4 Installation

Installation manual

19

D2CND024A1/4AA + D2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-3E – 2017.07

a

a

60/100 to 80/125 adapter

80/125 flue parts to be used are shown below:

a

b

c

d

e

f

a

80/125 wall terminal kit (type C13)

b

80/125 roof terminal kit (type C33)

c

90° elbow 80/125

d

45° elbow 80/125

e

30° elbow 80/125

f

Extension 80/125
L = 500-1000 mm

Type C43x (concentric flue system)

Several heat sources draw combustion air from the outside through
the annular gap of the room sealed balanced flue system and expel
flue  gas  to  the  outside  via  the  roof,  through  a  moisture-resistant
internal pipe.

The multi-served chimney is a system that is part of the building and
has a separate CE marking. The connection between the boiler and
the  shaft  and,  the  connection  between  the  boiler  and  the  air  intake
system must be obtained via Daikin.

e

f

g

h

L

i

a b c

d

a

Tee flex boiler connection set 100 or 130

b

Extension 60 mm

c

Chimney connection 60/100

d

Elbow 60/100 90°

Optional:

e

90° elbow 60/100

f

45° elbow 60/100

g

Tee 60/100 with measurement point

h

30° elbow 60/100

i

Extension 60/100
L = 500-1000 mm

Maximum  allowable  length  of  the  flue  duct  up  to  common
chimney is 3  1 60/100 90° elbow.

In C43x type units, condensate flow into the unit is not allowed.

Type C63x (concentric flue system)

To  install  the  boiler  as  a  C63x  option  the  following  data  must  be
used  to  determine  the  correct  diameters  and  lengths  of  the  flue
system.

For D2TND*

▪ Nominal combustion products temperature: 77°C

▪ Combustion products mass flow rate: 10.75 g/s

▪ Overheat combustion products temperature: 90°C

▪ Minimum combustion products temperature: 20°C

▪ Maximum  allowable  pressure  difference  between  combustion  air

inlet and flue gas outlet (including wind pressures): 100 Pa

For D2CND*

▪ Nominal combustion products temperature: 93°C

▪ Combustion products mass flow rate: 11.48 g/s

▪ Overheat combustion products temperature: 100°C

▪ Minimum combustion products temperature: 20°C

▪ Maximum  allowable  pressure  difference  between  combustion  air

inlet and flue gas outlet (including wind pressures): 125 Pa

For D2CND* and D2TND*

▪ Minimum combustion products mass flow rate: 1.32 g/s

▪ CO

2

 content at nominal heat input: 9.0%

▪ Maximum allowable draught: 200 Pa

▪ The  boiler  must  be  connected  to  a  system  with  the  following

characteristics: T120 P1 W

▪ Maximum allowable temperature of combustion air: 50°C

▪ Maximum  allowable  recirculation  rate  under  wind  conditions  is

10%

▪ The  terminals  for  the  supply  of  combustion  air  and  for  the

evacuation  of  combustion  products  shall  not  be  installed  on
opposite walls of the building.

▪ Condensate flow into the unit is allowed.

Type C53x (twin pipes flue system)

Air  supply  and  flue  gas  discharge  from  /  to  atmosphere  in  areas  of
different pressure. The boiler draws combustion air from outside via
a horizontal pipe fitted to the external wall and expels flue gas to the
outside via the roof.

The terminals for the supply of combustion air and for the evacuation
of combustion products shall not be installed on opposite walls of the
building.

Summary of Contents for D2TND012A4AA

Page 1: ...Installation manual Wall mounted condensing boiler English Installation manual Wall mounted condensing boiler D2CND024A1AA D2CND024A4AA D2TND012A4AA D2TND018A4AA D2TND024A4AA...

Page 2: ...tatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumie...

Page 3: ...t be appropriately disposed of in accordance with local and national regulations The components are easy to separate and the plastics are marked This allows the various components to be sorted for app...

Page 4: ...nfiguration and service must be performed by qualified competent persons in accordance with local standards and regulations Incorrect installation of this unit may harm the user and his her surroundin...

Page 5: ...rature sensor which is located at the outlet of the main heat exchanger This protection activates the boiler pump when the water temperature drops below 13 C and it activates the burner when the water...

Page 6: ...Return temperature sensor s Silencer t Automatic air vent pump u Water pressure sensor v By pass w Boiler pump x Domestic hot water flow sensor y Domestic hot water flow limiter z Internal filling val...

