background image

Summary of Contents for BACnet

Page 1: ...Installation and Maintenance Manual IM 1040 Group Controls Part Number IM 1040 Date April 2015 BACnet VAV Actuator Electronic Output Start up Procedures ...

Page 2: ...ors 4 Setting controller address 4 Setting the application 4 Enabling actuators 5 Specifying motor setup 5 Verifying actuator setup 5 Setting the number of heat stages or valves 5 Selecting automatic calibration option 6 Setting room temperature setpoints 6 Setting override time 6 Enabling Wall Switch 6 Setting Duct Area 6 Setting flow coefficient 7 Setting airflow setpoints 7 Setting room tempera...

Page 3: ...f not avoided CAUTION Cautions indicate potentially hazardous situations which can result in personal injury or equipment damage if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes DANGER Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to...

Page 4: ...appropriate number see Configuring BACnet Parameters The start up is complete Setting the application NOTICE You can continue the startup procedure while calibration is underway However the controller will ignore commands to control end devices such as the damper until calibration of the air velocity sensor is finished Add the TEC to your job database and select one of the following applications f...

Page 5: ...ating before continuing MTRSETUP determines which actuators are controlled by the application and whether they are direct or reverse acting Set MTRSETUP according to Table 4 Table 4 Motor Enable Reverse Values for MTR SETUP Point 58 Enabled Enabled and Reversed Motor 1 damper Motor 2 Not used 1 default 3 Enabled 5 7 Enabled and Reversed 13 15 Verifying actuator setup Command all actuators closed V...

Page 6: ...er the override switch is depressed 4 factory default value Calibration occurs on the time interval set in the point CAL TIMER Point 96 For example if CAL TIMER 12 then the calibration period is12 hours Actual calibration is subject to a time delay based on the value of CTLR ADDRESS See the example in Option 1 This is the recommended option when using a controller with an Autozero Module Setting r...

Page 7: ... MIN to 0 zero Equipment damage may occur at 0 zero CFM with electric heat ON NOTICE Maximum flow s must be set minimum flow s NOTICE For Applications 2562 2563 2564 and 2566 HTG FLOW MAX should be less than CLG FLOW MAX Otherwise cold supply air may cool rather than heat the space in heating mode A typical setting for HTG FLOW MAX is 50 or less of CLG FLOW MAX 1 Set CLG FLOW MIN to the desired mi...

Page 8: ... configure Daikin BACnet MS TP TEC s Do not check the Metric checkbox in the Device Properties dialogue box if the controller is communicating through the MS TP driver in the Field Panel Metric can be checked only if the controller is communicating through a router If you need metric and the controller is communicating through the MS TP driver in the Field Panel then the Metric checkbox in the Dev...

Page 9: ......

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...

Reviews: