Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt or 
water out.

Be sure to 
place a cap.

Rain

Cautions on Pipe Handling

Protect the open end of the pipe against dust and moisture.

All pipe bends should be as gentle as possible. Use a pipe bender for bending.
(Bending radius should be 30 to 40 mm
or larger.)

Selection of Copper Pipes and Heat Insulation materials

When using commercial copper pipes and fittings, observe the following:

Insulation material:  Polyethylene foam

Heat transfer rate:  0.041 to 0.052kW/mK (0.035 to 0.045 kcal/mh°C)

Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.

Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

25/35 class

50/60 class

25/35/50/60 class

O.D. 9.5 mm

O.D. 12.7 mm

O.D. 6.4 mm

Thickness 0.8 mm

Gas pipe thermal insulation

25/35 class

50/60 class

25/35/50/60 class

I.D. 12-15 mm

I.D. 14-16 mm

I.D. 8-10 mm

Thickness 10 mm Min.

Liquid pipe

thermal insulation

REFRIGERANT PIPING WORK

Summary of Contents for CDKS25BVMB

Page 1: ...plit R 410A Fran ais Manuel d installation S rie split R 410A Italiano Manuale d installazione Serie Multiambienti R 410A Nederlands Montagehandleiding R 410A Split systeem Portugues Manual de Instala...

Page 2: ...eceive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not...

Page 3: ...gh to support the weight of the unit If there is a risk that the ceiling is not strong enough reinforce the ceiling before installing the unit Select the signal receiver mounting location within the s...

Page 4: ...he suspension bolt positions Install the suspension bolts Use M10 size bolts for the suspension bolts In order to reinforce the ceiling bearing the weight of the unit use anchors when installing onto...

Page 5: ...nd below the hanger brackets to secure them NOTE Use washers when mounting with M8 bolts Use a water level or water filled vinyl tubes to check that the unit is level at all four corners as shown in t...

Page 6: ...g into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Do never install a dri...

Page 7: ...fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052kW mK 0 035 to 0 045 kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choos...

Page 8: ...y screw wires to the corresponding terminals 3 Connect the earth wires to the corresponding terminals 4 Pull wires to make sure that they are securely latched up then retain wires with wire retainer 5...

Page 9: ...e of the unit and push the other side gently over the 2 bends Cleaning the drain pan Clean the drain pan periodically or drain piping may be clogged with dust and may result in water leakage Ask your...

Page 10: ...power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut...

Page 11: ...2P098794 3 M02B075 0210 HT...

Reviews: