background image

3

WARNING

To avoid possible explosion, use only returnable (not 

disposable) service cylinders when removing refrigerant 

from a system. 

• 

Ensure the cylinder is free of damage which could lead 

to a leak or explosion.

• 

Ensure the hydrostatic test date does not exceed 5 

years.

• 

Ensure the pressure rating meets or exceeds 400 psig.

When in doubt, do not use cylinder.

Refrigerant Lines

CAUTION

The compressor POE oil for R-410A units is extremely 

susceptible to moisture absorption and could cause 

compressor failure. Do not leave system open to atmosphere 

any longer than necessary for installation. 

Use only refrigerant grade (dehydrated and sealed) 

copper tubing to connect the condensing unit with the 

indoor evaporator. After cutting the tubing, install plugs to 

keep refrigerant tubing clean and dry prior to and during 

installation. Tubing should always be cut square keeping 

ends round and free from burrs. Clean the tubing to 

prevent contamination.

Do NOT let refrigerant lines come in direct contact with 

plumbing, ductwork, floor joists, wall studs, floors, and 

walls. When running refrigerant lines through a foundation 

or wall, openings should allow for sound and vibration 

absorbing material to be placed or installed between tubing 

and foundation. Any gap between foundation or wall and 

refrigerant lines should be filled with a pliable silicon-

based caulk, RTV or a vibration damping material. Avoid 

suspending refrigerant tubing from joists and studs with 

rigid wire or straps that would come in contact with the 

tubing. Use an insulated or suspension type hanger. Keep 

both lines separate and always insulate the suction line.

These sizes are recommended for line lengths of 79 feet 

or less to obtain optimum performance. For alternate line 

sizing options or runs of more than 79 feet, refer to TP-107 

R-410A Long Line Set Application Guidelines or contact 

your distributor for assistance.

Cond

Unit

Tons

Suct

Liq

Suct

Liq

Suct

Liq

1 1/2

5/8

1/4

3/4

3/8

3/4

3/8

2

5/8

1/4

3/4

3/8

3/4

3/8

2 1/2

5/8

1/4

3/4

3/8

7/8

3/8

3

3/4

3/8

7/8

3/8

1 1/8

3/8

3 1/2

7/8

3/8

1 1/8

3/8

1 1/8

3/8

4

7/8

3/8

1 1/8

3/8

1 1/8

3/8

5

7/8

3/8

1 1/8

3/8

1 1/8

3/8

Line Diameter (In. OD)

RECOMMENDED INTERCONNECTING TUBING (Ft)

0-24

25-49

    50-79*

*

Lines greater than 79 f eet in length or v ertical elev ation changes more than 

50 f eet 

refer to 

TP

-107  R-410A  Long Line Set Application Guidelines

or 

contact your distributor for assistance.

Insulation is necessary to prevent condensation from 

forming and dropping from the suction line. Armflex (or 

satisfactory equivalent) with 3/8” min. wall thickness is 

recommended. In severe conditions (hot, high humidity 

areas) 1/2” insulation may be required. Insulation must be 

installed in a manner which protects tubing from damage 

and contamination.

Existing Line Sets

Where possible, drain as much residual compressor 

oil from existing systems, lines, and traps; pay close 

attention to low areas where oil may collect. Use of an 

approved flushing agent is recommended followed by a 

nitrogen purge to remove any remaining flushing agent 

from the lines or indoor coil. Replacement of indoor coil is 

recommended. 

Summary of Contents for DX3SEA

Page 1: ...ty of the carrier Verify the model number specifications electrical characteristics and accessories are correct prior to installation The distributor or manufacturer will not accept claims from dealer...

Page 2: ...on Ensure the foundation is sufficient to support the unit A concrete slab raised above ground level provides a suitable base ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof st...

Page 3: ...igid wire or straps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line These sizes are recommended for...

Page 4: ...the formation of copper oxide inside the refrigerant lines The POE oils used in R 410A applications will clean any copper oxide present from the inside of the refrigerant lines and spread it througho...

Page 5: ...vacuate the system to less than 500 microns 3 Isolate the pump from the system and hold vacuum for 10 minutes minimum Typically pressure will rise slowly during this period If the pressure rises to le...

Page 6: ...following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerat...

Page 7: ...eaks Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap Tighten cap finger tight and then tighten additional 1 6 of a turn 1 wrench flat or to the followi...

Page 8: ...and refrigerant tubing sizes or poor performance should Superheat setting require adjustment These adjustments should only be performed by qualified service personnel For detailed charge and TXV adju...

Page 9: ...0 13 15 19 23 24 25 6 9 11 15 20 21 23 7 12 17 18 20 8 13 15 16 7 10 11 13 7 8 10 7 8 7 105 110 115 75 80 85 90 95 100 System Superheat Targets for Piston Match ups 1 0 F Indoor Wet Bulb Temperature F...

Page 10: ...D SUCTION PRESSURE TEMPERATURE CHART LIQUID PRESSURE SATURATED LIQUID TEMPERATURE F PSIG R 410A 200 70 210 73 220 76 225 78 235 80 245 83 255 85 265 88 275 90 285 92 295 95 305 97 325 101 355 108 375...

Page 11: ...5 14 F 1 F 2 11 F 1 F 2 5 9 F 1 F 3 9 F 1 F 3 5 9 F 1 F 4 9 F 1 F 5 9 F 1 F ADVANCED ADJUSTMENT RECOMMENDATIONS NOTE Units matched with indoor coils equipped with a TXV should be charged by Subcooling...

Page 12: ...n Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage or Refrigerant Test For Leaks Add Refrigerant Restrict...

Page 13: ...rflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cau...

Page 14: ...tdoor Unit Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING...

Page 15: ...15 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 16: ...CT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additio...

Reviews: