Packaged Air Conditioner Drain Pump Kit - BDU510B250VM

1

Read these instructions carefully before installation. Keep this manual in a handy place for future reference.
The original documentation is written in English. All other languages are translations.

CONTENTS

1. COMPONENTS 

1

2. PREPARATION FOR INSTALLATION 

1

3. INSTALLATION PROCEDURE 

2

4. DRAINAGE PIPE INSTALLATION 

4

5. ELECTRICAL WIRING 

4

6. TRIAL OPERATION PROCEDURE 

5

7. CHECK AFTER INSTALLATION 

7

8. MAINTENANCE 

7

 1. COMPONENTS

Check that the following accessories are provided and that each accessory is correct in amount.

PRECAUTION

The accessories are required for the installation of the air conditioner. Be sure to keep them until the installation work is completed.

Name

Drain Pump assembly

Hanging bracket

Drain connecting pipe 1 Drain connecting pipe 2

Drain connecting pipe 3

Shape

Quantity

1

2

1

1

1

Name

Heat insulating tube 1

Heat insulating tube 2

Heat insulating tube 3

Heat insulating tube 4

Heat insulating material 1

Shape

ID38 x L35

ID38 x L125

ID38 x L114

ID38 x L94

60 x 290

Quantity

1

1

1

1

3

Name

Heat insulating material 2 Heat insulating material 3 Heat insulating material 4

Mounting screw

Hose band

Shape

20 x 400

230 x 250

90 x 240

M5x12

Quantity

2

1

1

8

3

Name

Cable tie 1

Cable tie 2

Plastic band

Installation manual

Shape

L265

L150

Quantity

1

1

1

1

 2. PREPARATION FOR INSTALLATION

2.1 Required Installation Space

To install an indoor unit with the drain pump kit, a clearance of 560mm or more is required between the ceiling slab and the ceiling surface
(Refer to fi gure below). Provide an inspection hatch in a position where you can readily service the indoor unit and the drain pump kit.

Ceiling slab

Indoor unit

min. 20mm

50m

m

56

0m

m

 or

 m

ore

min. 70mm

Ceiling surface

Drain pump kit 

Side View

The bottom surface of the drain pump kit will be 

lower than the bottom surface of the indoor unit

 

Indoor unit

Approx. 150

Drain pump kit

Inspection hatch 
(600mm X 600mm)

65

or

 m

ore

 

(S

er

vic

spa

ce

)

Top View

Summary of Contents for BDU510B250VM

Page 1: ...Packaged Air Conditioner Drain Pump Kit BDU510B250VM 4P590204 1 Installation manual...

Page 2: ...Heat insulating tube 2 Heat insulating tube 3 Heat insulating tube 4 Heat insulating material 1 Shape ID38 x L35 ID38 x L125 ID38 x L114 ID38 x L94 60 x 290 Quantity 1 1 1 1 3 Name Heat insulating ma...

Page 3: ...or other failure Suction Side Suction Side 1 or less 1 or less Indoor unit Drain Socket Indoor unit Drain Socket 3 INSTALLATION PROCEDURE CAUTION Do not hold the drain pump kit by the drain socket wh...

Page 4: ...in pump kit 10 Clamp the pipe joints with the hose bands included 11 Wrap heat insulating material 2 around the drain connecting pipes at hose band location Then wrap the drain connecting pipes with h...

Page 5: ...al wiring for the drain pump kit properly as follows CAUTION Be sure to turn OFF the power to the indoor unit before starting the procedure below 1 Remove the indoor unit control box cover 2 Insert dr...

Page 6: ...URE CAUTION Be sure to turn OFF the power to the indoor unit before starting the procedure below 1 Check again that the installation and electrical wiring procedures for the drain pump kit have been c...

Page 7: ...rth terminal of the power terminal block X1M Then close the indoor unit control box cover and turn ON the power 6 Use the remote controller to start trial operation mode and select FAN operation mode...

Page 8: ...100 Is the drain hose adequately insulated Are the wires connected correctly 8 MAINTENANCE Clean the drain pump kit at the end of every season in which the unit is used for cooling 1 Drain all the wat...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...4P590204 1 2019 07 Copyright 2019 Daikin...

Reviews: