BHF1357

 

Outdoor unit multi connection piping kit

 

4PW38477-1

 

Installation manual

 

2

 

Selection procedure

 

Table 3

 

R

 

ESTRICTIONS

 

 

 

ON

 

 

 

INSTALLING

 

 

 

THE

 

 

 

MULTI

 

 

 

CONNECTION

 

 

 

PIPING

 

 

 

KIT

 

 

Install the joints horizontally, so that the caution label (1)
attached to the joint comes to the top.
Do not tilt the joint more than ±15° (see view 

 

A

 

). 

Do not install the joint vertically (see view 

 

B

 

). 

 

 

Make sure that the total length of the piping connected to the
joint is absolute straight for more than 500 mm. Only if a straight
field piping of more than 120 mm is connected, more than
500 mm of straight section can be ensured. 

 

 

Improper installation may lead to malfunction of the outdoor unit.

 

Number of outdoor units

Kit name

 

2 units

BHFQ23P907

3 units

BHFQ23P1357

 

 

The quantity and selection procedure for use of joints
with an angle of 90° only apply to front connection
installations.

 

 

For lower front connection and bottom connection
installations, the quantity and selection procedure are
different. Please refer to the dedicated instructions.

 

 

Joints for pipes with the same diameter are only
needed for bottom connection installations. See
dedicated instructions for quantities and specifications.

A

1

0

°±

15

view

B

1

view

>120 m

m

>500 m

m

 

 

When installing the multi outdoor system, connect the
units as shown in the figure below.
If installed in a different order, the outdoor unit multi
connection piping kit may not fit properly and some
additional field supplied pipe size reducers may be
required.

 

Outdoor unit multi

connection piping kit type:

 

Unit capacity

 

:

 

1

 

To indoor unit

 

2

 

Outdoor unit multi connection piping kit (first branch)

 

3

 

Outdoor unit multi connection piping kit (second branch)

 

 

If the total capacity of the connected indoor units
exceeds the total capacity of the outdoor units,
cooling and heating performance may be reduced
when running the indoor units. Refer to the capacity
table in the Engineering Data Book for more details.

 

 

Use piping with temper grade in function of the pipe
diameter as listed in the table below.

 

 

The pipe thickness of the refrigerant piping must
comply with relevant local and national regulations.
The minimum pipe thickness for R410A piping must
be in accordance with the table below (for design
pressure of 4.0 MPa (40 bar)).

1 2

A

B

1 2

A

B

C

3

BHFQ23P907

BHFQ23P1357

A

B

A

B

C

Temper grade

O type

1/2H type

Pipe Ø

6.4

9.5 12.7 15.9 19.1 22.2 25.4 28.6 31.8 34.9 38.1 41.3

Minimum 
thickness 
t (mm)

0.80 0.80 0.80 1.00 1.00 1.00 1.00 1.00 1.10 1.21 1.32 1.43

O = Annealed
1/2H = Half hard

Summary of Contents for BHFQ23P1357

Page 1: ...INSTALLATION MANUAL BHFQ23P907 BHFQ23P1357 Outdoor unit multi connection piping kit...

Page 2: ...8 6 ID 31 8 ID 25 4 1 ID 31 8 ID 28 6 ID 28 6 ID 25 4 ID 19 1 ID 22 2 ID 25 4 1 ID 22 2 ID 19 1 ID 15 9 ID 19 1 ID 15 9 1 ID 19 1 ID 22 2 ID 25 4 OD 25 4 ID 28 6 1 ID 28 6 ID 31 8 OD 31 8 2 ID 19 1 ID...

Page 3: ...antities and specifications A 1 0 15 view B 1 view 120 mm 500 mm When installing the multi outdoor system connect the units as shown in the figure below If installed in a different order the outdoor u...

Page 4: ...28 6x1 0 1 2H 22 2x1 0 1 2H 15 9x1 0 O 20 22 Hp 28 6x1 0 1 2H 28 6x1 0 1 2H 15 9x1 0 O 24 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 15 9x1 0 O 26 32 Hp 34 9x1 21 1 2H 28 6x1 0 1 2H 19 1x1 0 1 2H Total capacity...

Page 5: ...it 50 and connect the HP LP gas reducer 2 see view A in the figure below Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requirements Outdoor unit Pipe 1 L mm...

Page 6: ...n the outdoor and indoor unit All piping must be executed according to instructions in the installation manual of the outdoor unit and an air tight test must be performed after complete installation o...

Page 7: ...6 has been taken into account If dimension B of the angled joint you use is different from that dimension B adjust the L dimension of HP LP gas pipes 1 5 accordingly Table 15 Table 16 1 Liquid joint 3...

Page 8: ...the figure Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer to Pipe size selection and cutting position of the joint on page 3 for the cutting requi...

Page 9: ...e type without stoppers If dimension B of the angled joint you use is different from that dimension B and or if the joints for same diameter pipes have stopppers adjust the L dimension of suction gas...

Page 10: ...igure below Bend the field supplied liquid pipe up to the stop valve as shown in the figure below Refer to the installation manual delivered with the outdoor unit for cautions on brazing pipes Refer t...

Page 11: ...page 5 6 Liquid reducer 1 7 Liquid pipe 2 field supply select the pipe length on site 8 Equalizer pipe field supply select the pipe length on site 9 Liquid accessory pipe 2 supplied with the outdoor...

Page 12: ...ction gas pipes only For L dimension of suction gas pipes 1 3 dimension B of the field supplied angled joint as in table 25 on page 11 has been taken into account If dimension B of the angled joint yo...

Page 13: ...80 67 262 59 42 44 Hp 80 97 262 59 46 48 Hp 80 97 256 47 Outdoor unit Joint angle of 90 field supply B mm 34 44 Hp 17 46 48 Hp 23 Suction gas reducer 1 Unit A Suction gas reducer 1 Unit B 1 Connectio...

Page 14: ...joint 1 3 Cutting position 4 Connection to liquid joint 2 5 No cutting for 34 Hp 1 Liquid pipe accessory 1 supplied with the outdoor unit 2 Liquid pipe field supply select the pipe length on site 3 Li...

Page 15: ...168 168 244 44 48 212 195 160 168 168 232 Outdoor unit Joint angle of 90 field supply Joint 1 B mm Joint 2 B mm Joint 3 B mm 34 Hp 29 23 23 36 38 Hp 29 29 23 40 Hp 29 29 29 42 Hp 29 29 23 44 48 Hp 29...

Page 16: ...oint 5 angle of 90 field supply refer to table 33 on page 14 22 Suction gas pipe 2 field supply refer to table 30 on page 14 23 HP LP gas pipe 2 field supply refer to table 32 on page 14 24 Suction ga...

Page 17: ...and 3 and HP LP gas reducer 2 and 3 Be sure to foresee enough space for brazing and piping work under the unit 1 Liquid pipe 3 Suction gas pipe 2 HP LP gas pipe 4 Equalizer pipe Suction gas accessory...

Page 18: ...HP LP gas accessory pipe 1 supplied with the outdoor unit 8 HP LP gas reducer 1 9 Suction gas reducer 2 10 HP LP gas pipe field supply select the pipe length on site 11 HP LP gas reducer 3 12 HP LP ga...

Page 19: ...NOTES NOTES...

Page 20: ...Zandvoordestraat 300 B 8400 Oostende Belgium Copyright Daikin 4PW38477 1...

Reviews: