background image

5

Coat here with 
refrigeration machine oil 

Torque wrench

Piping union

Flare nut

Spanner

Insulation for fitting
(attached)
(For gas pipe)

Large sealing pad
(attached)

Gas pipe

Liquid pipe

Insulation for fitting
(attached)
(For liquid pipe)

Small sealing pad
(attached)

(Cut exactly at 
right angles.)

Remove burrs

Set exactly at the position shown below.

A

Flaring

Die

A

0 ~ 0.5 mm

Clutch-type

Flare tool for R-410A

1.0 ~ 1.5 mm

Clutch-type (Rigid-type)

1.5 ~ 2.0 mm

Wing-nut type (Imperial-type)

Conventional flare tool

Check

Flare's inner 
surface must be 
flaw-free.

The pipe end 
must be evenly 
flared in a 
perfect circle.

Make sure that 
the flare nut is 
fitted.

REFRIGERANT PIPING WORK

See the installation manual supplied with the Multi outdoor unit for outdoor unit.

1

FLARING THE PIPE END

1. Cut the pipe end with a pipe cutter.
2. Remove burrs with the cut surface facing

downward so that the chips do not enter the pipe.

3. Put the flare nut on the pipe.
4. Flare the pipe.
5. Check that the flaring is properly made.

WARNING

Do not use mineral oil on flared part.
Prevent mineral oil from getting into the system as this would reduce the
lifetime of the units.
Never use piping which has been used for previous installations. Only use
parts which are delivered with the unit.
Do never install a drier to this R-410A unit in order to guarantee its lifetime.
The drying material may dissolve and damage the system.
Incomplete flaring may cause refrigerant gas leakage.

2

REFRIGERANT PIPING

1. Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.

Then tighten them fully with the torque wrenches.

Use torque wrenches when tightening the flare nuts to prevent damage to
the flare nuts and escaping gas.

2. To prevent gas leakage, apply refrigeration machine oil on both inner and

outer surfaces of the flare. (Use refrigeration oil for R-410A)

Wrap only the gas line side with the sealing pad. Bend the pad over the
insulation for fitting (union) from above.

Flare nut tightening torque

Gas side

Liquid side

3/8 inch

1/2 inch

1/4 inch

32.7~39.9 N•m

49.5~60.3 N•m

14.2~17.2 N•m

(333~407 kgf•cm) (505~615 kgf•cm)

(144~175 kgf•cm)

Service port cap tightening torque

10.8~14.7 N•m (110~150 kgf•cm)

Valve cap tightening torque

Gas side

Liquid side

3/8 inch

1/2 inch

1/4 inch

21.6~27.4 N•m

26.5~32.3 N•m

21.6~27.4 N•m

(220~280 kgf•cm) (270~330 kgf•cm)

(220~280 kgf•cm)

Summary of Contents for CDKS25BVMB

Page 1: ...plit R 410A Fran ais Manuel d installation S rie split R 410A Italiano Manuale d installazione Serie Multiambienti R 410A Nederlands Montagehandleiding R 410A Split systeem Portugues Manual de Instala...

Page 2: ...eceive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not...

Page 3: ...gh to support the weight of the unit If there is a risk that the ceiling is not strong enough reinforce the ceiling before installing the unit Select the signal receiver mounting location within the s...

Page 4: ...he suspension bolt positions Install the suspension bolts Use M10 size bolts for the suspension bolts In order to reinforce the ceiling bearing the weight of the unit use anchors when installing onto...

Page 5: ...nd below the hanger brackets to secure them NOTE Use washers when mounting with M8 bolts Use a water level or water filled vinyl tubes to check that the unit is level at all four corners as shown in t...

Page 6: ...g into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Do never install a dri...

Page 7: ...fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052kW mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choos...

Page 8: ...y screw wires to the corresponding terminals 3 Connect the earth wires to the corresponding terminals 4 Pull wires to make sure that they are securely latched up then retain wires with wire retainer 5...

Page 9: ...e of the unit and push the other side gently over the 2 bends Cleaning the drain pan Clean the drain pan periodically or drain piping may be clogged with dust and may result in water leakage Ask your...

Page 10: ...power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut...

Page 11: ...2P098794 3 M02B075 0210 HT...

Reviews: