6.4 Active Setpoint
All actual setpoints used by the software to control AHU devices are reported in the
Active Setpoint
page.
In the Main Menu screen is displayed the actual setpoint used for controlled temperature
.
HMI Path: Main Menu -> Active Setpoint
Parameters
Description
Temperature
Display the actual setpoint used for the controlled temperature.
This value is the sum of the basic setpoint (given by
Summer/Winter
state)
plus the offset set through the
Room unit
(R.U.), if present.
-
Summer mode
Temperature = Cool (+ R.U. Offset, if present)
-
Winter mode
Temperature = Heat (+ R.U. Offset, if present)
Supply Fan
Display the actual setpoint value for the supply fan.
This value is the sum of the basic setpoint plus the offset evaluated by the
software for compensation (if a
compensation function is active).
Supply Fan = Supply Fan (+ Comp. Offset, if
active)
Return Fan
Display the actual setpoint value for the return fan.
This value is the sum of the basic setpoint plus the offset evaluated by the
software for compensation (if a
compensation function is active).
Return Fan = Return Fan (+ Comp. Offset, if
active)
Humidification
Display the actual humidification setpoint.
Dehumidification
Display the actual dehumidification setpoint.
Air Quality
Display the actual air quality setpoint.