D-EOMOAH00903-21_01EN 15 / 37
Parameters
Value Range
Description
Temperature:
Cool
10..40 [°C]
Cooling temperature setpoint.
(Available when direct
Htg/Clg
setpoint
control selected)
Heat
10..40 [°C]
Heating temperature setpoint.
(Available when direct
Htg/Clg
setpoint
control selected)
Cool Economy
Cool..40 [°C]
Cooling temperature setpoint in Economy
mode.
(Available when direct
Htg/Clg
setpoint
control selected)
Heat Economy
10..Heat [°C]
Heating temperature setpoint in Economy
mode.
(Available when direct
Htg/Clg
setpoint
control selected)
Central Temp
10..40 [°C]
Central temperature setpoint.
(Available only when temperature regulation
with
deadzone
control selected)
Band Temp
0..20 [°C]
Deadzone
temperature setpoint.
(Available only when temperature regulation
with deadzone control selected)
Central Temp
Economy
Cool..40 [°C]
Central temperature setpoint in Economy
mode.
(Available only when temperature regulation
with deadzone control selected)
Band Temp
Economy
10..Heat [°C]
Deadzone temperature setpoint in Economy
mode.
(Available only when temperature regulation
with deadzone control selected)
Pursuit
10..40 [°C]
Pursuit mode temperature setpoint.
Refer to
Summer/Winter state
for more details.
(Available from Airstream 0.10.B SW version
and only if
Return or Room
temperature
control has been selected)
Pursuit Eco
10..40 [°C]
Pursuit mode temperature economy
setpoint.
Refer to
Summer/Winter state
for more
details.
(Available from Airstream 0.10.B SW version
and only if
Return or Room
temperature
control has been selected)
Pursuit Band
3,5..10 [°C]
Pursuit mode offset temperature setpoint.
This value is added/subtracted from actual
Pursuit setpoint in order to estimate
Summer/Winter changeover tresholds.
Refer
to
Summer/Winter state
for more
details.
(Available from Airstream 0.10.B SW version
and only if Return or Room temperature
control has been selected)
R.U. Offset
-
6…6 [°C]
Display the actual offset set through the
room unit.
(Available only with room unit)
Pre-Heating
0..30 [°C]
Temperature threshold for
Pre-Heating
control activation.