Packaged Air Conditioner Drain Pump Kit - BDU510B250VM

 4. DRAINAGE PIPE INSTALLATION

Install the drain pipe to ensure proper drainage.

1.  Use a pipe diameter equal to or larger than that of the connecting pipe (PVC pipes with a nominal diameter of 25mm and an external diameter 

of 32mm).

2.  Make the pipe length as short as possible and incline the pipe downward at a ratio of 1/100 or greater to prevent the accumulation of air.
3.  Install pipe supports at intervals of 1.0m to 1.5m to prevent defl ection.
4.  Use a new drain hose and hose bands when replacing the drain pump kit with a new one.

1~1.5m 1~1.5m

Pipe support

CAUTION

• The height of the drain-up pipe must be 750mm or less relative to the indoor unit drain outlet.
• The rising drain-up pipe must be installed vertically.

Ceiling slab

1~1.5m

Pipe support

(Field supply)

Drain-up piping 

750mm 

or 

less

• Refer to the fi gure below for concentrated drain piping.

750mm or less

 5. ELECTRICAL WIRING

Perform electrical wiring for the drain pump kit properly as follows.

CAUTION

• Be sure to turn OFF the power to the indoor unit before starting the procedure below.

1.  Remove the indoor unit control box cover.
2.  Insert drain pump and fl oat switch lead wires through the rubber bush on the hanging bracket. Route and connect the lead wires to the printed 

circuit board of the indoor unit (Refer fi gure below).

3.  Bind the lead wires together with the drain connecting pipe 1 (included) using cable tie 1 (included).

Note: Do not compress the insulation after install the cable tie. Be sure the lead wire is fi xed close to the indoor unit.

4.  Clamp the lead wires inside control box using cable tie 2 (included) and plastic band (included), along the path to PCB, secure with other 

hardness wires fi xing band (Refer to fi gure below).

5.  Remove the short circuit connector from the X15A terminal on the indoor unit printed circuit board (A1P).
6.  Connect the fl oat switch lead wire to the X15A terminal.
7.  Connect the drain pump lead wire to the X25A terminal.
8.  After completion of the wiring, be sure to organize the wires neatly, bind together and clamp the wires.
9.  Install back the indoor unit control box cover.

Summary of Contents for BDU510B250VM

Page 1: ...Packaged Air Conditioner Drain Pump Kit BDU510B250VM 4P590204 1 Installation manual...

Page 2: ...Heat insulating tube 2 Heat insulating tube 3 Heat insulating tube 4 Heat insulating material 1 Shape ID38 x L35 ID38 x L125 ID38 x L114 ID38 x L94 60 x 290 Quantity 1 1 1 1 3 Name Heat insulating ma...

Page 3: ...or other failure Suction Side Suction Side 1 or less 1 or less Indoor unit Drain Socket Indoor unit Drain Socket 3 INSTALLATION PROCEDURE CAUTION Do not hold the drain pump kit by the drain socket wh...

Page 4: ...in pump kit 10 Clamp the pipe joints with the hose bands included 11 Wrap heat insulating material 2 around the drain connecting pipes at hose band location Then wrap the drain connecting pipes with h...

Page 5: ...al wiring for the drain pump kit properly as follows CAUTION Be sure to turn OFF the power to the indoor unit before starting the procedure below 1 Remove the indoor unit control box cover 2 Insert dr...

Page 6: ...URE CAUTION Be sure to turn OFF the power to the indoor unit before starting the procedure below 1 Check again that the installation and electrical wiring procedures for the drain pump kit have been c...

Page 7: ...rth terminal of the power terminal block X1M Then close the indoor unit control box cover and turn ON the power 6 Use the remote controller to start trial operation mode and select FAN operation mode...

Page 8: ...100 Is the drain hose adequately insulated Are the wires connected correctly 8 MAINTENANCE Clean the drain pump kit at the end of every season in which the unit is used for cooling 1 Drain all the wat...