background image

21

English

9.8

GAS FURNACE SET UP

Set up for gas furnace is possible by CXTQ’s dip switch only.
Gas furnace’s dip switch is not valid.  Refer to the gas
furnace’s installation manual for details of each setting menu.

If the HEAT OFF delay time was changed to a longer time,
warm up process time of the heat pump may increase.

9.9

CFM TABLE SETTING

Change this setting from “STANDARD” to “LOW” when
connecting CXTQ with the following rated combinations.
Once “Low” is set, the indoor airflow CFM will be equivalent
to one tonnage lower for only heat pump operation.

Combination A

Combination B

Combination C

Outdoor unit

2 ton x 1 unit

3 ton x 1 unit

4 ton x 1 unit

CXTQ

3 ton x 1 unit

4 ton x 1 unit

5 ton x 1 unit

Other indoor unit

N/A

N/A

N/A

AIRFLOW CFM SETTING

MODE 

NO.

FIRST CODE 

NO.

SECOND 

CODE NO.

Standard

  01*

Low

02

*Factory set

13 (23)

5

Table 17

Note: Only rated combinations are allowed to change this setting

9.10

OUTDOOR UNIT SETTINGS

To completely configure the gas furnace, the CXTQ coil needs
to receive a signal from the outdoor unit. Some field settings or
optional PCB might be needed with outdoor unit. See outdoor
unit manuals.

10.

 ACCESSORIES

1.

When installing separately sold accessories, such as a hu-
midifier, economizer, or air purifier (UV lamp), refer to the
installation manual provided with the accessory.

2.

Connect the wires of the separately sold accessory by run-
ning the wiring through the control panel bushing and mak-
ing the wiring connection to the appropriate terminal block.
Refer to the wiring diagram inside the unit.

.

3.

Set the appropriate field settings to adjust the gas furnace’s
fan operation when the UV lamp or humidifier is operating.
Refer to Table 18.

Termina l  Na me 

Input/output s ignal

CONTROL ON/OFF

Outputs : i ndoor unit ON
 (Wet conta ct 24V) 11.5VA or les s

ECONOMIZER 2

Output: i ndoor uni t cooli ng THERMO ON
 (Wet conta ct 24V) 11.5VA or les s

ECONOMIZER 1

Recei ves  input: Economizer opera ti on ON  
 (Dry conta ct)

HUMIDIFIER

Recei ves  input: Humidi fi er opera tion ON   
 (Dry conta ct)

AIR CLEANER

Recei ves  input: Ai r puri fi er opera tion ON   
 (Dry conta ct)

.  UV lamp + humidifier fan speed

This setting controls the blower fan speed when a field in-
stalled UV lamp or humidifier is running.

.  Heat pump standby duration

Once the economizer operation starts, the operation of the
economizer will continue for at least the duration tabulated
in Table 18.

01 02

03

04

05

UV lamp + humidifier fan 
speed

User set 

speed

High

User set 

speed

High

User set 

speed

Heat pump standby duration 
(min)

10

10

20

20

30

OPTIONAL ACCESSORY 

CONFIGURATION

MODE 

NO.

FIRST CODE 

NO.

14 (24)

4

SECOND CODE NO.

06

07

08

09

10

UV lamp + humidifier fan 
speed

High

User set 

speed

High

User set 

speed

High

Heat pump standby duration 
(min)

30

40

40

50

50

SECOND CODE NO.

GAS FURNACE SETTING

MODE 

NO.

FIRST CODE 

NO.

14 (24)

4

11

12

13

14*

UV lamp + humidifier fan 
speed

User set 

speed

High

User set 

speed

High

Heat pump standby duration 
(min)

60

60

Free 

cooling 

only

Free 

cooling 

only

*Factory set

14 (24)

4

SECOND CODE NO.

GAS FURNACE SETTING

MODE 

NO.

FIRST CODE 

NO.

Table 18

10.1

SETTINGS FOR SEPARATELY SOLD
ACCESSORIES

See the instruction manuals included with each of the
optional accessories for the necessary settings.

When using a wireless remote controller

The address of the controller should be assigned during ini-
tial set-up. See the installation manual included with the wire-
less remote controller for details on how to set the address.

Summary of Contents for CXTQ24TASBLUA

Page 1: ...LUA CXTQ60TASBLUA INSTALLATION MANUAL ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL ADJUST SERVICE OR REPAIR HEREINAFTER SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT...

Page 2: ...or death by suffocation Nails and other metal or wood parts used for packing may cause wounds or other injuries All phases of the field installation including but not lim ited to electrical piping sa...

Page 3: ...composition can change and the system will not work properly The indoor unit is for R 410A See the catalog for indoor models that can be connected Normal operation is not possible when connected to ot...

Page 4: ...e plates together with a rope when lifting to avoid damage or scratches to the unit Be sure to verify the type of R 410A refrigerant to be used before installing the unit Using an incorrect refrigeran...

Page 5: ...nough to bear the indoor unit weight Where piping between indoor and outdoor units is pos sible within the allowable limit Refer to the installa tion manual for the outdoor unit If a return air duct i...

Page 6: ...6 English UPFLOW Figure 2 DOWN FLOW Figure 3...

Page 7: ...insu lation kit DPICX is recommended Insulation kits are available through your local Daikin distributor The DPICX is not supplied with the cased coil and is recommended to mini mize pan sweating in...

Page 8: ...he designated refrigerant such as air to get mixed into the refrigerant circuit If any refrigerant gas leaks while working on the unit immediately ventilate the room 5 1 Cut off the spin closure This...

Page 9: ...lure Reconnect Control Panel wiring to component wiring 5 5 After the work is finished make sure to check that there is no gas leak Follow the VRV Air Tight test procedure in the outdoor unit installa...

Page 10: ...equired run the line separately from the primary drain and end it where conden sate discharge can be easily seen Drain port labeled A in Figure 10 is the primary drain and con densate drain line must...

Page 11: ...ctwork in an area that can intro duce toxic or objectionable fumes odors into the ductwork The return ductwork is to be connected to the gas furnace 8 ELECTRICAL WIRING WORK IMPORTANT All routing of e...

Page 12: ...quipment s unit nameplate power requirements and within the range shown 24 VAC power volt age is supplied to EEV cased coil control board from transformer supply terminals See Figure 13 For appropriat...

Page 13: ...r to the mounting holes of the furnace transformer on the PCB control deck Bracket B should be located between the PCB control deck and furnace transformer Secure innermost bracket mounting location a...

Page 14: ...e may result in malfunction and breakdown Use only specified wire and connect to terminals tightly Be careful that wires do not place external stress on terminals Keep wire in neat order not to obstru...

Page 15: ...Single phase 24V Outdoor Unit MAIN SUB NO 2 SYSTEM For group control or use with 2 remote controllers Figure 18 When one remote controller is used with multiple indoor units which are different model...

Page 16: ...ecification Gauge Length External terminal Contact that can ensure the minimum applicable load of 16 V DC 1mA Table 4 In the case of Forced Off and On Off operation The user can use this function for...

Page 17: ...GS WHEN USING THE OPTIONAL REMOTE SENSOR This product does not include an air inlet thermistor It uses the remote controller thermistor to measure the room temperature For this reason it is necessary...

Page 18: ...30 min 45 min 07 09 11 Run gas furnace during defrost oil return operation Allowed Allowed Allowed Heat pump prohibition duration 15 min 30 min 45 min Factory set This time means the duration which CX...

Page 19: ...T CODE NO SECOND CODE NO LL 01 User set fan speed 02 OFF 03 Factory set 12 22 3 Table 14 NOTE a When fan operation is allowed during heating thermo off careful consideration is required before decidin...

Page 20: ...OFF ON OFF OFF OFF ON OFF ON ON OFF OFF OFF ON ON OFF ON OFF ON ON ON ON ON DS2 OFF OFF OFF OFF OFF ON ON OFF OFF ON OFF ON OFF ON OFF OFF ON ON ON ON OFF ON ON ON OFF OFF ON OFF OFF ON ON ON Factory...

Page 21: ...rnace s fan operation when the UV lamp or humidifier is operating Refer to Table 18 Terminal Name Input output signal CONTROL ON OFF Outputs indoor unit ON Wet contact 24V 11 5VA or less ECONOMIZER 2...

Page 22: ...refrigerant charge mode etc the gas furnace test will not start c This setting will be returned to factory setting automatically after finishing test operation GAS FURNACE TEST MODE MODE NO FIRST CODE...

Page 23: ...23 English THIS PAGE INTENTIONALLY LEFT BLANK...

Page 24: ...24 English Our continuing commitment to quality products may mean a change in specifications without notice 2017 5151 San Felipe St Suite 500 Houston TX 77056 www daikincomfort com...

Reviews: