![background image](http://html1.mh-extra.com/html/daikin/ebla08e23v3/ebla08e23v3_installation-manual_4256610015.webp)
6 Electrical installation
Installation manual
15
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685229-1D – 2022.10
▪ Install freeze protection valves (optional – field supply) at all
lowest points of the field piping.
▪ Normally closed valves (recommended – field supply) can prevent
that all water from indoor piping is drained when the freeze
protection valves open.
NOTICE
When freeze protection valves are installed, set the
minimum cooling setpoint (default=7°C) at least 2°C higher
than the maximum opening temperature of the freeze
protection valve. If lower, freeze protection valves can
open during cooling operation.
For more information, see the installer reference guide.
5.2.4
To fill the domestic hot water tank
See the installation manual of the domestic hot water tank.
5.2.5
To insulate the water piping
The piping in the complete water circuit MUST be insulated to
prevent condensation during cooling operation and reduction of the
heating and cooling capacity.
Outdoor water piping insulation
NOTICE
Outside piping.
Make sure the outside piping is insulated
as instructed to protect against hazards.
For piping in free air, it is recommended to use the insulation
thickness as shown in below table as a minimum (with λ=0.039 W/
mK).
Piping length (m)
Minimum insulation thickness
(mm)
<20
19
20~30
32
30~40
40
40~50
50
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator
which
can
be
reached
via
professional.standbyme.daikin.eu
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Item
Tightening torque (N•m)
X1M
2.45 ±10%
X2M
0.88 ±10%
X3M
0.88 ±10%
X4M
2.45 ±10%
X5M
0.88 ±10%
X7M
0.88 ±10%
X9M
2.45 ±10%
X10M
0.88 ±10%
6.3
Connections to the outdoor unit
Item
Description
Power supply (main)
"6.3.2 To connect the main power
Power supply (backup
heater)
(in case of outdoor unit
with integrated backup
heater)
"6.3.3 To connect the backup heater
Backup heater kit +
Bypass valve kit
(in case of external
backup heater kit)
20].
User interface
22].
Shut-off valve
"6.3.6 To connect the shut-off
24].
Electricity meters
"6.3.7 To connect the electricity
Domestic hot water
pump
"6.3.8 To connect the domestic hot
Alarm output
25].
Space cooling/heating
operation control
"6.3.10 To connect the space cooling/
Changeover to
external heat source
control
"6.3.11 To connect the changeover to
Power consumption
digital inputs
27].
Safety thermostat
thermostat (normally closed
contact)"
Smart Grid
Summary of Contents for EBLA08E23V3
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ...4P685229 1D 2022 10 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...