D-EOMOAH00903-21_01EN - 28 / 37
Alarm String
Description
Possible causes & solutions
This alarm occurs when the
Heat Wheel recovery device
communicate to the controller
(through the digital input
“Heat Wheel Alarm”) that an
alarm state has been
detected
Error on the Heat Wheel
Check the operating manual of the
Heat Wheel
I/O Extension
module: Alarm
Communication malfunction
between the controller and an
expansion module
Causes
Solutions
One or more expansion
modules are not connected
to the controller
Check the wiring connection
between the expansion modules
and the controller
One or more expansion
modules are broken
Change the expansion module
One or more expansion
modules are not configured
properly
Change the DIP switch value (refer
to the wiring diagram)
ERQ 1 alarm:
Alarm
Digital input related to the
ERQ 1 is closed
Causes
Solutions
Error on the ERQ
Check the operating manual of the
ERQ
ERQ 2 alarm:
Alarm
Digital input related to the
ERQ 2 is closed
Causes
Solutions
Error on the ERQ
Check the operating manual of the
ERQ
ERQ 3 alarm:
Alarm
Digital input related to the
ERQ 3 is closed
Causes
Solutions
Error on the ERQ
Check the operating manual of the
ERQ
ERQ 4 alarm:
Alarm
Digital input related to the
ERQ 4 is closed
Causes
Solutions
Error on the ERQ
Check the operating manual of the
ERQ
Emergency
Stop: Alarm
Digital input related to
Emergency stop button is
open
Causes
Solutions
Emergency stop button
pressed
Release the emergency stop
button
6.11 About Unit
About Unit is the last item of the controller main menu and gives general information about the AHU controller.
HMI Path: Main Menu -> About Unit