background image

8

NOTE: Superheat adjustments should not be made 

until indoor ambient conditions have stabilized. 

This could take up to 24 hours depending on 

indoor temperature and humidity. Before checking 

superheat run the unit in cooling for 10-15 minutes 

or until refrigerant pressures stabilize. Use the 

following guidelines and methods to check unit 

operation and ensure that the refrigerant charge 

is within limits. 

The outdoor temperature must be 60°F or higher. Set the 

room thermostat to COOL, fan switch to AUTO, and set the 

temperature control well below room temperature.

Units matched with indoor coils equipped with a non-

adjustable TXV should be charged by Subcooling only. 

Superheat on indoor coils with adjustable TXV valves are 

factory set and no adjustment is normally required during 

startup. Only in unique applications due to refrigerant 

line length, differences in height between the indoor 

and outdoor unit and refrigerant tubing sizes or poor 

performance should Superheat setting require adjustment. 

These adjustments should only be performed by 

qualified service personnel. For detailed charge and TXV 

adjustments refer to the appropriate Service Manual.

Fixed Orifice

CAUTION

To prevent personal injury, carefully connect and 

disconnect manifold gauge hoses. Escaping liquid 

refrigerant can cause burns. Do not vent refrigerant into 

the atmosphere. Recover all refrigerant during system 

repair and before final unit disposal.

1. 

Purge gauge lines. Connect service gauge manifold 

to base-valve service ports. Run system at least 10 

minutes to allow pressure to stabilize.

2. 

Temporarily install a thermometer 4-6” from 

the compressor on the suction line. Ensure the 

thermometer makes adequate contact and is insulated 

for best possible readings. Use vapor temperature to 

determine superheat.

3.  Refer to the superheat table provided for proper 

system superheat. Add charge to lower superheat or 

recover charge to raise superheat.

4.  Disconnect manifold set, installation is complete.

Superheat Formula = Suct. Line Temp. - Sat. Suct. 

Temp.

Summary of Contents for DX3SEA

Page 1: ...ty of the carrier Verify the model number specifications electrical characteristics and accessories are correct prior to installation The distributor or manufacturer will not accept claims from dealer...

Page 2: ...on Ensure the foundation is sufficient to support the unit A concrete slab raised above ground level provides a suitable base ROOFTOP INSTALLATIONS If it is necessary to install this unit on a roof st...

Page 3: ...igid wire or straps that would come in contact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the suction line These sizes are recommended for...

Page 4: ...the formation of copper oxide inside the refrigerant lines The POE oils used in R 410A applications will clean any copper oxide present from the inside of the refrigerant lines and spread it througho...

Page 5: ...vacuate the system to less than 500 microns 3 Isolate the pump from the system and hold vacuum for 10 minutes minimum Typically pressure will rise slowly during this period If the pressure rises to le...

Page 6: ...following overcurrent protection devices are approved for use Time delay fuses HACR type circuit breakers These devices have sufficient time delay to permit the motor compressor to start and accelerat...

Page 7: ...eaks Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap Tighten cap finger tight and then tighten additional 1 6 of a turn 1 wrench flat or to the followi...

Page 8: ...and refrigerant tubing sizes or poor performance should Superheat setting require adjustment These adjustments should only be performed by qualified service personnel For detailed charge and TXV adju...

Page 9: ...0 13 15 19 23 24 25 6 9 11 15 20 21 23 7 12 17 18 20 8 13 15 16 7 10 11 13 7 8 10 7 8 7 105 110 115 75 80 85 90 95 100 System Superheat Targets for Piston Match ups 1 0 F Indoor Wet Bulb Temperature F...

Page 10: ...D SUCTION PRESSURE TEMPERATURE CHART LIQUID PRESSURE SATURATED LIQUID TEMPERATURE F PSIG R 410A 200 70 210 73 220 76 225 78 235 80 245 83 255 85 265 88 275 90 285 92 295 95 305 97 325 101 355 108 375...

Page 11: ...5 14 F 1 F 2 11 F 1 F 2 5 9 F 1 F 3 9 F 1 F 3 5 9 F 1 F 4 9 F 1 F 5 9 F 1 F ADVANCED ADJUSTMENT RECOMMENDATIONS NOTE Units matched with indoor coils equipped with a TXV should be charged by Subcooling...

Page 12: ...n Motor Repair or Replace Shorted or Grounded Fan Motor Test Motor Windings Improper Cooling Anticipator Check Resistance of Anticipator Shortage or Refrigerant Test For Leaks Add Refrigerant Restrict...

Page 13: ...rflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cau...

Page 14: ...tdoor Unit Suction Circuit Pressure Suction Line Temperature PSIG TEMP F Liquid Circuit Pressure Liquid Temperature PSIG TEMP F Outdoor Air Temperature Dry bulb Wet bulb DB F WB F SUPERHEAT SUBCOOLING...

Page 15: ...15 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Page 16: ...CT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and entitles you to additio...

Reviews: