background image

8

Heat Pump Start-Up Procedure

9.  Check the cooling mode for the heat pump in 

the same manner as above. The reversing valve 

is energized when the thermostat is placed in 

the cooling position. A clicking sound should be 

noticeable from the reversing valve. By lowering the 

temperature setting to call for cooling, the contractor 

is energized. The compressor, blower and fan should 

then be running. After the cooling mode is checked 

out, turn the thermostat system switch to “OFF”.

10. Turn the thermostat system switch to “HEAT” and fan 

switch to “AUTO”.

11.  Slowly raise the heating temperature setting. When 

the heating first stage makes contact, stop raising 

the temperature setting. The compressor, blower and 

fan should now be running with the reversing valve in 

the de-energized (heating) position. After giving the 

unit time to settle out, make sure the unit is supplying 

heated air.

12. If the out door ambient is above 80°F, the unit may 

trip on its high pressure cut out when on heating. The 

compressor should stop. The heating cycle must be 

thoroughly checked, so postpone the test to another 

day when conditions are more suitable but - DO NOT 

FAIL TO TEST.

If the out door ambient is low and the unit operates 

properly on the heating cycle, you may check the 

pressure cutout operation by blocking off the indoor 

return air until the unit trips.

13. If unit operates properly in the heating cycle, raise 

the temperature setting until the heating second 

stage makes contact. Supplemental resistance 

heat, if installed should now come on. Make sure it 

operates properly.

NOTE: 

If outdoor thermostats are installed the 

outdoor ambient must be below the set point of 

these thermostats for the heaters to operate. It may 

be necessary to jumper these thermostats to check 

heater operation if outdoor ambient is mild.

14. For thermostats with emergency heat switch, return 

to step 11. The emergency heat switch is located 

at the bottom of the thermostat. Move the switch to 

emergency heat. The heat pump will stop, the blower 

will continue to run, all heaters will come on and the 

thermostat emergency heat light will come on.

15. If checking the unit in the wintertime, when the 

outdoor coil is cold enough to actuate the defrost 

control, observe at least one defrost cycle to make 

sure the unit defrosts completely. 

EVAPO

RAT

OR

COOLING

SERVIC E VALVE

SERVIC E PO RT

REVERSING  VALVE

CO

ND

EN

SER

SERVIC E PO RT

CO MPR ESSOR

SERVIC E PO RT

AC CUM ULATO R

EXPANSION  DEVIC E

CH ECK VALVE 

OR IFICE

SERVIC E

VALVE

CH ECK VALVE 

OR IFICE

INDO OR

CO IL

DISTRIBU TOR

OU TDO OR

CO IL

EVAPO

RAT

OR

HEATING

SERVIC E VALVE

SERVIC E PO RT

REVERSING  VALVE

CO

ND

EN

SER

CO MPR ESSOR

SERVIC E PO RT

AC CUM ULATO R

CH ECK VALVE 

OR IFICE

SERVIC E

VALVE

CH ECK VALVE 

OR IFICE

INDO OR

CO IL

DISTRIBU TOR

OU TDO OR

CO IL

DISTRIBU TOR

Heat Pump Refrigerant Circuit - Figure 7

Summary of Contents for DP5HH2441 Series

Page 1: ...ourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the cus...

Page 2: ...24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor Compressor damage may occur if this step is not followed Before using this manual check the seri...

Page 3: ...ct work The units can also be easily converted to accommodate a plenum for normal or low static applications The DP C DP H series are self contained packaged units so the only connections needed for i...

Page 4: ...the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away The unit should be set on a solid level foundation preferably a concrete slab at least 4 inches...

Page 5: ...rter Your distributor has a factory designed square to round converter transition The model s of these kits are as follows Small Chassis 25 SQRPCH101 Medium Chassis 27 5 SQRPCH102 Large and Extra Larg...

Page 6: ...ty of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch ci...

Page 7: ...gth of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate From the unit disconnect to unit the smallest wire size allowable in Table 4 may be used for the...

Page 8: ...ndoor return air until the unit trips 13 If unit operates properly in the heating cycle raise the temperature setting until the heating second stage makes contact Supplemental resistance heat if insta...

Page 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Page 10: ...ostat calls for heat At the end of the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 5 F the defrost cycle is termi...

Page 11: ...ll use the higher speed setting NOTE GPC15 and GPH16 units are rated for a maximum E S P of 0 8 except when using a 20kw electric heater The maximum static for 20 kW electric heat is 0 5 E S P When th...

Page 12: ...d small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on low stage with TXV application s...

Page 13: ...clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cut out Outside Air Into Return Duct Do not introduce cold outside air into...

Page 14: ...M 1645 1602 1560 1517 1475 1433 1390 1347 Watts 285 297 309 321 333 346 358 370 CFM 1239 1184 1146 1091 1049 1001 948 890 Watts 152 163 175 184 194 205 220 235 CFM 1837 1789 1748 1706 1665 1623 1577 1...

Page 15: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Page 16: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Page 17: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 20: ...he feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and e...

Reviews: