5 Installation

Installation manual

6

ATXM20~50+FTXM20~71N2V1B

Daikin room air conditioner

3P482320-8K – 2018.09

i

Outline of back side

j

Outline of front side

5.2.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  (class  15~42)  or  80  mm  (class  50~71)  large
feed-through  hole  in  the  wall  with  a  downward  slope  towards
the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65/80

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

5.2.3

To remove the pipe port cover

To  connect  the  piping  on  right-side,  right-bottom,  left-side  or  left-
bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.2.4

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe  size.

  If  drain  hose  extension  or  embedded  drain  piping  is

required, use appropriate parts that match the hose front end.

Ø16

Ø18

NOTICE

▪ Install the drain hose with a downward slope.

▪ Traps are NOT permitted.

▪ Do NOT put the end of the hose in water.

Drain  hose  extension.

  To  extend  the  drain  hose,  use  a  field

supplied  hose  with  inner  Ø16  mm.  Do  NOT  forget  to  use  a  heat
insulation tube on the indoor section of the extension hose.

a

a

b

c

Ø16

Ø16

a

Drain hose supplied with the indoor unit

b

Heat insulation tube (field supply)

c

Extension drain hose

Rigid polyvinyl chloride pipe.

 When connecting a rigid polyvinyl

chloride pipe (nominal Ø13 mm) directly to the drain hose as with
embedded piping work, use a field supplied drain socket (nominal
Ø13 mm).

a

b

c

Ø18

a

Drain hose supplied with the indoor unit

b

Drain socket with nominal Ø13 mm (field supply)

c

Rigid polyvinyl chloride pipe (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

1

Insert the drain hose in the drain pipe as shown in the following
figure, so it will NOT be pulled out of the drain pipe.

≥50

mm

Summary of Contents for CTXM15N2V1B

Page 1: ...in room air conditioner English Installation manual Daikin room air conditioner CTXM15N2V1B ATXM20N2V1B ATXM25N2V1B ATXM35N2V1B ATXM50N2V1B FTXM20N2V1B FTXM25N2V1B FTXM35N2V1B FTXM42N2V1B FTXM50N2V1B...

Page 2: ...sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v sk...

Page 3: ...erence Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by...

Page 4: ...allation 5 1 Opening the indoor unit 5 1 1 To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it a a Panel tabs 2 Remove the front panel by sliding it to the lef...

Page 5: ...Finish the installation by securing the mounting plate on the wall using M4 25L screws field supply Class 15 42 Class 50 71 INFORMATION The removed pipe port cover can be kept in the mounting plate po...

Page 6: ...over as this would damage the front grille 5 2 4 To provide drainage Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the indoor u...

Page 7: ...drain leakage from the plug a a 4 mm hexagonal wrench 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw otherwise water leakage may occur a b a b a Insulat...

Page 8: ...part from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at...

Page 9: ...the definition of Directive 2014 53 EU INFORMATION Install the wireless LAN adapter after finishing the indoor unit installation Refer to 5 6 2 To install the wireless LAN adapter on page 9 Basic par...

Page 10: ...ssory 2 To place the wireless LAN adapter into the unit For class 15 42 1 Place the wireless LAN adapter against the hooks 2 Lock the adapter by pressing it down 3 To remove the adapter perform the in...

Page 11: ...ts in the switch box The insulation resistance of the compressor is OK There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks Th...

Page 12: ...CH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GRE...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...3P482320 8K 2018 09 Copyright 2018 Daikin...

Reviews: