background image

Installation manual

intelligent Tablet Controller

English

Installation manual

intelligent Tablet Controller

DCC601A51

Summary of Contents for DCC601A51

Page 1: ...Installation manual intelligent Tablet Controller English Installation manual intelligent Tablet Controller DCC601A51 ...

Page 2: ...t audience Authorised installers Documentation set This document is part of a documentation set The complete set consists of Installation manual Installation instructions Format Paper supplied in the kit Installer reference guide Preparation of the installation reference data Format Digital files on http www daikineurope com support and manuals product information Latest revisions of the supplied ...

Page 3: ... performed in accordance with the wiring diagram supplied with the product Make sure to install earth wiring Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical shock Make sure to use a dedicated power circuit NEVER use a power supply shared by another appliance Make sure to install the required fuses or circuit breakers Make sure to inst...

Page 4: ...ller kit see 10 5 Schematic setup of the intelligent Tablet Controller 4 11 Before installing the intelligent Tablet Controller kit modules draw up an efficient plan of work using this schematic and based on the real environment it needs to be installed in 5 3 Compatible Daikin equipment The intelligent Tablet Controller solution can connect to certain Daikin units that provide a DIII NET communic...

Page 5: ...ments Location Indoor inside an electrical cabinet The electrical cabinet must be lockable or designed to be opened only with a special tool The key or tool should be available only to service personnel must be installed in a space with no access for the general public must comply with the applicable legislation must have ingress protection class of IP4X or higher however make sure enough ventilat...

Page 6: ...itches a RESET Button for restarting the CPU module and I O module k DIP SW Reserved for servicing Factory default all switches are set to OFF OFF n BACKUP Switch for turning on off the backup power supply for retaining the current settings provided by the internal battery Factory default OFF OFF This will be set to the ON ON position during commissioning q Lever To assist mounting dismounting the...

Page 7: ...perating condition CPU ALIVE ALARM Normal Blink OFF Hardware failure OFF ON Power interruption OFF OFF Communication failure between CPU module and I O module for 10 seconds or more ON Blink 7 Installation 7 1 Installation of the intelligent Tablet Controller hardware The intelligent Tablet Controller components are to be mounted onto a 35 mm DIN rail inside an electrical cabinet For more informat...

Page 8: ...on terminal sized for maximum 4 mm According to applicable legislation Solid or stranded wire allowed The internal protection of the WAGO PSU is fused at 2 5 A 250 V 24 V DC power supply to the CPU module According to applicable legislation Solid or stranded wire allowed USB cable 5 m Commercial USB 2 0 cable type A to type B connector provided in the intelligent Tablet Controller kit a Total leng...

Page 9: ...ternally So you can use any one of them However you can only connect up to 2 wires simultaneously to each COM terminal If applicable connect the I O module s COM terminal to the negative side of the device terminals 7 2 3 Connecting the power supply to all modules For all wiring requirements see 7 2 1 Wiring requirements 47 To connect the power supply to all modules 1 Connect the power supply to t...

Page 10: ...e data backup battery Both intelligent Tablet Controller modules are marked with the following symbol This means that electrical and electronic products may not be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable...

Page 11: ...chematic setup of the intelligent Tablet Controller USB 230 V AC RJ 45 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 OUT IN F1 F2 http cloud daikineurope com DIII NET POWER I O IF CPU IF LAN F1 F2 Di1 Di4 d e f i i i h j k 24 V DC c b g a l l L N a WAGO power supply unit b CPU module c I O module d Optional Daikin supplied tablet e Daikin Cloud Service f Daikin Cloud Service g LAN gateway optional Dai...

Page 12: ...4P414342 1D 2020 12 Copyright 2015 Daikin 4P414342 1 D 0000000Y Verantwortung für Energie und Umwelt ...