background image

Packaged Air Conditioner Drain Pump Kit - BDU510B250VM

7

Insulation tube 
(Field supply)

No gap allowed

Drain pump kit

CAUTION
Wrap the heat insulating material 
to adequately insulate the hose 
band

 7. CHECK AFTER INSTALLATION

Check again at the least the following items after completion of installation.

Check Item

Check Mark

Are the indoor unit and the drain pump kit installed horizontally?

Is the drain pipe connected fi rmly?

Is there no possibility of water leakage?

Is the drain piping properly inclined downward (1/50 to 1/100)?

Is the drain hose adequately insulated?

Are the wires connected correctly?

 8. MAINTENANCE

Clean the drain pump kit at the end of every season in which the unit is used for cooling.

1.  Drain all the water out of the drain pump kit by removing the insulation plug and rubber plug.

Note: Even after removing the rubber plug from the drain pump kit, some water may remain trapped in the drain connecting pipes 
and the drain pump kit.

2.  Remove the inspection port cover from the drain pump kit.
3.  Remove dust and water in the areas around the inspection port.
4.  After fi nish cleaning, install back the inspection port cover, rubber plug and insulation plug.

Drain pump kit

Rubber plug

Insulation plug

Screws (4pcs.)

Inspection port cover

Summary of Contents for BDU510B250VM

Page 1: ...Packaged Air Conditioner Drain Pump Kit BDU510B250VM 4P590204 1 Installation manual...

Page 2: ...Heat insulating tube 2 Heat insulating tube 3 Heat insulating tube 4 Heat insulating material 1 Shape ID38 x L35 ID38 x L125 ID38 x L114 ID38 x L94 60 x 290 Quantity 1 1 1 1 3 Name Heat insulating ma...

Page 3: ...or other failure Suction Side Suction Side 1 or less 1 or less Indoor unit Drain Socket Indoor unit Drain Socket 3 INSTALLATION PROCEDURE CAUTION Do not hold the drain pump kit by the drain socket wh...

Page 4: ...in pump kit 10 Clamp the pipe joints with the hose bands included 11 Wrap heat insulating material 2 around the drain connecting pipes at hose band location Then wrap the drain connecting pipes with h...

Page 5: ...al wiring for the drain pump kit properly as follows CAUTION Be sure to turn OFF the power to the indoor unit before starting the procedure below 1 Remove the indoor unit control box cover 2 Insert dr...

Page 6: ...URE CAUTION Be sure to turn OFF the power to the indoor unit before starting the procedure below 1 Check again that the installation and electrical wiring procedures for the drain pump kit have been c...

Page 7: ...rth terminal of the power terminal block X1M Then close the indoor unit control box cover and turn ON the power 6 Use the remote controller to start trial operation mode and select FAN operation mode...

Page 8: ...100 Is the drain hose adequately insulated Are the wires connected correctly 8 MAINTENANCE Clean the drain pump kit at the end of every season in which the unit is used for cooling 1 Drain all the wat...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...4P590204 1 2019 07 Copyright 2019 Daikin...