Installation manual
11
BHF1357
Outdoor unit multi connection piping kit
4PW38477-1
■
Cut the pipe with a pipe cutter
How to install the reducers
■
Suction gas pipe
-
For 34 Hp, connect the suction gas reducer (5) to the suction
gas joint (1) as shown in the figure below.
-
For 36~48 Hp, connect the suction gas reducer (4) to the
suction gas joint (1) as shown in the figure below
■
HP/LP gas pipe
For 38~48 Hp, connect the suction gas reducer (5) to the HP/LP
gas joint (1) as shown in the figure below.
■
Using piping inbetween connection joints suction gas pipe
For 40~48 Hp, connect two times the suction gas reducer (5) to
the suction gas joints (1) and (2) as shown in the figure below
I
N
CASE
OF
FRONT
PIPING
1. E
XTERIOR
2. D
IMENSIONS
FOR
INSTALLATION
3. I
NSTALLATION
OF
SUCTION
GAS
AND
HP/LP
GAS
PIPES
Cutting the field supplied gas pipes
Use the following tables in case dimension A is 318 mm (refer to
"Dimensions for installation" on page 11
If dimension A exceeds 318 mm, extend the L dimension of the gas
pipes 1~3 and HP/LP gas pipes 1~4 accordingly.
■
For suction gas pipes only
For L dimension of suction gas pipes 1~3, dimension B of the
field supplied angled joint as in table 25 on page 11 has been
taken into account. If dimension B of the angled joint you use is
different from that dimension B, adjust the L dimension of
suction gas pipes 1~3 accordingly.
Table 24
Table 25
1 Suction gas joint (1)
3 Field supplied gas pipe (Ø34.9)
2 Suction gas reducer (5)
4 Suction gas joint (2)
1
Liquid joint (1)
5
Equalizer pipe
2
To indoor unit
6
Liquid joint (2)
3
Suction gas joint (1)
7
HP/LP gas joint (2)
4
HP/LP gas joint (1)
8
Suction gas joint (2)
1
2
3
≥
15
1
Joint or reducer
2
Cut in order to have a
fitting depth of
≥
15 mm
3
Field pipe
1
4
2
3
2
2
1
3
4
5
6
7
8
5
5
B
B
B
B
B
B
A
318 mm (standard)
1
Liquid pipe
2
Suction gas pipe
3
HP/LP gas pipe
4
Equalizer pipe
5
Bottom frame
NOTE
In case dimension A exceeds 318 mm, extend the field
supplied interconnection piping between the joint and
the outdoor unit.
Outdoor unit
Pipe 1
L (mm)
Pipe 2
L (mm)
Pipe 3
L (mm)
34 Hp
135
79
256
36+38 Hp
135
153
256
40 Hp
135
153
252
42 Hp
135
153
256
44~48 Hp
135
153
252
Outdoor unit
Joint (angle of 90°) (field supply)
B (mm)
34~38 Hp
23
40 Hp
29
42 Hp
23
44~48 Hp
29
B
B
181
148
152
198
1 2 3
4
detail
B
B
5
152
211
283
58
63
105
181
L
B
B