background image

3

English

This equipment can be installed with a Ground-Fault Cir-
cuit Breaker (GFCI).  Although this is a recognized mea-
sure for additional protection, with the grounding sys-
tem in North America, a dedicated GFCI is not required.

When installing or relocating the system, keep the refriger-
ant circuit free from substances (such as air) other than the
specified refrigerant (R-410A). Any presence of air or other
foreign substance in the refrigerant circuit can cause an ab-
normal pressure rise or rupture, resulting in injury.

Do not change the setting of the protection devices. If the
pressure switch, thermal switch, or other protection device
is shorted and operated forcibly, or parts other than those
specified by Daikin are used, fire or explosion may occur.

Do not touch the switch with wet fingers. Touching
switch with wet fingers can cause electric shock.

To prevent injury, children should never play on or
around the unit.

Do not touch the refrigerant pipes during and immedi-
ately after operation as the refrigerant pipes may be hot
or cold, depending on the condition of the refrigerant
flowing through the refrigerant piping, compressor and
other refrigerant cycle parts. Your hands may suffer
burns or frostbite if you touch the refrigerant pipes. To
avoid injury, give the pipes time to return to normal tem-
perature or, if you must touch them, be sure to wear
proper gloves.

Install drain piping to proper drainage. Improper drain
piping may result in water leakage and property dam-
age.

Insulate piping to prevent condensation.

Be careful when transporting the product.

Do not use a charging cylinder. Using a charging cylin-
der may cause the refrigerant to deteriorate.

Refrigerant R-410A in the system must be kept clean,
dry and tight.

(a)   Clean and Dry — Foreign materials (including min-

eral oils  such as SUNISO oil or moisture) should
be prevented from getting into the system.

(b)   Tight — R-410A does not contain any chlorine, does

not destroy the ozone layer, and does not reduce
the earth’s protection again harmful ultraviolet ra-
diation. R-410A can contribute to the greenhouse
effect if it is released. Therefore take proper mea-
sures to check for the tightness of the refrigerant
piping installation. Read the  

Refrigerant Piping

(section 5) and follow the procedures.

 

Since R-410A is a blend, the required additional refrig-
erant must be charged in its liquid state. If the refriger-
ant is charged in a state of gas, its composition can
change and the system will not work properly.

The indoor unit is for R-410A. See the catalog for indoor
models that can be connected. Normal operation is not
possible when connected to other units.

Remote controller (wireless kit) transmitting distance can
be shorter than expected in rooms with electronic fluo-
rescent lamps (inverter or rapid start types). Install the
indoor unit far away from fluorescent lamps as much as
possible.

Indoor units are for indoor installation only. Outdoor
units can be installed either outdoors or indoors. This
unit is for indoor use.

Do not install the air conditioner or heat pump in the
following locations:

(a)   Where a mineral oil mist or oil spray or vapor is

produced (for example, in a kitchen).

Plastic parts may deteriorate and fall off or result

in water leakage.

(b)

Where corrosive gas, such as sulfurous acid gas,

is produced. Corroding copper pipes or soldered
parts may result in refrigerant leakage.

(c)

Near machinery emitting electromagnetic waves.

Electromagnetic waves may disturb the operation
of the control system and cause the unit to mal-
function.

(d)

Where flammable gas may leak, where there is car-

bon fiber or ignitable dust suspension in the air, or
where volatile flammables such as thinner or gaso-
line are handled. Operating the unit in such condi-
tions can cause a fire.

Take adequate measures to prevent the outside unit from
being used as a shelter by small animals. Small animals
making contact with electrical parts can cause malfunc-
tions, smoke, or fire. Instruct the customer to keep the
area around the unit clean.

Install the power supply and control wires for the indoor
and outdoor units at least 3.5 feet away from televisions
or radios to prevent image interference or noise. Depend-
ing on the radio waves, a distance of 3.5 feet may not be
sufficient to eliminate the noise.

When dismantling the unit, treatment of the refrigerant,
oil and additional parts must be done in accordance with
the relevant local, state and national regulations.

Do not use the following tools that have been previously
used with conventional refrigerants: gauge manifold,
charge hose, gas leak detector, reverse flow check valve,
refrigerant charge base, vacuum gauge or refrigerant re-
covery equipment.

If the conventional refrigerant and refrigerator oil are
mixed in R-410A, the refrigerant may deteriorate.

This air conditioner or heat pump is an appliance that
should not be accessible to the general public.

As design pressure is 450 psi, the wall thickness of field-
installed pipes should be selected in accordance with
the relevant local, state and national regulations.

Summary of Contents for CXTQ24TASBLUA

Page 1: ...LUA CXTQ60TASBLUA INSTALLATION MANUAL ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT...

Page 2: ...or death by suffocation Nails and other metal or wood parts used for packing may cause wounds or other injuries All phases of the field installation including but not lim ited to electrical piping sa...

Page 3: ...composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal operation is not possible when connected to ot...

Page 4: ...e plates together with a rope when lifting to avoid damage or scratches to the unit Be sure to verify the type of R 410A refrigerant to be used before installing the unit Using an incorrect refrigeran...

Page 5: ...nough to bear the indoor unit weight Where piping between indoor and outdoor units is pos sible within the allowable limit Refer to the installa tion manual for the outdoor unit If a return air duct i...

Page 6: ...6 English UPFLOW Figure 2 DOWN FLOW Figure 3...

Page 7: ...insu lation kit DPICX is recommended Insulation kits are available through your local Daikin distributor The DPICX is not supplied with the cased coil and is recommended to mini mize pan sweating in...

Page 8: ...he designated refrigerant such as air to get mixed into the refrigerant circuit If any refrigerant gas leaks while working on the unit immediately ventilate the room 5 1 Cut off the spin closure This...

Page 9: ...lure Reconnect Control Panel wiring to component wiring 5 5 After the work is finished make sure to check that there is no gas leak Follow the VRV Air Tight test procedure in the outdoor unit installa...

Page 10: ...equired run the line separately from the primary drain and end it where conden sate discharge can be easily seen Drain port labeled A in Figure 10 is the primary drain and con densate drain line must...

Page 11: ...ctwork in an area that can intro duce toxic or objectionable fumes odors into the ductwork The return ductwork is to be connected to the gas furnace 8 ELECTRICAL WIRING WORK IMPORTANT All routing of e...

Page 12: ...quipment s unit nameplate power requirements and within the range shown 24 VAC power volt age is supplied to EEV cased coil control board from transformer supply terminals See Figure 13 For appropriat...

Page 13: ...r to the mounting holes of the furnace transformer on the PCB control deck Bracket B should be located between the PCB control deck and furnace transformer Secure innermost bracket mounting location a...

Page 14: ...e may result in malfunction and breakdown Use only specified wire and connect to terminals tightly Be careful that wires do not place external stress on terminals Keep wire in neat order not to obstru...

Page 15: ...Single phase 24V Outdoor Unit MAIN SUB NO 2 SYSTEM For group control or use with 2 remote controllers Figure 18 When one remote controller is used with multiple indoor units which are different model...

Page 16: ...ecification Gauge Length External terminal Contact that can ensure the minimum applicable load of 16 V DC 1mA Table 4 In the case of Forced Off and On Off operation The user can use this function for...

Page 17: ...GS WHEN USING THE OPTIONAL REMOTE SENSOR This product does not include an air inlet thermistor It uses the remote controller thermistor to measure the room temperature For this reason it is necessary...

Page 18: ...30 min 45 min 07 09 11 Run gas furnace during defrost oil return operation Allowed Allowed Allowed Heat pump prohibition duration 15 min 30 min 45 min Factory set This time means the duration which CX...

Page 19: ...T CODE NO SECOND CODE NO LL 01 User set fan speed 02 OFF 03 Factory set 12 22 3 Table 14 NOTE a When fan operation is allowed during heating thermo off careful consideration is required before decidin...

Page 20: ...OFF ON OFF OFF OFF ON OFF ON ON OFF OFF OFF ON ON OFF ON OFF ON ON ON ON ON DS2 OFF OFF OFF OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON ON ON OFF ON ON ON OFF OFF ON OFF OFF ON ON ON Factory...

Page 21: ...rnace s fan operation when the UV lamp or humidifier is operating Refer to Table 18 Terminal Name Input output signal CONTROL ON OFF Outputs indoor unit ON Wet contact 24V 11 5VA or less ECONOMIZER 2...

Page 22: ...refrigerant charge mode etc the gas furnace test will not start c This setting will be returned to factory setting automatically after finishing test operation GAS FURNACE TEST MODE MODE NO FIRST CODE...

Page 23: ...23 English THIS PAGE INTENTIONALLY LEFT BLANK...

Page 24: ...24 English Our continuing commitment to quality products may mean a change in specifications without notice 2017 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com...

Reviews: