background image

16

English

R C

2

1

(SUB)

(MAIN)

Remote

Controller

(Option)

For use with 2

remote controllers

Figure 22

8.6

CONTROL BY 2 REMOTE CONTROLLERS

 Controlling 1 indoor unit by 2 remote controllers

When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”.

Refer to the installation manual of the controller for setting
the “MAIN” and “SUB” controller.

PRECAUTIONS

Daisy chain wiring is needed when using group control
and 2 remote controllers at the same time.

Connect the indoor unit at the end of the crossover wire
(P1, P2) to remote controller 2 (SUB).

Remote controller 1

(MAIN)

Indoor unit 1

Indoor unit 2

Max. No. of

indoor units

Daisy chain wire (P1, P2)

Remote controller 2

(SUB)

Figure 23

8.7

REMOTE CONTROL (FORCED OFF, ON/OFF,
AND SYSTEM/EQUIPMENT PROTECTION
OPERATION)

Connect input lines from the outside to the terminals T1 and T2
on the terminal block (8P) to achieve remote control or Sys-
tem/Equipment Protection.  Use wiring specification Table 4
when making connection to T1/T2.  See Figure 24.

T1

T2

Input A or Alarm Switch

Figure 24

Sheathed vinyl cord or cable (2 wires)
AWG18 - 16
Max. 328 ft.

Wire specification
Gauge
Length

External terminal

Contact that can ensure the minimum
applicable load of 16 V DC, 1mA.

Table 4

 

In the case of Forced Off and On/Off operation

The user can use this function for occupancy sensors, door
switch interlocks etc. (i.e. in hotels so the unit won’t run when
the door is open). When configured as “Forced Off” or “On/
Off”, no error code will be displayed when operating T1/T2.

In the case of System/Equipment Protection

The user can use this function as an alarm switch. When the
alarm switch is open the controller will respond by turning off
the system (including the heat pump and all associated indoor
units). The proper error code will then be displayed on the con-
troller.

See the 

“9.2 REMOTE CONTROL SETTING (T1, T2)” 

for

details on operation.

8.8

AUXILIARY ALARM SWITCH

The CXTQ control board is equipped with two Auxiliary Alarm ter-
minals, labeled TB4 and TB5 (2VA or less) which are typically uti-
lized in series with a condensate switch.

The auxiliary alarm switch must be normally closed. The switch
should only be open when the alarm occurs. For example, a nor-
mally closed condensate switch will open when the base pan’s
water level reaches a particular level. The control will respond by
turning off the blower motor of the affected unit and displaying the
proper fault codes.

Summary of Contents for CXTQ24TASBLUA

Page 1: ...LUA CXTQ60TASBLUA INSTALLATION MANUAL ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT...

Page 2: ...or death by suffocation Nails and other metal or wood parts used for packing may cause wounds or other injuries All phases of the field installation including but not lim ited to electrical piping sa...

Page 3: ...composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal operation is not possible when connected to ot...

Page 4: ...e plates together with a rope when lifting to avoid damage or scratches to the unit Be sure to verify the type of R 410A refrigerant to be used before installing the unit Using an incorrect refrigeran...

Page 5: ...nough to bear the indoor unit weight Where piping between indoor and outdoor units is pos sible within the allowable limit Refer to the installa tion manual for the outdoor unit If a return air duct i...

Page 6: ...6 English UPFLOW Figure 2 DOWN FLOW Figure 3...

Page 7: ...insu lation kit DPICX is recommended Insulation kits are available through your local Daikin distributor The DPICX is not supplied with the cased coil and is recommended to mini mize pan sweating in...

Page 8: ...he designated refrigerant such as air to get mixed into the refrigerant circuit If any refrigerant gas leaks while working on the unit immediately ventilate the room 5 1 Cut off the spin closure This...

Page 9: ...lure Reconnect Control Panel wiring to component wiring 5 5 After the work is finished make sure to check that there is no gas leak Follow the VRV Air Tight test procedure in the outdoor unit installa...

Page 10: ...equired run the line separately from the primary drain and end it where conden sate discharge can be easily seen Drain port labeled A in Figure 10 is the primary drain and con densate drain line must...

Page 11: ...ctwork in an area that can intro duce toxic or objectionable fumes odors into the ductwork The return ductwork is to be connected to the gas furnace 8 ELECTRICAL WIRING WORK IMPORTANT All routing of e...

Page 12: ...quipment s unit nameplate power requirements and within the range shown 24 VAC power volt age is supplied to EEV cased coil control board from transformer supply terminals See Figure 13 For appropriat...

Page 13: ...r to the mounting holes of the furnace transformer on the PCB control deck Bracket B should be located between the PCB control deck and furnace transformer Secure innermost bracket mounting location a...

Page 14: ...e may result in malfunction and breakdown Use only specified wire and connect to terminals tightly Be careful that wires do not place external stress on terminals Keep wire in neat order not to obstru...

Page 15: ...Single phase 24V Outdoor Unit MAIN SUB NO 2 SYSTEM For group control or use with 2 remote controllers Figure 18 When one remote controller is used with multiple indoor units which are different model...

Page 16: ...ecification Gauge Length External terminal Contact that can ensure the minimum applicable load of 16 V DC 1mA Table 4 In the case of Forced Off and On Off operation The user can use this function for...

Page 17: ...GS WHEN USING THE OPTIONAL REMOTE SENSOR This product does not include an air inlet thermistor It uses the remote controller thermistor to measure the room temperature For this reason it is necessary...

Page 18: ...30 min 45 min 07 09 11 Run gas furnace during defrost oil return operation Allowed Allowed Allowed Heat pump prohibition duration 15 min 30 min 45 min Factory set This time means the duration which CX...

Page 19: ...T CODE NO SECOND CODE NO LL 01 User set fan speed 02 OFF 03 Factory set 12 22 3 Table 14 NOTE a When fan operation is allowed during heating thermo off careful consideration is required before decidin...

Page 20: ...OFF ON OFF OFF OFF ON OFF ON ON OFF OFF OFF ON ON OFF ON OFF ON ON ON ON ON DS2 OFF OFF OFF OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON ON ON OFF ON ON ON OFF OFF ON OFF OFF ON ON ON Factory...

Page 21: ...rnace s fan operation when the UV lamp or humidifier is operating Refer to Table 18 Terminal Name Input output signal CONTROL ON OFF Outputs indoor unit ON Wet contact 24V 11 5VA or less ECONOMIZER 2...

Page 22: ...refrigerant charge mode etc the gas furnace test will not start c This setting will be returned to factory setting automatically after finishing test operation GAS FURNACE TEST MODE MODE NO FIRST CODE...

Page 23: ...23 English THIS PAGE INTENTIONALLY LEFT BLANK...

Page 24: ...24 English Our continuing commitment to quality products may mean a change in specifications without notice 2017 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com...

Reviews: