background image

iom-cliv-cf-eng

www.clima-flex.com

11

CAUTION  

!

Adding glycol or draining the system is the recommended 

method of freeze protection. If the chiller does not have 

the ability to control the pumps and the water system is not 

drained or does not have adequate glycol at subfreezing 

temperatures, catastrophic evaporator failure can occur.

FLOW SWITCH

All chillers require a chilled water flow switch to verify that there 

is adequate water flow through the evaporator and to shut down 

the unit if necessary to prevent evaporator freeze-up under low or 

no flow conditions. 
A factory-installed thermal dispersion flow switch will be installed 

on packaged models. On remote evaporator models, the flow 

switch can be supplied separately in the field, or optionally 

shipped loose for field installation. 
Terminals for field mounting and wiring of the water flow switch 

are provided in the unit control center. 

Wire from the Y and R terminals on the switch to the terminals on 

the unit control panel shown in the field wiring diagrams, page 20 

through page 23. Mount the flow switch on the outlet water line 

to shut off the unit when water flow is interrupted. A flow switch 

is an equipment protection control and should never be used to 

cycle the unit. 
Installation should be in accordance with the manufacturer’s 

instructions included with the switch. Flow switches should be 

calibrated to shut the unit off when operating below the minimum 

flow rate. 
There is also a set of paddle switch contacts on the switch that 

can be used for an indicator light or alarm to indicate when a “no 

flow” condition exists. Protect any flow switches that are installed 

outdoors from freezing. It is not recommended that differential 

pressure switches be installed outdoors. They may freeze and 

not indicate a no-flow condition.

EVAPORATOR FREEZE PROTECTION

Evaporator freezing can be a problem in the application of air-

cooled water chillers in sub-zero temperature areas. To protect 

against freezing, the evaporator comes with insulation and an 

electric heater. 
Although the evaporator is equipped with freeze protection, 

it does not protect the water piping external to the unit or the 

evaporator itself if there is a power failure or the heater burns out, 

or if the chiller cannot control the chilled water pumps. Use one of 

the following recommendations for additional freeze protection:

COLD WATER PUMP 

It is important that the chilled water pumps are connected to 

and controlled by the chiller microprocessor. The controller will 

activate the pump whenever at least one chiller circuit is enabled 

for operation, whether there is a call for cooling or not. 
This helps ensure proper start-up sequencing of the unit. The 

pump will also turn on when the water temperature is below the 

freeze set point for longer than the specified time to help prevent 

evaporator freeze-up. Connection points are shown in the field 

wiring diagram beginning on page 20+.

1. If the unit will not operate during the winter, drain the evapora-

tor and cold water lines and flush them with glycol.

2. Add a glycol solution to the chilled water system. Breakage 

protection should be approximately 10°F below the minimum 

design ambient temperature.

3. Insulate exposed piping.

4. Add thermostatically controlled heat by wrapping lines with 

heat tape. 

5. When glycol is added to the water system for freeze protec-

tion, the refrigerant suction pressure will be lower, the cooling 

performance will be lower, and the water side pressure drop 

will be higher. 

If the chiller is not allowed to control the pump, the following 

problems may occur:

1. if the chiller attempts to start without first starting the pump, 

the chiller will lock out with the no flow alarm and require a 

manual restart.

2. If the chiller evaporator water temperature drops below the 

“freezing set point”, the chiller will attempt to start the water 

pumps to prevent the evaporator from freezing.

3. If the chiller does not have the ability to start the pumps, the 

chiller will alarm for lack of water flow. 

4. If the chiller does not have the ability to control the pumps 

and the water system must not be drained in sub-zero tem-

peratures or contain glycol, the chiller may be subject to cat-

astrophic evaporator failure due to freezing. The evaporator 

freeze-up rate is based on the evaporator heater and pump 

operation. The external brazed plate heater alone may not 

be able to adequately protect the evaporator from freezing 

without water circulation.

CAUTION  

!

Improper use of detergents, chemicals and additives in the 

cooling system water can adversely affect the performance 

of the chiller and potentially result in repair costs not covered 

under warranty. Any decision to use these products is at 

the discretion of the owner/occupant/operator/user, and the 

owner/occupant/operator/user assumes full responsibility for 

any damage that may occur due to their use.

gpm” is often used. A storage tank may have to be added to the 

system to achieve the recommended volume.

