Sequence Of Operation
Figure 16. Sequence of operation of the unit - Cool mode.
Unit Power up
Unit in OFF state
Is unit
enabled?
No
No
Yes
Is motor
saver alarm
active?
Yes
Is switch
“Reset”
button
on?
No
Evaporator pump
output on
Is flow
present?
No
Wait the time for the
start up compressor
The contactor auxiliar
remains on while chiller
is enabled
Is the protection
module or
frecuency
variator of the
compressor
active?
Keep pump and auxiliary
output on while the
chiller is enabled
Is there
enough
load to
start
chiller?
Start the circuit
Operation of circuit in
stabilization
Yes
No
No
Yes
1
Yes
1
1
2