D-EOMWC00803-26_01EN - 23/39
Menu Password
It is possible to keep the User level always active to avoid to enter the User password. To do this the Password Disable
setpoint shall be set to On.
Setpoint/Sub-Menu
Default
Range
Description
Pwd Disable
Off
Off, On
Menu for Circuit #1
4.3
Active Setpoint
This link jumps to the page “Tmp Setpoint”. This page resumes all chiller water temperature setpoints (limits and active
setpoint will depend on the operating mode selected).
Setpoint/Sub-Menu
Default
Range
Description
Cool LWT 1=
7.0°C
4.0…15.0°C (cool mode)
-
8.0…15.0°C (cool w/ glycol mode)
Primary cooling setpoint
Cool LWT 2=
7.0°C
4.0…15.0°C (cool mode)
-
8.0…15.0°C (cool w/ glycol mode)
Secondary cooling setpoint (see 3.6.3)
Heat LWT 1=
35.0°C
Compressor dependent
Primary Heating setpoint
Heat LWT 2=
35.0°C
Compressor dependent
Secondary Heating setpoint
4.4
Evaporator LWT
This
link jumps to the page “Temperatures”. This page resumes all the relevant water temperatures.
Setpoint/Sub-Menu
Default
Range
Description
Evap LWT=
-273.1°C
-
Controlled water temperature
Evap EWT=
-273.1°C
-
Return water temperature
Cond LWT=
-273.1°C
-
Condenser leaving water temperature
Cond EWT=
-273.1°C
-
Condenser entering water temperature
Evap Delta T=
-273.1°C
-
Delta T across Evaporator
Cond Delta T=
-273.1°C
-
Delta T across Condenser
Pulldn Rate
N/A
-
Rate of decrease of the controlled temperature
Ev LWT Slope
0.0°C/min
-
Rate of decrease of the controlled temperature
Cd LWT Slope
0.0°C/min
-
Rate of decrease of the condenser leaving water temperature
Act Slope Lim.
1.7 °C/min
Maximum slopes
Common LWT=
-273.1°C
-
Master Slave Common supply water temperature
4.5
Condenser LWT
This link jumps to the page “Temperatures”. See section 4.4 for detailed page content.
4.6
Unit Capacity
This page displays the actual unit and circuit capacity
Setpoint/Sub-Menu
Default
Range
Description
Unit
-
-
Actual unit capacity
Compressor 1
-
-
Actual compressor 1 capacity
Compressor 2
-
-
Actual compressor 2 capacity