SERVICING
C
Y
Indoor
Unit
Wiring Schematic - 3-Wire CoreSense™ Alert Module
Reset
Switch
Run/Alert
LED
Trip/Lock-Out
Red LED
Protection
Output
Data Port
One
Current
Sensor
Diagnostics - 2-Wire module
Applies to ASX130[18-60]CA, ASX140[18-36]1CA, ASX140421DA,
and ASX140[48-60]1BA units
The CoreSense™ module is self-contained with no required
external sensors and works with any residential condensing unit
that has a Copeland Scroll™ compressor inside.
Once attached, CoreSense™ provides around-the-clock mon
-
itoring for common electrical problems, compressor defects
and broad system faults. If a glitch is detected, an LED indicator
flashes the proper alert codes to help you quickly pinpoint the
problem.
See Diagnostic Table: 2-Wire Comfort Alert™ Module
on following pages.)
Schematic Abbreviation Descriptions
HTCO High Temperature Cut Out Switch
HPCO High Pressure Cut Out Switch
LPCO Low Pressure Cut Out Switch
CC Compressor Contactor
ECB Electronic Control Board
(Defrost or Time Delay)
Wiring Schematic - 2-Wire CoreSense™ Module