Daikin Clima-Flex CLIV Series Installation, Operation And Maintenance Manual Download Page 19

iom-cliv-cf-eng

www.clima-flex.com

19

DANGER 

!

LOCK OUT / DISCONNECT all power sources before 

starting, pressurizing, depressurizing or shutting down 

the chiller. Disconnect electrical power before servicing 

equipment, including condenser fan motors or compressors. 

More than one disconnect may be required to deenergize 

the unit. Failure to comply with this warning can result in 

serious injury or death. Be sure to read and understand 

the installation, operating and service instructions in this 

manual.

Electrical Data 

ELECTRICAL CONNECTION 

CLIV units can be ordered with standard multi-point power 

connections or with optional single-point connections and various 

disconnect and circuit breaker options. Wiring inside the unit is 

sized in accordance with the NEC®.

The required field wiring varies depending on the configuration 

of the unit. 

Voltage limitations are:

1. Within 10 percent of nameplate rating.

2. Voltage unbalance must not exceed 2 percent. Since a volt-

age unbalance of 2 percent can cause a current unbalance of 

6 to 10 times the voltage unbalance per NEMA MG-1, it is im-

portant that phase-to-phase unbalance be kept to a minimum.

DANGER 

!

Qualified and licensed electricians must perform wiring. 

There is an electrical shock hazard that can cause serious 

injury or death.

Chiller electrical wiring connections may be made with copper 

wiring, provided the size and number of wires match the chiller 

terminals. All wiring must be in accordance with applicable 

local and national codes, including NECA/AA 10402012 for 

installation of aluminum wiring in buildings (ANSI). 

1. The control transformer is supplied and no separate 115V 

power is required. For single and multipoint power connec-

tions, the control transformer is on circuit #1 with control pow-

er wired from there to circuit #2. For multipoint power, discon-

necting power from circuit #1 disconnects the control power 

from the unit.

2. The size of the wiring supplied to the control panel shall be in 

accordance with the field wiring diagram. 

3. The single point power supply requires a single disconnect 

to supply electrical power to the unit. This power supply must 

have a fuse or use a circuit breaker. 

4. All field wiring terminal range values listed in the unit selection 

report apply to 75°C cable per NEC. 

5. It must be grounded per national and local electrical codes.

CAUTION  

!

Static discharge during handling of the circuit boards can 

cause damage to the components. Use an antistatic strap 

before performing any maintenance work. Never unplug 

cables, circuit board terminal blocks or plugs while the panel 

is powered.

USE WITH ON-SITE GENERATORS

Switching from site mains to generator power and vice versa 

requires the chiller to be off or the power to be disconnected for 

more than five seconds to avoid sending out-of-phase voltage to 

the chiller. A properly installed and fully synchronized automatic 

transfer switch must be used to transfer power if the chiller is 

operating under load.

Generator sizing

WARNING 

!

The generator should be sized by an electrical engineer 

familiar with generator applications.

Transfer Back To The Grid

Proper transfer of power from the standby generator to the grid 

is essential to prevent damage to the chiller and must be used to 

ensure proper operation of the unit.

WARNING 

!

Stop the chiller before transferring power from the generator 

to the mains. Transferring power while the chiller is running 

can cause serious damage to the chiller.

The procedure required to reconnect generator power to the grid 

is as follows:

1. Set the generator to always run five minutes longer than the 

unit start timer, which can be set from two to sixty minutes, 

while keeping the chiller powered by the generator until the 

fully synchronized Automatic Transfer Switch properly deliv-

ers chiller power from the site.

2. Set the transfer switch supplied with the generator to automat-

ically shut down the chiller before the transfer is made. The 

automatic shutdown function can be accomplished through a 

BAS interface or with the “remote on/off” wiring connection 

shown in the field wiring diagrams.

A start signal can be given at any time after the stop signal, as the 

three-minute start timer will be in effect.

Summary of Contents for Clima-Flex CLIV Series

Page 1: ...Operation and Maintenance Manual IOM Group Chiller Part number IOM CLIV Date 16 November 2022 CLIV Series Air Cooled Fixed Compressor Chilled Water Chiller Unit Model 3 5 and 10 TR Refrigerant HFC 41...

Page 2: ...Controller Operation 24 Sequence Of Operation 26 Funciones De La Unidad 30 Funciones De Los Circuitos 31 Alarmas 33 Uso Del Controlador 35 Procedimientos De Arranque Y Apagado 38 Mantenimiento De La U...

Page 3: ...rtup Cooler components EXV sensor transducers installed and wired properly Wiring complies with National Electrical Code and local codes See Notes Various Si No N A Iniciales Unit control disconnects...

Page 4: ...rigerant leaks from the unit there is a potential choking danger as the refrigerant will displace air in the immediate area Be sure to follow all applicable published industry related standards and lo...

Page 5: ...0 060 60 000 120 120 000 AIR DISCHARGE HD Horizontal Discharge OPERATION C Cooling Only H Heat Pump UNITS 1 Stand alone CONDENSER FAN A Axial Fixed ANTICORROSION C Coat in Condenser I Coat in Componen...

Page 6: ...tions DANGER Improper rigging lifting or moving of a unit can result in property damage serious personal injury or death Follow the rigging and moving instructions carefully Do not stand under the uni...

Page 7: ...ation of fans and compressors The noise level for each unit size model is listed in the technical documentation If the unit is properly installed operated and regularly maintained the noise levels do...

Page 8: ...f wall openness is less than recommended for the distance to the unit it should be considered a solid wall The wall height is assumed to be equal to or less than the height of the unit when mounted on...

Page 9: ...evaporators must have a drain and vent connection at the bottom of the bottom connection piping and at the top of the top connection piping respectively see Figure 6 These evaporators do not have dra...

Page 10: ...tes below the minimum values can result in laminar flow leading to low pressure alarms fouling and poor temperature control Variable evaporator flow Reducing the evaporator flow rate in proportion to...

Page 11: ...for longer than the specified time to help prevent evaporator freeze up Connection points are shown in the field wiring diagram beginning on page 20 1 If the unit will not operate during the winter d...

Page 12: ...ith a series of flat tubes containing multiple parallel flow microchannels placed between the coolant manifolds The microchannel coils are designed to withstand the synthetic acidified seawater acidif...

Page 13: ...iom cliv cf eng www clima flex com 13 Figure 8 Refrigeration Schematics CLIV Refrigeration Schematics...

Page 14: ...iom cliv cf eng www clima flex com 14 Refrigeration Schematics Figure 9 CLIV heat pump cooling scheme...

Page 15: ...iom cliv cf eng www clima flex com 15 Figure 10 CLIV Dimensions and Weights Packaged Units...

Page 16: ...iom cliv cf eng www clima flex com 16 Dimensions and Weights Packaged Units Figure 11 CLIV heat pump...

Page 17: ...en open the register1 Fig 12 Subsequently isolate the vacuum pump and open the register 2 When a value of less than 200 mecrons is obtained try to reach the lowest possible value the vacuum procedure...

Page 18: ...E EVAPORATOR DROP TOTAL DROP DP ft WG DP ft WG 3 UNIT 16 7 32 5 UNIT 16 7 32 10 DUPLEX 16 7 32 Table 5 Evaporator Pressure Drop Data FAMILY TR R410A Lb R410A Kg CLIV 3 TR 3 56 1 61 CLIV 5 TR 3 52 1 60...

Page 19: ...gram 3 The single point power supply requires a single disconnect to supply electrical power to the unit This power supply must have a fuse or use a circuit breaker 4 All field wiring terminal range v...

Page 20: ...iom cliv cf eng www clima flex com 20 Electrical Data Figure 13 Typical field wiring diagram of the 220v slave only cold unit single point connection with all options shown...

Page 21: ...iom cliv cf eng www clima flex com 21 Electrical Data...

Page 22: ...iom cliv cf eng www clima flex com 22 Electrical Data Figure 14 Typical field wiring diagram of the 440v slave single cold unit single point connection with all options shown...

Page 23: ...iom cliv cf eng www clima flex com 23 Electrical Data...

Page 24: ...reless connectivity with mobile devices and is integrated on panel mounted models and purchased separately on DIN rail mounted models SYSTEM ARCHITECTURE The general architecture of the controls uses...

Page 25: ...essor 2 NO3 MC 95 Water pump NO4 B 24V2 4 way valve NO5 Output available for alarm connection SET POINTS When we start configuring the unit for the first time all the preload parameters have a default...

Page 26: ...et button on No Evaporator pump output on Is flow present No Wait the time for the start up compressor The contactor auxiliar remains on while chiller is enabled Is the protection module or frecuency...

Page 27: ...y Increase unit capacity Unit turn up full capacity Operation of circuit in stabilization Unit turn down full capacity Decrease unit capacity Is unit running at minimun capacity No No Yes No No Yes Ye...

Page 28: ...Reset button on No Evaporator pump output on Is flow present No Wait the time for the start up compressor The contactor auxiliar remains on while chiller is enabled Is the protection module or frecuen...

Page 29: ...y Increase unit capacity Unit turn up full capacity Operation of circuit in stabilization Unit turn down full capacity Decrease unit capacity Is unit running at minimun capacity No No Yes No No Yes Ye...

Page 30: ...CONTROLLER CALCULATIONS Condenser approach The capacitor approximation will be calculated for each circuit The equation is as follows Capacitor approximation Capacitor saturated temperature OAT Sucti...

Page 31: ...s capacity control logic commands it to shut down A discharge alarm occurs and sequencing requires this compressor to be the next compressor to shut down The circuit status is pumping and sequencing...

Page 32: ...frosted equalizer line indicates internal leaks and will require valve replacement Repair or replacement of a bent equalizer will be necessary for the valve to operate properly TXVs are designed to m...

Page 33: ...log If the alarm is automatically reset the alarm key is turned off the alarm code disappears from the list and the alarm termination event is recorded in the alarm log Procedure alarm acknowledgement...

Page 34: ...ther with the current pump configuration A15 This alarm usually appears when the water temperature does not drop due to the current cooling process This alarm is more of a WARNING than a serious alarm...

Page 35: ...e top row the flow water temperature In the bottom row with the unit switched on the return water temperature With the unit switched off the OFF status during Bluetooth communication the text bLE flas...

Page 36: ...rs such as direct commands and active alarms can be accessed through the user terminal without password or with password to those dedicated to unit configuration and optimization Press DOWN for 3 s to...

Page 37: ...t pump units Press DOWN the manual defrost command dFr appears Press DOWN the command to cancel the alarm log ClrH appears Assistance level only Press DOWN the selection of units of measurement UoM ap...

Page 38: ...ydraulic circuit is closed Check for foreign objects in the fan discharge Check that the air inlet is not obstructed and has the suggested clearance INSPECTION OF THE HYDRAULIC CIRCUIT Date Place of W...

Page 39: ...ions Measure voltage on all units ground neutral and 3 phase line Check that motor overload protection conforms to design requirements and is in automatic mode Check voltage Motor save which is set to...

Page 40: ...turned on Turn the switch on the CONTROL UNIT to the ON position to power the control panel with 24 volts UNIT CONTROL To start operations turn the ON OFF switch to the ON position After 6 seconds th...

Page 41: ...onsible for the malfunction of the unit if the main cause is lack of maintenance or the operating conditions of the unit do not correspond to those recommended in this manual MAINTENANCE GENERAL Routi...

Page 42: ...ay start up and cause injury Disconnect all power sources before inspecting the fan EXPANSION VALVE The function of the expansion valve is to maintain adequate supply of refrigerant to the evaporator...

Page 43: ...these must be under the manufacturer s specifications Twice a month Plan x x x x x x Real Cleaning of the electrical panel monthly Plan x x x x x x x x x x x x Real PHYSICAL INSPECTION Jan Feb Mar Ap...

Page 44: ...r supports at suction or discharge Reposition add or remove hangers Compressor insulator bushing worn Replace Compressor mechanical failure Check for possible problem in compressor failure and replace...

Page 45: ...el too high with compressor operation Confirm superheat is correct remove oil Operation or selection of expansion value Confirm superheat at minimum and maximum load conditions Compressor mechanical p...

Page 46: ...iom cliv cf eng www clima flex com...

Reviews: