background image

17

English

If the switch is later detected closed for 30 seconds, normal op-
eration resumes and the error message is removed. (The switch
is closed as part of the default factory setting). The error will be
maintained in the equipment’s fault history.

See Figure 25.

TB5

SWITCH

ALARM

TB4

Figure 25

Never use auxiliary alarm function of gas furnace’s PCB.
The function may not operate properly.

8.9

CENTRALIZED CONTROL

For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional controller
for centralized control.

9.

 FIELD SETTING

Field settings may have to be performed using the remote
controller, depending on the type of installation.

1.

Make sure the electric component box covers are closed on
the indoor and outdoor units.

2.

Depending on the type of installation, make the field set-
tings from the remote controller after the power is turned
on, following the “Field Settings” manual which came with
the remote controller.

The settings can select “Mode No.”, “FIRST CODE NO.” and
“SECOND CODE NO.”.

Field settings are normally applied to the entire remote con-
trol group, however if individual indoor units in the remote
control group require specific settings or for confirmation that
settings have been established, utilize the “Mode No.” in pa-
renthesis.

The “Field Settings” included with the remote controller lists
the order of the settings and method of operation.

Make sure the customer keeps the “Field Settings” manual,
along with the operating manual, in a safe place.

9.1

SETTINGS WHEN USING THE OPTIONAL

REMOTE SENSOR

This product does not include an air inlet thermistor. It uses the
remote controller thermistor to measure the room temperature.
For this reason, it is necessary to install an optional remote sen-
sor in the following cases:

When the remote controller will be installed at a location
where it cannot accurately measure the indoor temperature.

When using a remote controller without a built-in thermistor
(simplified remote controller, wireless remote controller, no
remote controller).

When using an optional remote sensor, change the settings
as described Table 5:

ROOM TEMPERATURE

SENSOR SELECTION

MODE

NO.

FIRST

CODE NO.

SECOND

CODE NO.

To use only the remote sensor

02

03*

2

To use only the remote controller
thermistor

10 (20)

*Factory Set

Table 5

Indoor units settings must be changed to Available as per Table
6 when group remote control is used.

Indoor units not using group remote control may remain on fac-
tory settings.

REMOTE CONTROLLER THERMISTOR 

(GROUP CONTROL ONLY)

MODE 

NO.

FIRST CODE 

NO.

SECOND 

CODE NO.

Not Available

01*

Available

02  

*Factory set

10 (20)

6

Table 6

Setting Summary

Without Group Control With Group Control

Without Remote sensor

10(20)-2-03 (*)
10(20)-6-01 (*)

10(20)-2-03 (*)
10(20)-6-02 

With Remote sensor

10(20)-2-02
10(20)-6-01 (*)

10(20)-2-02
10(20)-6-02

 (*) Factory Setting

Table 7

9.2

REMOTE CONTROL SETTING (T1, T2)

Forced Off, ON/OFF operation and System/Equipment Protec-
tion can be selected by selecting the SECOND CODE NO. as
shown in Table 8.

EXTERNAL ON/OFF INPUT

MODE 

NO.

FIRST CODE 

NO.

SECOND 

CODE NO.

Forced Off

01*

ON/OFF Operation

02  

System/Equipment Protection

03  

*Factory set

12 (22)

1

Table 8

Input A of FORCED OFF, ON/OFF and SYSTEM/EQUIPMENT
PROTECTION operates as shown in Table 9.

Summary of Contents for CXTQ24TASBLUA

Page 1: ...LUA CXTQ60TASBLUA INSTALLATION MANUAL ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT...

Page 2: ...or death by suffocation Nails and other metal or wood parts used for packing may cause wounds or other injuries All phases of the field installation including but not lim ited to electrical piping sa...

Page 3: ...composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal operation is not possible when connected to ot...

Page 4: ...e plates together with a rope when lifting to avoid damage or scratches to the unit Be sure to verify the type of R 410A refrigerant to be used before installing the unit Using an incorrect refrigeran...

Page 5: ...nough to bear the indoor unit weight Where piping between indoor and outdoor units is pos sible within the allowable limit Refer to the installa tion manual for the outdoor unit If a return air duct i...

Page 6: ...6 English UPFLOW Figure 2 DOWN FLOW Figure 3...

Page 7: ...insu lation kit DPICX is recommended Insulation kits are available through your local Daikin distributor The DPICX is not supplied with the cased coil and is recommended to mini mize pan sweating in...

Page 8: ...he designated refrigerant such as air to get mixed into the refrigerant circuit If any refrigerant gas leaks while working on the unit immediately ventilate the room 5 1 Cut off the spin closure This...

Page 9: ...lure Reconnect Control Panel wiring to component wiring 5 5 After the work is finished make sure to check that there is no gas leak Follow the VRV Air Tight test procedure in the outdoor unit installa...

Page 10: ...equired run the line separately from the primary drain and end it where conden sate discharge can be easily seen Drain port labeled A in Figure 10 is the primary drain and con densate drain line must...

Page 11: ...ctwork in an area that can intro duce toxic or objectionable fumes odors into the ductwork The return ductwork is to be connected to the gas furnace 8 ELECTRICAL WIRING WORK IMPORTANT All routing of e...

Page 12: ...quipment s unit nameplate power requirements and within the range shown 24 VAC power volt age is supplied to EEV cased coil control board from transformer supply terminals See Figure 13 For appropriat...

Page 13: ...r to the mounting holes of the furnace transformer on the PCB control deck Bracket B should be located between the PCB control deck and furnace transformer Secure innermost bracket mounting location a...

Page 14: ...e may result in malfunction and breakdown Use only specified wire and connect to terminals tightly Be careful that wires do not place external stress on terminals Keep wire in neat order not to obstru...

Page 15: ...Single phase 24V Outdoor Unit MAIN SUB NO 2 SYSTEM For group control or use with 2 remote controllers Figure 18 When one remote controller is used with multiple indoor units which are different model...

Page 16: ...ecification Gauge Length External terminal Contact that can ensure the minimum applicable load of 16 V DC 1mA Table 4 In the case of Forced Off and On Off operation The user can use this function for...

Page 17: ...GS WHEN USING THE OPTIONAL REMOTE SENSOR This product does not include an air inlet thermistor It uses the remote controller thermistor to measure the room temperature For this reason it is necessary...

Page 18: ...30 min 45 min 07 09 11 Run gas furnace during defrost oil return operation Allowed Allowed Allowed Heat pump prohibition duration 15 min 30 min 45 min Factory set This time means the duration which CX...

Page 19: ...T CODE NO SECOND CODE NO LL 01 User set fan speed 02 OFF 03 Factory set 12 22 3 Table 14 NOTE a When fan operation is allowed during heating thermo off careful consideration is required before decidin...

Page 20: ...OFF ON OFF OFF OFF ON OFF ON ON OFF OFF OFF ON ON OFF ON OFF ON ON ON ON ON DS2 OFF OFF OFF OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON ON ON OFF ON ON ON OFF OFF ON OFF OFF ON ON ON Factory...

Page 21: ...rnace s fan operation when the UV lamp or humidifier is operating Refer to Table 18 Terminal Name Input output signal CONTROL ON OFF Outputs indoor unit ON Wet contact 24V 11 5VA or less ECONOMIZER 2...

Page 22: ...refrigerant charge mode etc the gas furnace test will not start c This setting will be returned to factory setting automatically after finishing test operation GAS FURNACE TEST MODE MODE NO FIRST CODE...

Page 23: ...23 English THIS PAGE INTENTIONALLY LEFT BLANK...

Page 24: ...24 English Our continuing commitment to quality products may mean a change in specifications without notice 2017 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com...

Reviews: