background image

cm-cliwp-eng

www.comfort-flex.com

14

MODIFICATION OF THE MANUFACTURER’S 

PARAMETERS

The Manufacturer level allows the configuration of all controller 

parameters, and therefore, in addition to the Assistance 

parameters, the parameters corresponding to the management of 

alarms, probes and valve configuration. 

Procedure:

1. Press Esc one or more times to go to the standard display.

2. Select the A or B driver for which you want to change the 

parameters.

3. Press Prg: the display shows a screen asking for the 

PASSWORD;

4. Press ENTER and enter the password for the Manufacturer 

level: 66, starting from the rightmost digit and confirm each 

digit with ENTER.

5. If the value entered is correct, the list of parameter categories 

appears:

• Configuration

• Probes

• Control

• Special

• Alarm configuration

• Valve

6. Press UP/DOWN to select the category and ENTER to access 

the first parameter of the category.

7. Press UP/DOWN to select the parameter to be changed and 

ENTER to move to the parameter value.

8. Press UP/DOWN to modify the value.

9. Press ENTER to save the new parameter value.

10.  Repeat steps 7, 8 and 9 to modify the other parameters.

11.  Press ESc to exit the Manufacturer parameter modification 

procedure.

NOTES:

- The entry at the Manufacturer level allows modification of 

all controller parameters.

- If an out-of-range value is entered during the configuration 

of a parameter, it is not accepted and the parameter 

returns to the value before the modification after a 

short time.

- If no key is pressed, the display automatically returns to the 

standard display after 5 minutes.

NETWORK ADDRESS 

The network address assigns the controller an address for serial 

connection to a supervisory system via RS485 and to a pCO 

controller via pLAN, tLAN, Modbus®. It is a common parameter for 

both driver A and B.

Parameter/description

Predet.

Min

Max

UM

Configuration 

Network address

198

1

207

-

In the case of network connection of the RS485/Modbus® models, 

it is also necessary to set the communication speed in bits per 

second, by means of the parameter “Network settings.

REFRIGERANT

The type of refrigerant is essential for the calculation of superheat. 

It is also used to calculate the evaporating and condensing 

temperature from the pressure probe measurement.

Parameter/description

Predet.

Configuration 

Refrigerant

R404A

VALVE

By setting the valve type, all the control parameters are automatically 

defined based on the construction data of each model. In the 

manufacturer’s programming mode it will then be possible to fully 

customize the control parameters in case the valve used is not 

present in the predefined list. In such a case, the controller will 

indicate the modification by marking the valve type as “Custom”. 

Parameter/description

Predet.

Configuration 

Valve:

CAREL

1= CAREL ExV;

EXV

- If no key is pressed, the display automatically returns to the 

standard display after 5 minutes.

- To set a negative value, position with Enter on the leftmost 

digit and press Up/Down.

NOTES:

-  The  configuration  of  two  CAREL  ExV  valves  connected 

together  must  be  selected  whenever  two  CAREL 

ExV valves are to be connected to the same terminal, 

to achieve parallel or complementary operation;

-  As indicated above, regulation is only possible with CAREL 

ExV valves;

-  Not all CAREL valves can be connected.

Control

Summary of Contents for Comfort Flex CLIWP Series

Page 1: ...Control Manual Model 3 RT 5 RT Refrigerant HFC 410A 60 Hz CM Group Wall Mounted Package Part Number CLIWP CM Date 29 May 2023 CLIWP Series Direct Expansion Unit with Scroll Compressor...

Page 2: ...ion and data cover the Comfort Flex product at the time of publication and we reserve the right to make changes in design and construction at any time without notice Manufactured in an ISO 9001 certif...

Page 3: ...ire WARNING If refrigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry relate...

Page 4: ...anel NOMENCLATURE CLIWP 036 U F L C T C A P 1 N C D M 1 4 0 FAMILY CAPACITY BTU 036 36 000 Btu H 060 60 000 Btu H DISCHARGE AIR U Upper COMPRESSOR F Fixed COMPRESSOR SIDE L Left R Right VOLTAGE C 208...

Page 5: ...ngent quality standards ASTM B117 1500 hour salt spray test The selection of high end compressors and heat exchangers ensures the capacity and high efficiency of the equipment All our equipment has a...

Page 6: ...3 C Dry load TECHNICAL FEATURES ElectroFin E Coat Coil coating corrosion resistant factory applied ElectroFin E Coat is a flexible water based cationic epoxy polymer using an electrodeposition coating...

Page 7: ...t the system to almost any cloud service either to upload historical data to analysis services deliver alarm messages to alarm processing services or to operate parts of the control system via a cloud...

Page 8: ...next field 3 Finally navigate to Save and Restart and press 4 Confirm the reboot and the device will reboot with the new IP address To set the BACnet device ID through the LCD display 1 On the main L...

Page 9: ...ograms LOYTEC LINX Configurator LOYTEC LINX Configurator The application starts and displays the data point manager screen as shown in Figure 7 2 When the device is online connect to the device by cli...

Page 10: ...2 1 AP Compressor APdx 24 VAC Relay DO 3 1 AC Free Cooling ACf 0 10 VDC AO 1 1 Zone Temp TZ LSTAT MODBUS RTU Total points per Ctrl 3 3 1 3 0 3 To adapt the I O name double click on the name in the Nam...

Page 11: ...nfigured so that the equipment can be turned on and the system points can be modified The following describes the use of the LSTAT thermostat as shown in Fig 9 and the indicators it contains in this c...

Page 12: ...RMS The CLIWP system has 3 alarms The first alarm is triggered by the low pressure switch and the second alarm is triggered by the high pressure switch these alarms are digital signals which are progr...

Page 13: ...ont keypad Access is different depending on the user level support installer and manufacturer parameters Modification of the Assistance parameters The Support parameters as well as the parameters for...

Page 14: ...ard display after 5 minutes NETWORK ADDRESS The network address assigns the controller an address for serial connection to a supervisory system via RS485 and to a pCO controller via pLAN tLAN Modbus I...

Page 15: ...menu Unlike the pressure probes the temperature probes do not have any parameters corresponding to the measuring range that can be changed and therefore only the models listed can be used see the cha...

Page 16: ...nly when heating or cooling In the ON position the fan will run constantly at all times with or without a heating or cooling demand Multifunction slide switch It provides easy access to common setting...

Page 17: ...me delay 5 default The thermostat waits 5 minutes before turning the system back on after the last time it was turned on This internal delay prevents rapid cycling and provides wallpack protection The...

Page 18: ...cm cliwp eng www comfort flex com...

Reviews: