Once the evaporator fan start time is over, the condenser fan will 

start and then the compressor will start, during the process of these 

last two steps the following icons will be displayed.

Once the system is turned on, the temperature 

of the site can be observed from the main 

screen.

To change the temperature set point, press the icon 

shown below on the thermostat.

Once the previous step is done, the display screen will change.

Entering the screen with the SPT legend, the up and down keys 

can be used to change the desired value from the LSTAT.

Once the above steps have been performed and the desired set 

point has been selected, if you need to go back to the main screen, 

press the menu button mentioned above again.

Free cooling:

The CLIWP system has a free cooling working mode which has the 

function of detecting when the outdoor temperature is lower than 

the indoor temperature, so when the temperature probe reflects 

these values it automatically turns off the condenser fan and the 

compressor in order to let the air in through the damper with the 

help of the evaporator fan. When this action happens the display 

will change to green and show the following icon:

Control

LOYTEC CONTROLLER ALARMS

The CLIWP system has 3 alarms: The first alarm is triggered by 

the low pressure switch and the second alarm is triggered by the 

high pressure switch, these alarms are digital signals which are 

programmed so that when an event happens where either of the 

2 pressure switches becomes open at that moment the controller 

stops the operation of the system allowing the compressor work not 

to continue until both the high and low pressure has been restored. 
The third alarm is a digital signal which is activated by the phase 

monitoring device, which has the function of activating an electrical 

signal to the controller at the time it detects an over current or an 

unbalance of electric current. 
The way in which the system detects the faults is through the 

LSTAT digital thermostat interface which, as soon as there is an 

alarm in the system caused by any of the 3 conditions mentioned 

above, will show an alarm icon as shown in Figure 10. 

  Figure 6.  Alarm

When a high pressure or low pressure alarm is activated, the 

system will initiate an auto reset routine which has the function 

to allow it to work without the need to reset it from the thermostat, 

the allowed number of auto reset is 3 times after having fulfilled 

these conditions, the system will alarm and as a consequence it 

will completely stop the system operation showing an icon in the 

display as the following one:

When this alarm occurs, the icon in the image 

must be pressed.

Summary of Contents for Comfort Flex CLIWP Series

Page 1: ...Control Manual Model 3 RT 5 RT Refrigerant HFC 410A 60 Hz CM Group Wall Mounted Package Part Number CLIWP CM Date 29 May 2023 CLIWP Series Direct Expansion Unit with Scroll Compressor...

Page 2: ...ion and data cover the Comfort Flex product at the time of publication and we reserve the right to make changes in design and construction at any time without notice Manufactured in an ISO 9001 certif...

Page 3: ...ire WARNING If refrigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry relate...

Page 4: ...anel NOMENCLATURE CLIWP 036 U F L C T C A P 1 N C D M 1 4 0 FAMILY CAPACITY BTU 036 36 000 Btu H 060 60 000 Btu H DISCHARGE AIR U Upper COMPRESSOR F Fixed COMPRESSOR SIDE L Left R Right VOLTAGE C 208...

Page 5: ...ngent quality standards ASTM B117 1500 hour salt spray test The selection of high end compressors and heat exchangers ensures the capacity and high efficiency of the equipment All our equipment has a...

Page 6: ...3 C Dry load TECHNICAL FEATURES ElectroFin E Coat Coil coating corrosion resistant factory applied ElectroFin E Coat is a flexible water based cationic epoxy polymer using an electrodeposition coating...

Page 7: ...t the system to almost any cloud service either to upload historical data to analysis services deliver alarm messages to alarm processing services or to operate parts of the control system via a cloud...

Page 8: ...next field 3 Finally navigate to Save and Restart and press 4 Confirm the reboot and the device will reboot with the new IP address To set the BACnet device ID through the LCD display 1 On the main L...

Page 9: ...ograms LOYTEC LINX Configurator LOYTEC LINX Configurator The application starts and displays the data point manager screen as shown in Figure 7 2 When the device is online connect to the device by cli...

Page 10: ...2 1 AP Compressor APdx 24 VAC Relay DO 3 1 AC Free Cooling ACf 0 10 VDC AO 1 1 Zone Temp TZ LSTAT MODBUS RTU Total points per Ctrl 3 3 1 3 0 3 To adapt the I O name double click on the name in the Nam...

Page 11: ...nfigured so that the equipment can be turned on and the system points can be modified The following describes the use of the LSTAT thermostat as shown in Fig 9 and the indicators it contains in this c...

Page 12: ...RMS The CLIWP system has 3 alarms The first alarm is triggered by the low pressure switch and the second alarm is triggered by the high pressure switch these alarms are digital signals which are progr...

Page 13: ...ont keypad Access is different depending on the user level support installer and manufacturer parameters Modification of the Assistance parameters The Support parameters as well as the parameters for...

Page 14: ...ard display after 5 minutes NETWORK ADDRESS The network address assigns the controller an address for serial connection to a supervisory system via RS485 and to a pCO controller via pLAN tLAN Modbus I...

Page 15: ...menu Unlike the pressure probes the temperature probes do not have any parameters corresponding to the measuring range that can be changed and therefore only the models listed can be used see the cha...

Page 16: ...nly when heating or cooling In the ON position the fan will run constantly at all times with or without a heating or cooling demand Multifunction slide switch It provides easy access to common setting...

Page 17: ...me delay 5 default The thermostat waits 5 minutes before turning the system back on after the last time it was turned on This internal delay prevents rapid cycling and provides wallpack protection The...

Page 18: ...cm cliwp eng www comfort flex com...