The quality of water supplied by the owner/occupant/operator/

user to a cooling system should minimize corrosion, scale buildup, 

erosion, and biological growth to achieve optimum efficiency 

of HVAC equipment without creating a DANGER for operating 

personnel or the environment. 
Filters should be used to protect cooling systems from waterborne 

debris. Clima Flex is not responsible for damage caused by 

waterborne debris or damage to chiller heat exchangers due to 

improper water treatment. 
Water systems must be cleaned and flushed prior to chiller 

installation. Water testing and treatment should be verified during 

initial chiller installation/commissioning and should be maintained 

on an ongoing basis by water treatment professionals. 

Installation and Application Information

Summary of Contents for Clima-Flex CLIV Series

Page 1: ...Operation and Maintenance Manual IOM Group Chiller Part number IOM CLIV Date 16 November 2022 CLIV Series Air Cooled Fixed Compressor Chilled Water Chiller Unit Model 3 5 and 10 TR Refrigerant HFC 41...

Page 2: ...Controller Operation 24 Sequence Of Operation 26 Funciones De La Unidad 30 Funciones De Los Circuitos 31 Alarmas 33 Uso Del Controlador 35 Procedimientos De Arranque Y Apagado 38 Mantenimiento De La U...

Page 3: ...rtup Cooler components EXV sensor transducers installed and wired properly Wiring complies with National Electrical Code and local codes See Notes Various Si No N A Iniciales Unit control disconnects...

Page 4: ...rigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry related standards and lo...

Page 5: ...0 060 60 000 120 120 000 AIR DISCHARGE HD Horizontal Discharge OPERATION C Cooling Only H Heat Pump UNITS 1 Stand alone CONDENSER FAN A Axial Fixed ANTICORROSION C Coat in Condenser I Coat in Componen...

Page 6: ...tions DANGER Improper rigging lifting or moving of a unit can result in property damage serious personal injury or death Follow the rigging and moving instructions carefully Do not stand under the uni...

Page 7: ...ation of fans and compressors The noise level for each unit size model is listed in the technical documentation If the unit is properly installed operated and regularly maintained the noise levels do...

Page 8: ...f wall openness is less than recommended for the distance to the unit it should be considered a solid wall The wall height is assumed to be equal to or less than the height of the unit when mounted on...

Page 9: ...evaporators must have a drain and vent connection at the bottom of the bottom connection piping and at the top of the top connection piping respectively see Figure 6 These evaporators do not have dra...

Page 10: ...tes below the minimum values can result in laminar flow leading to low pressure alarms fouling and poor temperature control Variable evaporator flow Reducing the evaporator flow rate in proportion to...

Page 11: ...for longer than the specified time to help prevent evaporator freeze up Connection points are shown in the field wiring diagram beginning on page 20 1 If the unit will not operate during the winter d...

Page 12: ...ith a series of flat tubes containing multiple parallel flow microchannels placed between the coolant manifolds The microchannel coils are designed to withstand the synthetic acidified seawater acidif...

Page 13: ...iom cliv cf eng www clima flex com 13 Figure 8 Refrigeration Schematics CLIV Refrigeration Schematics...

Page 14: ...iom cliv cf eng www clima flex com 14 Refrigeration Schematics Figure 9 CLIV heat pump cooling scheme...

Page 15: ...iom cliv cf eng www clima flex com 15 Figure 10 CLIV Dimensions and Weights Packaged Units...

Page 16: ...iom cliv cf eng www clima flex com 16 Dimensions and Weights Packaged Units Figure 11 CLIV heat pump...

Page 17: ...en open the register1 Fig 12 Subsequently isolate the vacuum pump and open the register 2 When a value of less than 200 mecrons is obtained try to reach the lowest possible value the vacuum procedure...

Page 18: ...E EVAPORATOR DROP TOTAL DROP DP ft WG DP ft WG 3 UNIT 16 7 32 5 UNIT 16 7 32 10 DUPLEX 16 7 32 Table 5 Evaporator Pressure Drop Data FAMILY TR R410A Lb R410A Kg CLIV 3 TR 3 56 1 61 CLIV 5 TR 3 52 1 60...

Page 19: ...gram 3 The single point power supply requires a single disconnect to supply electrical power to the unit This power supply must have a fuse or use a circuit breaker 4 All field wiring terminal range v...

Page 20: ...iom cliv cf eng www clima flex com 20 Electrical Data Figure 13 Typical field wiring diagram of the 220v slave only cold unit single point connection with all options shown...

Page 21: ...iom cliv cf eng www clima flex com 21 Electrical Data...

