background image

5

Leak test the system using dry nitrogen and soapy 

water to identify leaks. If you prefer to use an electronic 

leak detector, charge the system to 10 PSIG with the 

appropriate system refrigerant (see Serial Data Plate 

for refrigerant identification). Do not use an alternative 

refrigerant. Using dry nitrogen finish charging the system 

to 450 PSIG. Apply the leak detector to all suspect areas. 

When leaks are discovered, repair the leaks, and repeat 

the pressure test. If leaks have been eliminated proceed to 

system evacuation.

System Evacuation

Condensing unit liquid and suction valves are closed to 

contain the charge within the unit. The unit is shipped with 

the valve stems closed and caps installed. 

Do not open 

valves until the system is evacuated. 

WARNING

REFRIGERANT UNDER PRESSURE! 

Failure to follow proper procedures may cause property 

damage, personal injury or death.

NOTE: Scroll compressors should never be used 

to evacuate or pump down a heat pump or air 

conditioning system.

CAUTION

Prolonged operation at suction pressures less than 20 psig 

for more than 5 seconds will result in overheating of the 

scrolls and permanent damage to the scroll tips, drive 

bearings and internal seal.

Deep Vacuum Method (Recommended)

The Deep Vacuum Method requires a vacuum pump 

rated for 500 microns or less. This method is an effective 

and efficient way of assuring the system is free of non-

condensable air and moisture. As an alternative, the Triple 

Evacuation Method is detailed in the Service Manual for 

this product model.

It is recommended to remove the Schrader Cores from the 

service valves using a core-removal tool to expedite the 

evacuation procedure.

1.  Connect the vacuum pump, micron gauge, and 

vacuum rated hoses to both service valves. 

Evacuation must use both service valves to eliminate 

system mechanical seals.

2. 

Evacuate the system to less than 500 microns.

3.  Isolate the pump from the system and hold vacuum 

for 10 minutes (minimum). Typically, pressure will rise 

slowly during this period. If the pressure rises to less 

than 1000 microns and remains steady, the system is 

considered leak-free; proceed to system charging and 

startup.

4.  If pressure rises above 1000 microns but holds steady 

below 2000 microns, non-condensable air or moisture 

may remain or a small leak is present. Return to step 

2: If the same result is achieved check for leaks and 

repair. Repeat the evacuation procedure.

5.  If pressure rises above 2000 microns, a leak is 

present. Check for leaks and repair. Repeat the 

evacuation procedure.

5000

4500

4000

3500

3000

2500

2000

1500

1000

500

0      1      2      3      4       5      6      7      8       9 10

LEAK(S)

PRESENT

MINUTES

V

ACU

UM

 

IN

 

MI

CR

O

NS

CONDENSIBLES OR SMALL

LEAK PRESENT

NO LEAKS

NO CONDENSIBLES

ELECTRICAL CONNECTIONS - THREE 

PHASE OPERATION

For units designed for 3-phase operation, DO NOT 

OPERATE ON A SINGLE PHASE POWER SUPPLY. 

Measure the power supply to the unit. The supply voltage 

must

 be in agreement with the unit rating plate power 

requirements.

Rated Voltage

Minimum Supply 

Voltage

Maximum Supply 

Voltage

208 / 230V

197

253

460V

414

506

The unit rating plate lists pertinent electrical data necessary 

for proper electrical service and overcurrent protection. 

Wires should be sized to limit voltage drop to 2% (max.) 

from the main breaker or fuse panel to the unit. Consult 

the NEC, CEC, and all local codes to determine the correct 

wire gauge and length. The wire size must be sufficient to 

carry the Minimum Circuit Ampacity (MCA) listed on the 

serial plate. The supply voltage can be unbalanced (phase 

to phase) within 2%. The following formula can be used to 

determine the percentage of the voltage unbalance for your 

unit.

 

Percentage 

      Max Voltage Deviation From

 

Voltage  

=           Average Voltage    

Unbalance 

 

Average Voltage

Example: 

  

L1 - L2 = 220 V 

 

 

L2 - L3 = 216 V

Avg. Voltage:

  

(220 + 216 + 213) / 3

 

   = 

649 / 3

Maximum Deviation from Average 

= 220 - 216 = 4

% Voltage Unbalance  = 100 x (4 / 216) 

 

 

 

= 400 / 216

Summary of Contents for DX3SEA

Page 1: ...ty of the carrier Verify the model number specifications electrical characteristics and accessories are correct prior to installation The distributor or manufacturer will not accept claims from dealer...

Page 2: ...on Ensure the foundation is sufficient to support the unit A concrete slab raised above ground level provides a suitable base ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof st...

Page 3: ...igid wire or straps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line These sizes are recommended for...

Page 4: ...the formation of copper oxide inside the refrigerant lines The POE oils used in R 410A applications will clean any copper oxide present from the inside of the refrigerant lines and spread it througho...

Page 5: ...vacuate the system to less than 500 microns 3 Isolate the pump from the system and hold vacuum for 10 minutes minimum Typically pressure will rise slowly during this period If the pressure rises to le...

Page 6: ...following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerat...

Page 7: ...eaks Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap Tighten cap finger tight and then tighten additional 1 6 of a turn 1 wrench flat or to the followi...

Page 8: ...and refrigerant tubing sizes or poor performance should Superheat setting require adjustment These adjustments should only be performed by qualified service personnel For detailed charge and TXV adju...

Page 9: ...0 13 15 19 23 24 25 6 9 11 15 20 21 23 7 12 17 18 20 8 13 15 16 7 10 11 13 7 8 10 7 8 7 105 110 115 75 80 85 90 95 100 System Superheat Targets for Piston Match ups 1 0 F Indoor Wet Bulb Temperature F...

Page 10: ...D SUCTION PRESSURE TEMPERATURE CHART LIQUID PRESSURE SATURATED LIQUID TEMPERATURE F PSIG R 410A 200 70 210 73 220 76 225 78 235 80 245 83 255 85 265 88 275 90 285 92 295 95 305 97 325 101 355 108 375...

Page 11: ...5 14 F 1 F 2 11 F 1 F 2 5 9 F 1 F 3 9 F 1 F 3 5 9 F 1 F 4 9 F 1 F 5 9 F 1 F ADVANCED ADJUSTMENT RECOMMENDATIONS NOTE Units matched with indoor coils equipped with a TXV should be charged by Subcooling...

Page 12: ...n Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage or Refrigerant Test For Leaks Add Refrigerant Restrict...

Page 13: ...rflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cau...

Page 14: ...tdoor Unit Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING...

Page 15: ...15 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 16: ...CT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additio...

Reviews: