Packaged Air Conditioner Drain Pump Kit - BDU510B250VM
3
6. Insert heat insulating tube 2 (included) onto drain connecting pipe 1.
Drain pump kit
Indoor unit drain socket
Heat insulating tube 1 (included)
Drain connection pipe 1 (included)
Heat insulating tube 2 (included)
7. Insulate drain connecting pipe 2 (included) with heat insulating tube 3 (included), heat insulating tube 4 (included) and heat insulating material 1.
Note: Be sure to apply glue around the join of heat insulating tube 3 and heat insulating tube 4.
8. After glue dry, affi x heat insulating material 1 (included) to cover the join area.
Drain connection pipe 2
(included)
Heat insulating tube 4
(included)
Heat insulating tube 3
(included)
Apply glue around the
joint of insulating area
60mm
(
¿
eld supply)
(included)
Heat insulating material 1
Heat insulating material 1
(included)
Wrap around the joint
of insulating area
9. Connect the drain connecting pipe 2 to the drain pump kit and the drain connecting pipe 1.
Note: Be sure to connect the elbow side of the drain connecting pipe 2 to the drain pump kit.
10. Clamp the pipe joints with the hose bands (included).
11. Wrap heat insulating material 2 around the drain connecting pipes at hose band location. Then wrap the drain connecting pipes with heat
insulating materials 3 and heat insulating material 4. And fi nally wrap the exposed heat insulating tube with heat insulating material 1.
Indoor unit
Drain pump kit
Hose band
(included)
Drain connection pipe 2
(included)
Align to side
Heat insulating
material 2
(included)
Align to side
(included)
Heat insulating material 4
Heat insulating material 3
(included)
Joint of insulating area
Heat insulating material 1
(included)
(exposed heat insulating tube)
20mm
Drain connection pipe 1
(included)
90mm
60mm
20mm
230mm
60mm
12. Connect the drain connecting pipe 3 (included) to the outlet of the drain pump kit.
Note: Be sure to incline the external drain pipe downward.
13. Clamp the pipe joints with the hose bands (included).
14. Do not install the heat insulating material (fi eld supply) to the outlet of the drain pump kit at this point. It will be installed after the draining check
in the trial operation procedure (Refer to 6. TRIAL OPERATION PROCEDURE).
Drain pipe
(
¿
eld supply)
(included)
Drain connection pipe 3
Indoor unit
Hose band
(included)
Drain pump kit