Page 22: ...iom cliv cf eng www clima flex com 22 Electrical Data Figure 14 Typical field wiring diagram of the 440v slave single cold unit single point connection with all options shown...

Page 23: ...iom cliv cf eng www clima flex com 23 Electrical Data...

Page 24: ...reless connectivity with mobile devices and is integrated on panel mounted models and purchased separately on DIN rail mounted models SYSTEM ARCHITECTURE The general architecture of the controls uses...

Page 25: ...essor 2 NO3 MC 95 Water pump NO4 B 24V2 4 way valve NO5 Output available for alarm connection SET POINTS When we start configuring the unit for the first time all the preload parameters have a default...

Page 26: ...et button on No Evaporator pump output on Is flow present No Wait the time for the start up compressor The contactor auxiliar remains on while chiller is enabled Is the protection module or frecuency...

Page 27: ...y Increase unit capacity Unit turn up full capacity Operation of circuit in stabilization Unit turn down full capacity Decrease unit capacity Is unit running at minimun capacity No No Yes No No Yes Ye...

Page 28: ...Reset button on No Evaporator pump output on Is flow present No Wait the time for the start up compressor The contactor auxiliar remains on while chiller is enabled Is the protection module or frecuen...

Page 29: ...y Increase unit capacity Unit turn up full capacity Operation of circuit in stabilization Unit turn down full capacity Decrease unit capacity Is unit running at minimun capacity No No Yes No No Yes Ye...

Page 30: ...CONTROLLER CALCULATIONS Condenser approach The capacitor approximation will be calculated for each circuit The equation is as follows Capacitor approximation Capacitor saturated temperature OAT Sucti...

Page 31: ...s capacity control logic commands it to shut down A discharge alarm occurs and sequencing requires this compressor to be the next compressor to shut down The circuit status is pumping and sequencing...

Page 32: ...frosted equalizer line indicates internal leaks and will require valve replacement Repair or replacement of a bent equalizer will be necessary for the valve to operate properly TXVs are designed to m...

Page 33: ...log If the alarm is automatically reset the alarm key is turned off the alarm code disappears from the list and the alarm termination event is recorded in the alarm log Procedure alarm acknowledgement...

Page 34: ...ther with the current pump configuration A15 This alarm usually appears when the water temperature does not drop due to the current cooling process This alarm is more of a WARNING than a serious alarm...

Page 35: ...e top row the flow water temperature In the bottom row with the unit switched on the return water temperature With the unit switched off the OFF status during Bluetooth communication the text bLE flas...

Page 36: ...rs such as direct commands and active alarms can be accessed through the user terminal without password or with password to those dedicated to unit configuration and optimization Press DOWN for 3 s to...

Page 37: ...t pump units Press DOWN the manual defrost command dFr appears Press DOWN the command to cancel the alarm log ClrH appears Assistance level only Press DOWN the selection of units of measurement UoM ap...

Page 38: ...ydraulic circuit is closed Check for foreign objects in the fan discharge Check that the air inlet is not obstructed and has the suggested clearance INSPECTION OF THE HYDRAULIC CIRCUIT Date Place of W...

Page 39: ...ions Measure voltage on all units ground neutral and 3 phase line Check that motor overload protection conforms to design requirements and is in automatic mode Check voltage Motor save which is set to...

Page 40: ...turned on Turn the switch on the CONTROL UNIT to the ON position to power the control panel with 24 volts UNIT CONTROL To start operations turn the ON OFF switch to the ON position After 6 seconds th...

Page 41: ...onsible for the malfunction of the unit if the main cause is lack of maintenance or the operating conditions of the unit do not correspond to those recommended in this manual MAINTENANCE GENERAL Routi...

Page 42: ...ay start up and cause injury Disconnect all power sources before inspecting the fan EXPANSION VALVE The function of the expansion valve is to maintain adequate supply of refrigerant to the evaporator...

Page 43: ...these must be under the manufacturer s specifications Twice a month Plan x x x x x x Real Cleaning of the electrical panel monthly Plan x x x x x x x x x x x x Real PHYSICAL INSPECTION Jan Feb Mar Ap...

Page 44: ...r supports at suction or discharge Reposition add or remove hangers Compressor insulator bushing worn Replace Compressor mechanical failure Check for possible problem in compressor failure and replace...

Page 45: ...el too high with compressor operation Confirm superheat is correct remove oil Operation or selection of expansion value Confirm superheat at minimum and maximum load conditions Compressor mechanical p...

Page 46: ...iom cliv cf eng www clima flex com...

Reviews: