D-EOMWC00803-26_01EN - 15/39
Setpoint/Sub-
Menu
Default
Range
Description
Sl1 LWT=
-
-
Display the Slave1 leaving water temperature
Sl2 LWT=
-
-
Display the Slave2 leaving water temperature
Sl3 LWT=
-
-
Display the Slave3 leaving water temperature
Mst EWT=
-
-
Display the Master entering water temperature
Sl1 EWT=
-
-
Display the Slave1 entering water temperature
Sl2 EWT=
-
-
Display the Slave2 entering water temperature
Sl3 EWT=
-
-
Display the Slave3 entering water temperature
Mst Hrs=
-
-
Master running hours
Sl1 Hrs=
-
-
Slave 1 running hours
Sl2 Hrs=
-
-
Slave 2 running hours
Sl3 Hrs=
-
-
Slave 3 running hours
Mst Starts=
-
-
Master number of starts
Sl1 Starts=
-
-
Slave 1 number of starts
Sl2 Starts=
-
-
Slave 2 number of starts
Sl3 Starts=
-
-
Slave 3 number of starts
4.2.6.2
Options
This menu allows to set main parameter of Master Slave function
Setpoint/Sub-
Menu
Default
Range
Description
Master Priority=
1
1…4
Start Up / Shut Down priority of the chiller Master
Priority = 1
→
highest priority
Priority = 4
→
lowest priority
Slave 1 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 1
Priority = 1
→
highest priority
Priority = 4
→
lowest priority
Slave 2 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 2.
Priority = 1
→
highest priority
Priority = 4
→
lowest priority
This menu is visible only if the parameter M/S Num Of Unit
has been configured at least with value 3
Slave 3 Priority=
1
1…4
Start Up / Shut Down priority of the chiller Slave 3.
Priority = 1
→
highest priority
Priority = 4
→
lowest priority
This menu is visible only if the parameter M/S Num Of Unit
has been configured at least with value 4
Master Enable=
Enable
Enable Disable
This parameter allows to enable or disable locally the
Master Chiller
Control Mode=
Complete
Partial
Complete
Parameter to select the Partial or Complete control mode
Partial
→
On/Off control
Complete
→
On/Off + Capacity control
Control Tmp=
Leaving
Entering
Leaving
Parameter to define the controlled temperature
Entering - Thermoregulations is based on the Average
Entering Water Temperature (AEWT)
Leaving - Thermoregulation is based on the Common
Leaving Water Temperature (CLWT)
4.2.6.3
Thermostat Ctrl
This page resumes all thermostat control parameter of Master Slave.
Setpoint/Sub-
Menu
Default
Range
Description
Stage Up DT=
2.7°C
0.5…5.0°C
Offset respect the active setpoint for the unit startup.
Stage Dn DT =
1.5°C
0.5…5.0°C
Offset respect the active setpoint for the unit shutdown.
Dead Band =
0.2
0.1 - Min (Stage UP DT, Stage Dn
DT)
Dead Band respect the active setpoint within which the
load/unload command are no longer generated.
Threshold=
60%
30...100%
Threshold of load that have to reach all units running before
start of a new chiller.
Stage Up Time=
5min
0min…20min
Minimum time between the start of two chillers
Stage Dn Time=
5min
0min…20min
Minim time between the stop of two chillers
Min Evap Tmp=
4.0
-
18…30°C
Minimum Evaporator leaving water temperature
4.2.6.4
Timers
Setpoint/Sub-
Menu
Default
Range
Description
Cmp Cycle T Left
0s
…
Current remaining time for compressor to startup
Cmp Cycle T Clr
Off
Off…On
Clear compressor cycle timer
Stage Up Dly Rem
-
-
Current delay for new chiller stage up
Stage Dn Dly Rem
-
-
Current delay for new chiller stage down