background image

s

TarT

-u

p

 p

roCedures

www.DaikinApplied.com 

IM 1040 • VAV ACTUATOR

Setting flow coefficient

1. 

Set FLOW COEFF to the appropriate value found in 

Table 6. This value is a starting point for the air balancer.

2. 

To fine tune the flow coefficient use the following formula:

new flow coefficient = (actual volume / TEC volume) 

× old flow coefficient

The actual volume is the actual value obtained from the 

balancer’s measurements. The TEC volume is the value 

obtained from AIR VOLUME.

3. 

If the TEC volume is not within 5% of the actual volume, 

repeat the procedure until it is within 5%.

Table 7: 

Box Manufacturer Flow Coefficients.

Manufacturer

Sensor Tpe

Value

Anemostat

2-pipe without orifice

0.79

2-pipe with orifice

0.59

Spider without orifice

0.73

Spider with orifice

0.39

Carnes

2-pipe

065

Flow cross

0.59

Carrier

0.59

E.H. Price/Siemens Industry Lab Terminal Boxes 

0.78

Environmental Technologies

0.79

Krueger

0.68

Metal Aire

0.72

Nailor Industries

0.69

Titus

0.60

Trane

0.66

Setting airflow setpoints

 CAUTION

If using electric heat in a unit without a terminal fan, do not set 

HTG FLOW MIN to 0 (zero). Equipment damage may occur at 

0 (zero) CFM with electric heat ON.

 NOTICE

Maximum flow(s) must be set ≥ minimum flow(s).

 NOTICE

For Applications  2562,  2563,  2564,  and  2566,  HTG  FLOW 

MAX should be less than CLG FLOW MAX. Otherwise, cold 

supply  air  may  cool  rather  than  heat  the  space  in  heating 

mode. A typical setting for HTG FLOW MAX is 50% or less of 

CLG FLOW MAX.

1. 

Set CLG FLOW MIN to the desired minimum cooling 

airflow setpoint.

2. 

Set CLG FLOW MAX to the desired maximum cooling 

airflow setpoint.

Applications 2561 - 2567:

1. 

Set HTG FLOW MIN to the desired minimum heating 

airflow setpoint.

2. 

Set HTG FLOW MAX to the desired maximum heating 

airflow setpoint.

Setting room temperature offset 

(optional)

 

 NOTICE

The Room Temperature Offset feature is optional.

When the room has stabilized to within 5°F, take a precision 

temperature reading at the room temperature sensor, record 

any difference between this reading and the value of ROOM 

TEMP and set this difference value (to the nearest 0.25°F) into 

RMTMP OFFSET.

Example:

If the actual room temperature is 72.0°F, and the value of 

ROOM TEMP is 73.0°F, then the value entered into RMTMP 

OFFSET is –1.0. In this case, the value of ROOM TEMP would 

read 73.0°F, but the value of CTL TEMP would read 72.0°F.

CTL TEMP = ROOM TEMP + RMTMP OFFSET

Summary of Contents for BACnet

Page 1: ...Installation and Maintenance Manual IM 1040 Group Controls Part Number IM 1040 Date April 2015 BACnet VAV Actuator Electronic Output Start up Procedures ...

Page 2: ...ors 4 Setting controller address 4 Setting the application 4 Enabling actuators 5 Specifying motor setup 5 Verifying actuator setup 5 Setting the number of heat stages or valves 5 Selecting automatic calibration option 6 Setting room temperature setpoints 6 Setting override time 6 Enabling Wall Switch 6 Setting Duct Area 6 Setting flow coefficient 7 Setting airflow setpoints 7 Setting room tempera...

Page 3: ...f not avoided CAUTION Cautions indicate potentially hazardous situations which can result in personal injury or equipment damage if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes DANGER Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to...

Page 4: ...appropriate number see Configuring BACnet Parameters The start up is complete Setting the application NOTICE You can continue the startup procedure while calibration is underway However the controller will ignore commands to control end devices such as the damper until calibration of the air velocity sensor is finished Add the TEC to your job database and select one of the following applications f...

Page 5: ...ating before continuing MTRSETUP determines which actuators are controlled by the application and whether they are direct or reverse acting Set MTRSETUP according to Table 4 Table 4 Motor Enable Reverse Values for MTR SETUP Point 58 Enabled Enabled and Reversed Motor 1 damper Motor 2 Not used 1 default 3 Enabled 5 7 Enabled and Reversed 13 15 Verifying actuator setup Command all actuators closed V...

Page 6: ...er the override switch is depressed 4 factory default value Calibration occurs on the time interval set in the point CAL TIMER Point 96 For example if CAL TIMER 12 then the calibration period is12 hours Actual calibration is subject to a time delay based on the value of CTLR ADDRESS See the example in Option 1 This is the recommended option when using a controller with an Autozero Module Setting r...

Page 7: ... MIN to 0 zero Equipment damage may occur at 0 zero CFM with electric heat ON NOTICE Maximum flow s must be set minimum flow s NOTICE For Applications 2562 2563 2564 and 2566 HTG FLOW MAX should be less than CLG FLOW MAX Otherwise cold supply air may cool rather than heat the space in heating mode A typical setting for HTG FLOW MAX is 50 or less of CLG FLOW MAX 1 Set CLG FLOW MIN to the desired mi...

Page 8: ... configure Daikin BACnet MS TP TEC s Do not check the Metric checkbox in the Device Properties dialogue box if the controller is communicating through the MS TP driver in the Field Panel Metric can be checked only if the controller is communicating through a router If you need metric and the controller is communicating through the MS TP driver in the Field Panel then the Metric checkbox in the Dev...

Page 9: ......

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...

Reviews: