5 Installation

Installation manual

8

ATXM20~50+FTXM20~71N2V1B

Daikin room air conditioner

3P482320-8K – 2018.09

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

5.4.1

To connect the electrical wiring on the
indoor unit

Electrical  work  should  be  carried  out  in  accordance  with  the
installation manual and the national electrical wiring rules or code of
practice.

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

d

c

b

a

a

Mounting plate (accessory)

b

Piece of packing material

c

Interconnection cable

d

Wire guide

INFORMATION

Support the unit using a piece of packing material.

2

Open  the  front  panel,  and  then  the  service  cover.  Refer  to

"5.1 Opening the indoor unit" on page 4

.

3

Pass  the  interconnection  cable  from  the  outdoor  unit  through
the  feed-through  wall  hole,  through  the  back  of  the  indoor  unit
and through the front side.

Note: 

  In  case  the  interconnection  cable  was  stripped  in  advance,

cover the ends with insulating tape.

4

Bend the end of the cable up.

NOTICE

▪ Be  sure  to  keep  the  power  line  and  transmission  line

apart  from  each  other.  Transmission  wiring  and  power
supply wiring may cross, but may NOT run parallel.

▪ In order to avoid any electrical interference the distance

between  both  wirings  should  ALWAYS  be  at  least
50 mm.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

5

Strip the wire ends approximately 15 mm.

6

Match  wire  colours  with  terminal  numbers  on  the  indoor  unit
terminal blocks and firmly screw the wires to the corresponding
terminals.

7

Connect the earth wire to the corresponding terminal.

8

Firmly fix the wires with the terminal screws.

9

Pull  the  wires  to  make  sure  that  they  are  securely  attached,
then retain the wires with the wire retainer.

10

Shape  the  wires  so  that  the  service  cover  fits  securely,  then
close the service cover.

5.5

Finishing the indoor unit
installation

5.5.1

To insulate the drain piping, refrigerant
piping and interconnection cable

1

After the drain piping, refrigerant piping and the electrical wiring
are  finished.  Wrap  refrigerant  pipes,  interconnection  cable  and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant pipes

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

5.5.2

To pass the pipes through the wall hole

1

Shape the refrigerant pipes along the pipe path marking on the
mounting plate.

a

b

c

c

d

e

a

Drain hose

b

Caulk this hole with putty or caulking material.

c

Adhesive vinyl tape

d

Insulation tape

e

Mounting plate (accessory)

NOTICE

▪ Do NOT bend refrigerant pipes.

▪ Do  NOT  push  the  refrigerant  pipes  onto  the  bottom

frame or the front grille.

Summary of Contents for CTXM15N2V1B

Page 1: ...in room air conditioner English Installation manual Daikin room air conditioner CTXM15N2V1B ATXM20N2V1B ATXM25N2V1B ATXM35N2V1B ATXM50N2V1B FTXM20N2V1B FTXM25N2V1B FTXM35N2V1B FTXM42N2V1B FTXM50N2V1B...

Page 2: ...sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v sk...

Page 3: ...erence Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by...

Page 4: ...allation 5 1 Opening the indoor unit 5 1 1 To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Panel tabs 2 Remove the front panel by sliding it to the lef...

Page 5: ...Finish the installation by securing the mounting plate on the wall using M4 25L screws field supply Class 15 42 Class 50 71 INFORMATION The removed pipe port cover can be kept in the mounting plate po...

Page 6: ...over as this would damage the front grille 5 2 4 To provide drainage Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the indoor u...

Page 7: ...drain leakage from the plug a a 4 mm hexagonal wrench 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw otherwise water leakage may occur a b a b a Insulat...

Page 8: ...part from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at...

Page 9: ...the definition of Directive 2014 53 EU INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 5 6 2 To install the wireless LAN adapter on page 9 Basic par...

Page 10: ...ssory 2 To place the wireless LAN adapter into the unit For class 15 42 1 Place the wireless LAN adapter against the hooks 2 Lock the adapter by pressing it down 3 To remove the adapter perform the in...

Page 11: ...ts in the switch box The insulation resistance of the compressor is OK There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks Th...

Page 12: ...CH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GRE...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...3P482320 8K 2018 09 Copyright 2018 Daikin...

Reviews: