MENU STRUCTURE
All settings are divided in different menus. Each menu collects in a single page other sub-menus, settings or data related
to a specific function (for example Power Conservation or Setup) or entity (for example Unit or Circuit). In any of the
following pages, a grey box will indicate changeable values and the defaults.
4.1
Main Menu
Setpoint/Sub-
Menu
Default
Range
Description
Enter Password
-
Submenu to activate access levels
View/Set Unit
-
Submenu for unit data and settings
View/Set Circuit
-
Submenu for circuit data and settings
Unit Enable=
Enable,
-
Unit Enable state + link to unit and circuits enable page
Unit Status=
Off: Unit Sw
Auto
Off: Ice Mode Timer
Off: All Cir Disabled
Off: Unit Alarm
Off: Keypad Disable
Off: BAS Disable
Off: Unit Switch
Off: Test Mode
Auto: Wait For Load
Auto: Evap Recirc
Auto: Wait For Flow
Auto: Pumpdown
Auto: Max Pull Rate
Auto: Unit Cap Limit
Auto: Current Limit
Off: Cfg Chg Rst Ctrl
Off: Unit Not Cfgd
Auto: LP Hold
Auto: LP Unload
Auto: HP Hold
Auto: HP Unload
Auto: Cond Recirc
Auto: Rapid Restart
Status of the Unit
Active Setpoint=
7.0°C,
-
Water temperature active se link to Setpoint page
MS Ctrl Tmp=
-273.1°C,
-
Master slave controlled tempe link to Master Slave
Data page
Evaporator LWT=
-273.1°C,
-
Evaporator leaving water temperature + link to
Temperatures page
Condenser LWT=
-273.1°C,
-
Condenser leaving water temperature + link to
Temperatures page (W/C units only)
Unit Capacity=
0.0%,
-
Unit ca link to Capacity page
Unit Mode=
Cool,
-
Unit Mode + link to Available modes page
Timers
-
Submenu for unit timers
Alarms
-
Submenu for alarms; same function as Bell Button
Save/Restore
-
Submenu for saving/restoring parameters from SD card
Commission Unit
-
Submenu for commission unit
Diagnostic
-
Submenu for Controller internal features.
About Chiller
-
Application Info submenu
4.2
View/Set Unit
Setpoint/Sub-Menu
Default
Range
Description
Thermostat Ctrl
-
Submenu for Thermostatic control
Network Ctrl
-
Submenu for Network control
Pumps
-
Submenu for pump settings
Compressor VFD Setup
-
Submenu for Compressor VFD settings
Condenser
-
Submenu for Condenser tower control
Evaporator
-
Submenu for Evaporator three way valve control
Master/Slave
-
Submenu for Master Slave data and settings
Low Thd Filter
-
Submenu for Low Thd Filter
Rapid Restart
-
Submenu for Rapid Restart Option
Date/Time
-
Submenu Date, Time and Quiet Night mode schedule
Scheduler
-
Submenu for Time Scheduler
Power Conservation
-
Submenu Unit Limiting functions
Electrical Data
-
Submenu for electrical data
Ctrl IP Setup
-
Submenu for controller IP-address setup
Daikin on Site
-
Submenu for connection to Daikin cloud DoS
Menu Password
-
Submenu Disable Password for User level