Page 7: ...max m h 0 12 0 46 0 12 0 69 0 12 0 96 0 12 0 96 Combustion products mass flow rate min max G20 g s 1 32 5 12 1 32 7 78 1 32 10 75 1 32 10 75 Combustion products mass flow rate min max G31 g s 1 23 4...

Page 8: ...aters 50 C return temperature at heater inlet 4 Installation 4 1 To open the unit WARNING Only qualified competent persons are allowed to open the unit Certain actions explained in this document such...

Page 9: ...o the current I E E Wiring Regulations local Building Regulations or any other local regulations currently in service The intake air must not include chemicals that may cause corrosion toxic gas forma...

Page 10: ...ight and related system charge pressure are given below h p 6 m 0 8 bar 7 m 0 9 bar 8 m 1 0 bar 9 m 1 1 bar 10 m 1 2 bar 11 m 1 3 bar 12 m 1 4 bar 13 m 1 5 bar h h System water height m p System charg...

Page 11: ...f the user 4 7 Residual pump lift graph The residual pump lift graph shows the amount of pump lift mbar that remains for the central heating circuit 0 0 100 200 300 400 500 600 700 800 200 400 600 800...

Page 12: ...age while the gas line to the boiler is open see 5 3 To check for gas leakage on page 25 In case gas piping is adjacent to the wall and is to be connected to the gas pipe connection of the boiler with...

Page 13: ...any damage that may occur this way WARNING Use a dedicated power circuit Never use a power supply cable shared by another unit The unit runs on 230 V AC 50 Hz power A power cable is delivered with the...

Page 14: ...ands that are sent with the unit must be assembled to the bottom sheet of the boiler in case connection of these options Below you can see the cable glands placement PG 9 PG 9 PG 7 PG 7 Holes on the b...

Page 15: ...4AA Wall mounted condensing boiler 3P469346 3E 2017 07 4 8 6 Wiring diagram DANGER RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes before servicing Models D2CND024A1AA and D...

Page 16: ...face Ext3 X1M Opentherm room thermostat Ext4 X2M External power output 230 V AC Ext5 X2M Reserved not in use X1M X4 X11 X12 Low voltage terminal strip X2M X1 X2 High voltage terminal strip 4 8 7 Guide...

Page 17: ...e that products of combustion discharging from the terminal cannot re enter the building or other buildings through ventilators windows doors other sources of natural air infiltration or forced ventil...

Page 18: ...kit Optional c 45 elbow 60 100 d Extension 60 100 mm e Flat roof outlet kit f 90 elbow 60 100 g 45 elbow 60 100 h 30 elbow 60 100 i Extension 60 100 L 500 1000 mm Allowable flue length for C33x D2TND...

Page 19: ...and lengths of the flue system For D2TND Nominal combustion products temperature 77 C Combustion products mass flow rate 10 75 g s Overheat combustion products temperature 90 C Minimum combustion pro...

Page 20: ...use flue outlet duct length must be shortened with the same length Type C83x twin pipes flue system The boiler draws combustion air from outside via a separate supply pipe routed through the external...

Page 21: ...gh 140 19 6 69 2 DN 80 Flex square and rough 130 17 0 60 0 DN 80 Flex square and rough 120 12 2 43 0 DN 80 Star square and rough 140 47 5 167 8 DN 80 Star square and rough 120 33 3 117 9 Allowable flu...

Page 22: ...Tee 60 100 with measurement point EKFGP4667 90 elbow 60 100 with measurement point DRMEEA60100BA 90 elbow 60 100 EKFGP4660 90 elbow 80 125 EKFGP4810 45 elbow 60 100 EKFGP4661 45 elbow 80 125 EKFGP4811...

Page 23: ...venting 10 If after the venting the pressure decreases below 0 8 bar refill with water until the pressure reaches 0 8 bar again 11 Isolate the appliance from power mains Method 2 For model D2CND024A4A...

Page 24: ...onvert the system for use with a different type of gas 1 Open the front cover of the unit as described in this manual 2 To set natural gas adjust screw on the gas valve to position 1 3 To set LPG adju...

Page 25: ...nit to the main power supply The user interface will be energised 5 4 1 To commission the central heating 1 Set mode to winter mode via Mode button on the user interface and icons are displayed on the...

Page 26: ...5 Check that domestic hot water temperature rise is around 34 C 6 Hand over to the user After completing the installation and commissioning of the system the installer should hand over to the househo...

Page 27: ......

Page 28: ...MA S STEMLER SAN T C A K kbakkalk y Mah Kay da Cad No 1 Kat 21 22 34750 Ata ehir STANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr 3P469346 3E 2017 07...

Reviews: