SWITCHING FROM ONE DRIVER TO 

ANOTHER 

Press the Help and Enter keys simultaneously. Forced switching 

during parameter programming leads to displaying the parameters 

of driver A and driver B on the same screen.

Procedure 

NOTE:

 The S1 probe parameter is common to both drivers, 

the main control parameter is set for each driver. 

DISPLAY MODE

The Display mode allows to display the variables useful to know 

the system operation.

The variables displayed depend on the type of control chosen.

1. Press Esc one or more times to go to the standard display.

2. Select the driver A or B for which you want to display the 

variables (see par. 3.3);

3. Press UP/DOWN: the display shows a graph of the superheat 

variables, the valve opening percentage, the evaporating 

temperature and pressure and the suction temperature;

4. Press UP/DOWN: the display variables appear and in the 

queue the displays of the electrical connections of the probes 

and valve motors;

5. Press Esc to exit the Display mode.

6. For the complete list of the variables used according to the 

type of control.

PROGRAMMING MODE (DISPLAY)

Parameters can be changed via the front keypad. Access is 

different depending on the user level: support (installer) and 

manufacturer parameters.

Modification of the Assistance parameters.

The Support parameters, as well as the parameters for controller 

start-up, also include those for input configuration, output relay, 

overheating set point or control type in general and protection 

thresholds. 

Procedure:

1. Press Esc one or more times to go to the standard display 

and select the driver A or B from which you want to modify the 

parameters.

2. Press Prg: the display shows a screen asking for the 

PASSWORD.

3. Press ENTER and enter the password for the Assistance level, 

starting from the rightmost digit and confirming each digit with 

ENTER;

4. If the value entered is correct, the first modifiable parameter 

appears: network address.

5. Press UP/DOWN to select the parameter to be modified.

6. Press ENTER to move to the parameter value.

7. Press UP/DOWN to change the value.

8. Press ENTER to save the new parameter value.

9. Repeat steps 5, 6, 7, 8 to modify the other parameters.

10.  Press Esc to exit the procedure for modifying the Assistance 

parameters. The display automatically returns to the standard 

mode.

NOTES:

- If an out-of-range value is inserted during the configuration 

of a parameter, it is not accepted and after a short 

time the parameter returns to the value preceding 

the modification.

Control

Summary of Contents for Comfort Flex CLIWP Series

Page 1: ...Control Manual Model 3 RT 5 RT Refrigerant HFC 410A 60 Hz CM Group Wall Mounted Package Part Number CLIWP CM Date 29 May 2023 CLIWP Series Direct Expansion Unit with Scroll Compressor...

Page 2: ...ion and data cover the Comfort Flex product at the time of publication and we reserve the right to make changes in design and construction at any time without notice Manufactured in an ISO 9001 certif...

Page 3: ...ire WARNING If refrigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry relate...

Page 4: ...anel NOMENCLATURE CLIWP 036 U F L C T C A P 1 N C D M 1 4 0 FAMILY CAPACITY BTU 036 36 000 Btu H 060 60 000 Btu H DISCHARGE AIR U Upper COMPRESSOR F Fixed COMPRESSOR SIDE L Left R Right VOLTAGE C 208...

Page 5: ...ngent quality standards ASTM B117 1500 hour salt spray test The selection of high end compressors and heat exchangers ensures the capacity and high efficiency of the equipment All our equipment has a...

Page 6: ...3 C Dry load TECHNICAL FEATURES ElectroFin E Coat Coil coating corrosion resistant factory applied ElectroFin E Coat is a flexible water based cationic epoxy polymer using an electrodeposition coating...

Page 7: ...t the system to almost any cloud service either to upload historical data to analysis services deliver alarm messages to alarm processing services or to operate parts of the control system via a cloud...

Page 8: ...next field 3 Finally navigate to Save and Restart and press 4 Confirm the reboot and the device will reboot with the new IP address To set the BACnet device ID through the LCD display 1 On the main L...

Page 9: ...ograms LOYTEC LINX Configurator LOYTEC LINX Configurator The application starts and displays the data point manager screen as shown in Figure 7 2 When the device is online connect to the device by cli...

Page 10: ...2 1 AP Compressor APdx 24 VAC Relay DO 3 1 AC Free Cooling ACf 0 10 VDC AO 1 1 Zone Temp TZ LSTAT MODBUS RTU Total points per Ctrl 3 3 1 3 0 3 To adapt the I O name double click on the name in the Nam...

Page 11: ...nfigured so that the equipment can be turned on and the system points can be modified The following describes the use of the LSTAT thermostat as shown in Fig 9 and the indicators it contains in this c...

Page 12: ...RMS The CLIWP system has 3 alarms The first alarm is triggered by the low pressure switch and the second alarm is triggered by the high pressure switch these alarms are digital signals which are progr...

Page 13: ...ont keypad Access is different depending on the user level support installer and manufacturer parameters Modification of the Assistance parameters The Support parameters as well as the parameters for...

Page 14: ...ard display after 5 minutes NETWORK ADDRESS The network address assigns the controller an address for serial connection to a supervisory system via RS485 and to a pCO controller via pLAN tLAN Modbus I...

Page 15: ...menu Unlike the pressure probes the temperature probes do not have any parameters corresponding to the measuring range that can be changed and therefore only the models listed can be used see the cha...

Page 16: ...nly when heating or cooling In the ON position the fan will run constantly at all times with or without a heating or cooling demand Multifunction slide switch It provides easy access to common setting...

Page 17: ...me delay 5 default The thermostat waits 5 minutes before turning the system back on after the last time it was turned on This internal delay prevents rapid cycling and provides wallpack protection The...

Page 18: ...cm cliwp eng www comfort flex com...

Reviews: