Unit Controller Operation
INPUTS AND OUTPUTS
Physical address
Electrical diagram label
Name
S1
SR
Return Sensor
S2
SI
Injection Sensor
S3
SC
Condenser Sensor
Tabla 6. Analog inputs
Physical address
Electrical diagram label
Name
ID1
IF
Flow sensor
ID2
C/H
Heating / cooling switch
ID3
AP
High pressure switch
ID4
BP
Low pressure switch
ID5
System
Cliv unit on/off switch
Tabla 7. Digital inputs
Tabla 8. Digital outputs
Physical address
Electrical diagram label
Name
NO1
C1-A2
Compressor 1
NO2
2-E2
Compressor 2
NO3
MC-95
Water pump
NO4
B-24V2
4-way valve
NO5
Output available for alarm connection
-
SET POINTS
When we start configuring the unit for the first time all the preload parameters have a default value, these values are stored in permanent
memory but can be changed depending on the application of the unit.
Values can be changed from the display and submenus require a password if values are to be changed; if an option is not included in the
display menu the data is only an internal value in the controller and will be visible only if that mode is selected.
Operating parameters:
PARAMETER
VALUE
U077
0
S068
0
U076
0
C046
1
C047
0
S065
0
S064
0
Hc31
7
Hc32
8
Hc14
1
Hc15
2
Hc06
9
Hc07
4
U006
5.0
U007
20.0
U008
30.0
U009
45.0
Hc013
1