Daikin DP5HH2441 Series Installation Instructions Manual Download Page 7

7

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

High Voltage Wiring: (See Figure 6)

Single Phase - Two leads should be connected to terminals 

L1& L2 in the electrical control section, using wire sizes 

specified in wiring table.

Low Voltage Wiring: (See Figure 6)

a.  Air Conditioners - Connect 24V wires from the 

thermostat to the corresponding wires in the control 

box using No. 18AWG as shown in TABLE 2.

LEAD

THERMOSTAT

Red

R (24V)

Green

G (Fan)

Yellow

Y (Cool)

White

W1 (Heat)*

Brown

W2 (Heat)*

Table 2

b.  Heat Pumps - Connect 24V wires from the 

thermostat to the corresponding wires in the control 

box using No. 18AWG as shown in TABLE 3.

TERMINAL

THERMOSTAT

Red

R (24V)

Green

G (Fan)

Orange

O (Rev. Valve)

White

W1 (Heat, 2nd)*

Brown

W2 (Heat 3rd)*

Yellow

Y (Cool)

C (Blue)

C (Common)

*Optional field installed heat connections

Table 3

Internal Wiring:

A diagram detailing the internal wiring of this unit is located 

on the electrical box cover. If any of the original wire 

supplied with the appliance must be replaced, the wire 

gauge and insulation must be the same as the original 

wiring.

Transformer is wired for 230 volts on the 208/230 models. 

See wiring diagram for 208 volt wiring.

BRANCH CIRCUIT AMPACITY 15 20 25 30 35 40 45 50

SUPPLY WIRE LENGTH - 

FEET

200

6

4

4

4

3

3

2

2

150

8

6

6

4

4

4

3

3

100

10 8

8

6

6

6

4

4

50

14 12 10 10 8

8

6

6

Table 4

1.  For branch circuit wiring (main power supply to unit 

disconnect), the minimum wire size for the length of 

the run can be determined from Table 4 using the 

circuit ampacity found on the unit rating plate. From 

the unit disconnect to unit, the smallest wire size 

allowable in Table 4 may be used for the ampacity, 

as the Disconnect must be in sight of the unit.

2.  Wire size based on 60°C rated wire insulation and 

30°C Ambient Temperature (86°F).

3.  For more than 3 conductors in a raceway or cable, 

see the N.E.C. for derating the ampacity of each 

conductor.

OPERATION

Start-Up Procedure and Checklist

Begin with power turned off at all disconnects.

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

1.  Turn thermostat system switch to “Cool,” and fan 

switch to “Auto” and turn temperature setting as high 

as it will go.

2.  Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.

4.  Turn the fan switch to the “ON” position. The blower 

should operate after a 10 second delay.

5.  Turn the fan switch to “Auto” position. The blower 

should stop after a 60 second delay.

6.  Slowly lower the cooling temperature until the unit 

starts. The compressor, blower and fan should now 

be operating. Allow the unit to run 10 minutes, make 

sure cool air is being supplied by the unit.

7.  Turn the temperature setting to the highest position, 

stopping the unit. The indoor blower will continue to 

run for 60 seconds.

8.  Turn the thermostat system switch to “OFF” and 

disconnect all power when servicing the unit.

WARNING

HIGH VOLTAGE!

Disconnect all power before servicing or in-

stalling this unit. Multiple power sources may 

be present. Failure to do so may cause proper-

ty damage, personal injury or death. 

 

Summary of Contents for DP5HH2441 Series

Page 1: ...ourself with this Installation Manual Observe all safety warnings During installation or repair caution is to be observed It is your responsibility to install the product safely and to educate the cus...

Page 2: ...24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compressor Compressor damage may occur if this step is not followed Before using this manual check the seri...

Page 3: ...ct work The units can also be easily converted to accommodate a plenum for normal or low static applications The DP C DP H series are self contained packaged units so the only connections needed for i...

Page 4: ...the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away The unit should be set on a solid level foundation preferably a concrete slab at least 4 inches...

Page 5: ...rter Your distributor has a factory designed square to round converter transition The model s of these kits are as follows Small Chassis 25 SQRPCH101 Medium Chassis 27 5 SQRPCH102 Large and Extra Larg...

Page 6: ...ty of sufficient power to operate the unit The voltage frequency and phase at the power supply should be checked to make sure it corresponds to the unit s RATED VOLTAGE REQUIREMENT Install a branch ci...

Page 7: ...gth of the run can be determined from Table 4 using the circuit ampacity found on the unit rating plate From the unit disconnect to unit the smallest wire size allowable in Table 4 may be used for the...

Page 8: ...ndoor return air until the unit trips 13 If unit operates properly in the heating cycle raise the temperature setting until the heating second stage makes contact Supplemental resistance heat if insta...

Page 9: ...used to prevent full electric heater operation at varying outdoor ambient 0 F to 45 F They are normally open above their set points and closed below to permit staging of indoor supplement heater oper...

Page 10: ...ostat calls for heat At the end of the timing period the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 5 F the defrost cycle is termi...

Page 11: ...ll use the higher speed setting NOTE GPC15 and GPH16 units are rated for a maximum E S P of 0 8 except when using a 20kw electric heater The maximum static for 20 kW electric heat is 0 5 E S P When th...

Page 12: ...d small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on low stage with TXV application s...

Page 13: ...clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cut out Outside Air Into Return Duct Do not introduce cold outside air into...

Page 14: ...M 1645 1602 1560 1517 1475 1433 1390 1347 Watts 285 297 309 321 333 346 358 370 CFM 1239 1184 1146 1091 1049 1001 948 890 Watts 152 163 175 184 194 205 220 235 CFM 1837 1789 1748 1706 1665 1623 1577 1...

Page 15: ...ssor stuck grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage...

Page 16: ...minum Indoor Coil Cleaning Qualified Servicer Only This unit is equipped with an aluminum tube evaporator coil The safest way to clean the evaporator coil is to simply flush the coil with water This c...

Page 17: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Page 18: ...18 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 19: ...19 THIS PAGE LEFT INTENTIONALLY BLANK...

Page 20: ...he feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and e...

Reviews: