Daikin DP5HH2441 Series Installation Instructions Manual Download Page 16

16

PACKAGE UNITS - HEAT PUMP AND AC UNITS                                                                                                                        

HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed by a 

qualified service agency

 before the heating and cooling seasons begin.

Replace or Clean Filter

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

IMPORTANT NOTE: Never operate unit without a 

filter installed as dust and lint will build up on 

internal parts resulting in loss of efficiency, 

equipment damage and possible fire. 

A return air filter is not supplied with this unit; however, 

there must be a means of filtering the return air. An indoor 

air filter must be used with your comfort system. A properly 

maintained filter will keep the indoor coil of your comfort 

system clean. A dirty coil could cause poor operation and/

or severe equipment damage.

The installer of your unit can tell you where your filter(s) 

are and how to clean or replace them.

Check your return filter(s) at least once every two months. 

When they are dirty, replace or clean as required. 

Disposable type filters should be replaced. Reusable type 

filters may be cleaned.

NOTE:  Reusable type filters should be washed 

with warm water, dried completely and sprayed 

with an adhesive according to the manufacturers 

recommendations. 

                                

You may want to ask your dealer about high efficiency 

filters. High efficiency filters are available in both electronic 

and non-electronic types. These filters can do a better job 

of catching small airborne particles.

Improper filter maintenance is the most common cause of 

inadequate heating or cooling performance. Filters should 

be cleaned (permanent) or replaced (disposable) every two 

months or as required. When replacing a filter, it must be 

replaced with a filter of the same type and size and always 

make certain the air flow arrows on the filter point in the 

proper direction.

Condenser and Evaporator  Motors

The bearings on the air circulating blower motor and 

condenser motor are permanently lubricated and require 

no further lubrication.

Compressor

The compressor motor is hermetically sealed and does not 

require additional oiling.

Aluminum Indoor Coil Cleaning 

(Qualified Servicer Only)

This unit is equipped with an aluminum tube evaporator 

coil. The safest way to clean the evaporator coil is to simply 

flush the coil with water. This cleaning practice remains as 

the recommended cleaning method for both copper tube 

and aluminum tube residential cooling coils.

An alternate cleaning method is to use one of the products 

listed in the technical publication TP-109 (shipped in the 

literature bag with the unit) to clean the coils. The cleaners 

listed are the only agents deemed safe and approved 

for use to clean round tube aluminum coils. TP-109 is 

available on the web site in Partner Link > Service Toolkit.

NOTE: Ensure coils are rinsed well after use of 

any chemical cleaners.

Annual Inspection (Qualified Servicer Only)

Your package unit should be inspected by a qualified 

installer, or service agency at least twice every year. 

This check should be performed before the heating and 

cooling seasons begin. This will ensure that the system is 

performing properly and safely. Repair as necessary.

•  Check physical support of the unit. Ensure it is sound 

without any sagging, cracks, or gaps, around the 

base.

•  Check for obvious signs of deterioration of the unit.

•  Check both condenser and evaporator coil to make 

sure each are clean.

•  Return  Air Connection

. Check for physical 

soundness and ensure that the connection is firmly 

sealed to the package unit casing.

•  Wiring

. Check wires for damage. Check electrical 

connections for tightness and/or corrosion.

•  Filters

. Check that filters are clean and in the proper 

placement in the unit or duct system.

•  Louvers

. Inspect air inlet louvers inside the heat 

exchanger compartments. Ensure the area is clean 

and free of dirt and debris.

Before Calling Your Servicer

• 

Check the thermostat to confirm that it is properly 

set.

• 

Check the disconnect switch near the unit to confirm 

that it is closed.

•  Check the electrical panel for tripped circuit breakers  

or failed fuses. Reset the circuit breakers or replace 

fuses as necessary. 

•  Check for blockage of the indoor air inlets and 

outlets. Confirm that they are open and have not 

been blocked by objects (rugs, curtains or furniture).

• 

Check for obstructions on the unit. Confirm that it has 

not been covered on the sides or the top. Remove 

any obstruction that can be safely removed. If the 

unit is covered with dirt or debris, call a qualified 

servicer to clean it. 

• 

Check the filter. If it is dirty, clean or replace it.

Summary of Contents for DP5HH2441 Series

Page 1: ...ourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the cus...

Page 2: ...24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor Compressor damage may occur if this step is not followed Before using this manual check the seri...

Page 3: ...ct work The units can also be easily converted to accommodate a plenum for normal or low static applications The DP C DP H series are self contained packaged units so the only connections needed for i...

Page 4: ...the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away The unit should be set on a solid level foundation preferably a concrete slab at least 4 inches...

Page 5: ...rter Your distributor has a factory designed square to round converter transition The model s of these kits are as follows Small Chassis 25 SQRPCH101 Medium Chassis 27 5 SQRPCH102 Large and Extra Larg...

Page 6: ...ty of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch ci...

Page 7: ...gth of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate From the unit disconnect to unit the smallest wire size allowable in Table 4 may be used for the...

Page 8: ...ndoor return air until the unit trips 13 If unit operates properly in the heating cycle raise the temperature setting until the heating second stage makes contact Supplemental resistance heat if insta...

Page 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Page 10: ...ostat calls for heat At the end of the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 5 F the defrost cycle is termi...

Page 11: ...ll use the higher speed setting NOTE GPC15 and GPH16 units are rated for a maximum E S P of 0 8 except when using a 20kw electric heater The maximum static for 20 kW electric heat is 0 5 E S P When th...

Page 12: ...d small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on low stage with TXV application s...

Page 13: ...clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cut out Outside Air Into Return Duct Do not introduce cold outside air into...

Page 14: ...M 1645 1602 1560 1517 1475 1433 1390 1347 Watts 285 297 309 321 333 346 358 370 CFM 1239 1184 1146 1091 1049 1001 948 890 Watts 152 163 175 184 194 205 220 235 CFM 1837 1789 1748 1706 1665 1623 1577 1...

Page 15: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Page 16: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Page 17: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 20: ...he feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and e...

Reviews: