4
2
Select proper position in the ceiling for the decoration panel
considering length of the hose.
3
Make a hole in the false ceiling. (Length 104×183 mm)
4
Disconnect the hose from the decoration panel.
5
Fix the decoration panel to the ceiling by springs.
6
Attach hose back to decoration panel port.
Electric wiring work
General instructions
All field wiring and components must be installed by a licensed
electrician and must comply with relevant European and national
regulations.
Follow the "Wiring diagram" attached to the unit body to wire the
indoor unit and Auto-Cleaning option kit.
All cables entering the unit should be fixed by tie wraps
(accessory).
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
How to connect wiring
Remove the switch box covers as shown in figure 7, and connect the
indoor unit and option unit with wire harness (accessory set)
Plug all connectors according to figure 7.
Make sure that all connectors are securely connected.
It is necessary to fix the wire harness by the tie wraps
(accessory set) Use the fixing point shown in the figure 7.
When attaching the switch box cover make sure not to pinch any
wires.
Make sure that all wiring entering the units has this shape, which
prevents water flowing inside.
After all wiring connections are done, fill in any gaps in the
casing wiring holes with putty or insulation material (field supply)
thus to prevent small animals or dirt from entering the unit from
outside and causing short circuits in the control box.
T
EST
OPERATION
Perform the test operation of the Auto-Cleaning option kit after the
test operation of the indoor unit is finished.
The test operation of the Auto-Cleaning option kit is not possible
while the indoor unit is in operation.
Check that the Switch box lids of the indoor unit, outdoor
unit, and Auto-Cleaning option kit, respectively, are closed
Turn the indoor unit power on
The Auto-Cleaning option kit will perform the initialization (in
case of trolleys are not in parking position) it may take up to 5
minutes.
Conduct the Auto-Cleaning test operation
Confirm the cleaning operation of the filter with the remote
controller.
Test operation method with remote controller
1
Stop the operation of the indoor unit.
2
Press and hold the Cancel button for at least 4 seconds while
the backlight is lit. The service settings menu will appear.
3
Select
Test Filter Auto Clean
from the service settings menu,
and press the Menu/Enter button.
4
“
“ will appear on the basic screen.
The display will disappear when the test operation is finished.
The required test operation time is approximately 5-10 minutes
(depending on casing size).
Backlight for LCD
Press any button and the backlight will be lit for approximately 30
seconds.
1
Switch box cover
2
Switch box low voltage wiring inlet
3
Switch box high voltage wiring inlet
4
Wiring diagram of the option kit
5
Switch box of the option kit
6
Wire harness (accessory set)
7
Fixing point
NOTE
In case of combination of Auto-Cleaning option kit with
indoor unit FXDQ-A2/P2 contact your Daikin dealer to
obtain BAE20WH wire harness for successful
connection between indoor unit and Auto-Cleaning
option kit.
1
2
3
4
Cool
Set to
Cool
28
°C
Press and hold
Cancel button for
4 seconds or
longer during
backlight lit.
Return
Setting
Service Settings
Indoor Unit Status
Outdoor Unit Status
Forced Fan ON
Switch Main Sub Controller
Filter Indicator OFF
Test Filter Auto Clean
2/3
Press Menu/Enter
button.
Cool
Set to
Cool
28
°C
Collect dust
4PEN470901-1B.book Page 4 Thursday, September 7, 2017 3:17 PM