Installation manual

 

3

 

BHF1357

 

Outdoor unit multi connection piping kit

 

4PW38477-1

 

F

 

OR

 

 BHFQ23P907

 

Pipe size selection and cutting position of the joint

 

Select the correct pipe size according the tables below and cut the
joints and reducers on the correct cutting point with a pipe cutter.

 

Table 4

 

 

Select the pipe size in function of the total capacity of the
outdoor unit.

 

 

When upsizing the main pipe, use gas reducer (3).

 

 

When using pipes of Ø19.1 or larger, make sure to use pipes
with 1/2H temper grade with a wall thickness of 1.0 mm. In case
there is no alternative and you use the O temper grade for pipes
with Ø19.1, a minimal wall thickness of 1.2 mm or more is
required and connections need to be brazed.

 

Upsizing main pipe

 

For units with total capacity of 24~32 Hp, the suction gas reducer (3)
has to be used. Connect the reducer to the suction gas joint as
shown in the figure below.

 

Table 5

Table 6

 

 

Cut the pipe with a pipe cutter.

 

I

 

N

 

 

 

CASE

 

 

 

OF

 

 

 

FRONT

 

 

 

PIPING

 

 

 

1. E

 

XTERIOR

 

2. D

 

IMENSIONS

 

 

 

FOR

 

 

 

INSTALLATION

 

Refer to the installation manual of the outdoor unit for
selection and restrictions for the piping between outdoor
branches. Not observing restrictions on the interconnecting
piping may result in malfunctioning of the unit.

 

Total capacity 
of outdoor 
units

 

Pipe size

 

(a)

 

(a) OD x minimum wall thickness (temper grade type)

 

Suction gas

HP/LP gas

Liquid

 

18 Hp

Ø28.6x1.0 (1/2H)

Ø22.2x1.0 (1/2H)

Ø15.9x1.0 (O)

20~22 Hp

Ø28.6x1.0 (1/2H)

Ø28.6x1.0 (1/2H)

Ø15.9x1.0 (O)

24 Hp

Ø34.9x1.21 (1/2H)

Ø28.6x1.0 (1/2H)

Ø15.9x1.0 (O)

26~32 Hp

Ø34.9x1.21 (1/2H)

Ø28.6x1.0 (1/2H)

Ø19.1x1.0 (1/2H)

 

Total capacity 
of outdoor 
units

 

Pipe size

 

(a)

 

(a) OD x minimum wall thickness (temper grade type)

 

Suction gas

HP/LP gas

Liquid

 

18 Hp

Ø22.2x1.0 (1/2H)

Ø19.1x1.0 (1/2H)

Ø9.5x0.80 (O)

20~24 Hp

Ø28.6x1.0 (1/2H)

Ø19.1x1.0 (1/2H)

Ø12.7x0.80 (O)

26~32 Hp

Ø28.6x1.0 (1/2H)

Ø22.2x1.0 (1/2H)

Ø12.7x0.80 (O)

 

Total capacity 
of outdoor 
units

 

Pipe size

 

(a)

 

(a) OD x minimum wall thickness (temper grade type)

 

Suction gas

HP/LP gas

Liquid

 

18 ~22 Hp

Ø22.2x1.0 (1/2H)

Ø19.1x1.0 (1/2H)

Ø9.5x0.80 (O)

24+28 Hp

Ø28.6x1.0 (1/2H)

Ø19.1x1.0 (1/2H)

Ø12.7x0.80 (O)

26 Hp

Ø22.2x1.0 (1/2H)

Ø19.1x1.0 (1/2H)

Ø9.5x0.80 (O)

30+32 Hp

Ø28.6x1.0 (1/2H)

Ø22.2x1.0 (1/2H)

Ø12.7x0.80 (O)

1

2

3

4

A

A

B

B

1

Main pipe, see table 4 on page 3

2

Joint (refer to 

"Restrictions on 

installing the multi connection 
piping kit" on page 2

)

3

Pipe between joint and the outdoor 
unit A, see table 5 on page 3

4

Pipe between joint and the outdoor 
unit B, see table 6 on page 3

24~32 Hp

1

2

3

15

1

Joint or reducer

2

Cut in order to have a 
fitting depth of 

15 mm

3

Field pipe

 

1

 

Liquid joint

 

4

 

HP/LP gas joint

 

2

 

To indoor unit

 

5

 

Equalizer pipe

 

3

 

Suction gas joint

 

A

 

300 mm (standard)

 

1

 

Liquid pipe

 

2

 

Suction gas pipe

 

3

 

HP/LP gas pipe

 

4

 

Equalizer pipe

 

5

 

Bottom frame

 

NOTE

 

In case dimension A exceeds 300 mm, extend the field
supplied interconnection piping between the joint and
the outdoor unit.

2

1

3

4

5

B

B

B

B

B

B

B

181

148

152

198

1 2 3

4

detail

5

152
211
283

58

63

105

181

Top view

Front view

Summary of Contents for BHFQ23P1357

Page 1: ...INSTALLATION MANUAL BHFQ23P907 BHFQ23P1357 Outdoor unit multi connection piping kit...

Page 2: ...8 6 ID 31 8 ID 25 4 1 ID 31 8 ID 28 6 ID 28 6 ID 25 4 ID 19 1 ID 22 2 ID 25 4 1 ID 22 2 ID 19 1 ID 15 9 ID 19 1 ID 15 9 1 ID 19 1 ID 22 2 ID 25 4 OD 25 4 ID 28 6 1 ID 28 6 ID 31 8 OD 31 8 2 ID 19 1 ID...

Page 3: ...antities and specifications A 1 0 15 view B 1 view 120 mm 500 mm When installing the multi outdoor system connect the units as shown in the figure below If installed in a different order the outdoor u...

Page 4: ...28 6x1 0 1 2H 22 2x1 0 1 2H 15 9x1 0 O 20 22 Hp 28 6x1 0 1 2H 28 6x1 0 1 2H 15 9x1 0 O 24 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 15 9x1 0 O 26 32 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 19 1x1 0 1 2H Total capacity...

Page 5: ...it 50 and connect the HP LP gas reducer 2 see view A in the figure below Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requirements Outdoor unit Pipe 1 L mm...

Page 6: ...n the outdoor and indoor unit All piping must be executed according to instructions in the installation manual of the outdoor unit and an air tight test must be performed after complete installation o...

Page 7: ...6 has been taken into account If dimension B of the angled joint you use is different from that dimension B adjust the L dimension of HP LP gas pipes 1 5 accordingly Table 15 Table 16 1 Liquid joint 3...

Page 8: ...the figure Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requi...

Page 9: ...e type without stoppers If dimension B of the angled joint you use is different from that dimension B and or if the joints for same diameter pipes have stopppers adjust the L dimension of suction gas...

Page 10: ...igure below Bend the field supplied liquid pipe up to the stop valve as shown in the figure below Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer t...

Page 11: ...page 5 6 Liquid reducer 1 7 Liquid pipe 2 field supply select the pipe length on site 8 Equalizer pipe field supply select the pipe length on site 9 Liquid accessory pipe 2 supplied with the outdoor...

Page 12: ...ction gas pipes only For L dimension of suction gas pipes 1 3 dimension B of the field supplied angled joint as in table 25 on page 11 has been taken into account If dimension B of the angled joint yo...

Page 13: ...80 67 262 59 42 44 Hp 80 97 262 59 46 48 Hp 80 97 256 47 Outdoor unit Joint angle of 90 field supply B mm 34 44 Hp 17 46 48 Hp 23 Suction gas reducer 1 Unit A Suction gas reducer 1 Unit B 1 Connectio...

Page 14: ...joint 1 3 Cutting position 4 Connection to liquid joint 2 5 No cutting for 34 Hp 1 Liquid pipe accessory 1 supplied with the outdoor unit 2 Liquid pipe field supply select the pipe length on site 3 Li...

Page 15: ...168 168 244 44 48 212 195 160 168 168 232 Outdoor unit Joint angle of 90 field supply Joint 1 B mm Joint 2 B mm Joint 3 B mm 34 Hp 29 23 23 36 38 Hp 29 29 23 40 Hp 29 29 29 42 Hp 29 29 23 44 48 Hp 29...

Page 16: ...oint 5 angle of 90 field supply refer to table 33 on page 14 22 Suction gas pipe 2 field supply refer to table 30 on page 14 23 HP LP gas pipe 2 field supply refer to table 32 on page 14 24 Suction ga...

Page 17: ...and 3 and HP LP gas reducer 2 and 3 Be sure to foresee enough space for brazing and piping work under the unit 1 Liquid pipe 3 Suction gas pipe 2 HP LP gas pipe 4 Equalizer pipe Suction gas accessory...

Page 18: ...HP LP gas accessory pipe 1 supplied with the outdoor unit 8 HP LP gas reducer 1 9 Suction gas reducer 2 10 HP LP gas pipe field supply select the pipe length on site 11 HP LP gas reducer 3 12 HP LP ga...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium Copyright Daikin 4PW38477 1...

Reviews: