (if applicable)) in the installation is guaranteed in all
conditions.

If operation is…

Then the minimum required

flow rate is…

Cooling

10 l/min

Heating

6 l/min

BUH operation

12 l/min

Heating defrost

12 l/min

DHW

25 l/min

NOTICE

If  glycol  was  added  to  the  water  circuit,  and  the
temperature  of  the  water  circuit  is  low,  the  flow  rate  will
NOT  be  displayed  on  the  user  interface.  In  this  case,  the
minimum  flow  rate  can  be  checked  by  way  of  the  pump
test.

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).

See the installer reference guide for more information.

Summary of Contents for EBLA08E23V3

Page 1: ...therma 3 M English Installation manual Daikin Altherma 3 M EBLA04E2V3 EBLA06E2V3 EBLA08E2V3 EBLA04E23V3 EBLA06E23V3 EBLA08E23V3 EDLA04E2V3 EDLA06E2V3 EDLA08E2V3 EDLA04E23V3 EDLA06E23V3 EDLA08E23V3 htt...

Page 2: ...ne ovat muutettuina 14 15 16 17 18 19 v platn m zn n kako je izmijenjeno amandmanima s m dos t saik rendelkez seit z p niejszymi zmianami cu amendamentele respective kakor je bilo spremenjeno 20 21 22...

Page 3: ...tila TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvu...

Page 4: ...6 1105 Pressure Equipment Safety Regulations 2016 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS...

Page 5: ...ated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q H...

Page 6: ...sistance of the compressor 29 8 Configuration 29 8 1 Overview Configuration 29 8 1 1 To access the most used commands 30 8 2 Configuration wizard 31 8 2 1 Configuration wizard Language 31 8 2 2 Config...

Page 7: ...o as to prevent mechanical damage and in a well ventilated room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater WARNING M...

Page 8: ...ok for optional equipment f Energy label g WLAN cartridge h User interface front plate rear plate screws and wall plugs i Unit mounting plate j Vibration dampers k Cable tie l Bolts nuts washers and s...

Page 9: ...r unit is NEVER snowed up d c c a b a Snow cover or shed b Pedestal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the...

Page 10: ...unit does NOT protrude 4 Remove the protective cardboard and instruction sheet a b a Protective cardboard b Instruction sheet 4 2 3 To provide drainage Make sure that condensation water can be evacua...

Page 11: ...the switch box During the installation you will need access to the inside of the outdoor unit To have easier front access rotate the switch box out of the unit as follows Prerequisite The front plate...

Page 12: ...s EKHWP tank booster heater EKHWS D tank booster heater DHW pump 0 l Preheating on the tank is not possible but a backup heater internal or external is present 10 l Preheating on the tank is not possi...

Page 13: ...side of the unit in place using a spanner to provide extra leverage 1 Connect the shut off valve with integrated filter to the outdoor unit water inlet using thread sealant b a b d c 2 1 a Water OUT s...

Page 14: ...p off the glycol container causes the concentration of water to increase The glycol concentration is then lower than assumed As a result the hydraulic components might freeze up after all Take prevent...

Page 15: ...al regulations may differ and shall be followed 6 Electrical installation DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables CAUTION Do NOT push or place redundant...

Page 16: ...mostat type For the additional zone 3 A Ext thermostat type 3 9 read only Control Item Description Heat pump convector There are different controllers and setups possible for the heat pump convectors...

Page 17: ...e guide D Wireless gateway Flow switch See installation manual of the flow switch Wires 2 0 5 mm Location extra components The following illustration shows the location of the extra components that yo...

Page 18: ...power supply contact Wires 2 0 75 1 25 mm Maximum length 50 m Preferential kWh rate power supply contact 16 V DC detection voltage supplied by PCB The voltage free contact shall ensure the minimum ap...

Page 19: ...upply Wires 3V 1N 230 V 2 GND 9 3 Backup heater WARNING The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation CAUTION...

Page 20: ...setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than...

Page 21: ...voltage cables should be at least 50 mm 1 On the backup heater kit connect the LV and HV cables to the appropriate terminals as shown in the illustration below 1 9 8 7 6 10 2 X15M F1B LV HV 2 On the...

Page 22: ...in this topic supersedes that of the instruction sheet delivered with the bypass valve kit Wires 3 0 75 mm The components of the bypass valve kit are as follows You only need B and D A B C D 1 Integra...

Page 23: ...Required for operation Delivered with the unit as accessory X5M 180 11 121516 Installing the user interface and connecting the user interface cable to it You need the following user interface accesso...

Page 24: ...USB memory stick if any 2 Push the rear plate on each of the 4 spots where the snap fits are located 6 3 6 To connect the shut off valve INFORMATION Shut off valve usage example In case of one LWT zo...

Page 25: ...e ties to the cable tie mountings 6 3 8 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump output Maximum load 2 A inrush 230 V AC 1 A continuous 9 2 2 DHW pump 9 2 3 DHW pump schedul...

Page 26: ...tration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required X2M 7 A4P Y2 180 X2M YC Y2 A4P...

Page 27: ...free contact shall ensure the minimum applicable load of 15 V DC 10 mA 1 Access the electrical connections See 6 3 1 To connect the electrical wiring to the outdoor unit 417 2 Connect the safety ther...

Page 28: ...wiring to the outdoor unit 417 2 Connect the wiring as follows X5M 4 X5M 3 X5M 10 X5M 9 X5M 6 X5M 5 1 2 S4S S10S S11S 180 X5M 3 4 5 6 9 10 1314 3 Fix the cables with cable ties to the cable tie mount...

Page 29: ...ation refrigerant accumulates in the compressor the insulation resistance over the poles can drop but if it is at least 1 M then the unit will not break down Use a 500 V mega tester when measuring ins...

Page 30: ...sing settings via the code in the overview field settings Code For example C 07 See also To access the installer settings 430 8 5 Menu structure Overview installer settings 439 8 1 1 To access the mos...

Page 31: ...l volume Tank with booster heater installed at the side of the tank with a volume of 150 l or 180 l EKHWS E big volume Tank with booster heater installed at the side of the tank with a volume of 200 l...

Page 32: ...he number of water zones must be set INFORMATION Mixing station If your system layout contains 2 LWT zones you need to install a mixing station in front of the main LWT zone Code Description 4 4 7 02...

Page 33: ...A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you change one chec...

Page 34: ...weather dependent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence o...

Page 35: ...en a storage economic action is scheduled preferably during day Code Description 5 3 6 0B Eco setpoint 30 C min 50 6 0E C Reheat setpoint Desired reheat tank temperature used in Schedule reheat mode d...

Page 36: ...different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature is heated increasi...

Page 37: ...nk Restriction Only available to installers 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum a...

Page 38: ...licable in external room thermostat control For more info about the functionality see 8 4 1 Main zone 437 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2...

Page 39: ...oiler efficiency Temperature Hysteresis 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater BBR16 activation BBR16 power limit 9 Installe...

Page 40: ...ing to the applicable legislation The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and ha...

Page 41: ...n of the pump will start Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To chan...

Page 42: ...se make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Make sure that the user has the printed documentation and ask him...

Page 43: ...t pressure sensor S1PH High pressure switch A1 Water IN screw connection male 1 A2 Water OUT screw connection male 1 Thermistors hydro module b Drain valve water circuit R1T Outlet water heat exchange...

Page 44: ...ors hydro module b Drain valve water circuit R1T Outlet water heat exchanger c Expansion vessel R3T Refrigerant liquid side d Flow sensor R4T Inlet water e Plate heat exchanger f Automatic air purge v...

Page 45: ...valve Y1S Solenoid valve 4 way valve Z C Noise filter ferrite core Z F Noise filter NOTES 1 When operating do not short circuit protection device s S1PH and Q1L 2 Colours BLK black RED red BLU blue WH...

Page 46: ...Grid feed in S6S S9S Digital power limitation inputs S10S S11S Low voltage Smart Grid contact SS1 A4P Selector switch TR1 Power supply transformer X4M Terminal strip booster heater power supply X8M Te...

Page 47: ...or wireless On OFF thermostat Only for wireless On OFF thermostat Only for Only for Hydro module Internal backup heater Translation of text on wiring diagram English Translation 1 Connection diagram 1...

Page 48: ...core signal 2 core signal 2 core Flow switch signal 2 core 2 core 2 core 2 core 2 core 3 core R2T External sensor oor or ambient Only for KRTETS WLAN cartridge Optional part for EWA EWYA signal 2 cor...

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ...4P685229 1D 2022 10 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: