Before you begin

 NOTICE

WinCIS version 2.1.4 or later must be used to configure Daikin 

BACnet controllers.

If WinCIS does not communicate (through the HMI port / RTS 

sensor), try a different baud rate. The default buad rate is 1200 

(allowable baud rates are: 1200, 9600, 19200, 38400 and 

76800).

Figure 1: Actuator Components    

Communication and DO indicators

The BACnet actuator has LEDs to indicate communication 

(yellow) and DO [digital output] status (green).
The RX LED will flash for data packets received by the actuator 

from the MS/TP network. The TX LED will flash for data 

packets sent by the actuator to the MS/TP network. Each DO 

(3 to 6) has an associated LED located above its termination 

point. This LED point is ON when the accociated DO is 

commanded ON, otherwise it is OFF. The BACnet actuator 

will attempt to communicate with other devices as soon as 

it powers up. The TX LED will start flashing as it attempts to 

connect and transfer data.

Setting controller address

 NOTICE

For BACnet, the controller address is the same as the BACnet 

MAC address.

 NOTICE

Set the controller address and MS/TP network baud rate prior 

to connecting the controller to the network.

• 

Set the controller address by setting CTLR ADDRESS 

to the appropriate number, see Configuring BACnet 

Parameters 

• 

The start-up is complete 

Setting the application

 NOTICE

You  can  continue  the  startup  procedure  while  calibration  is 

underway.  However,  the  controller  will  ignore  commands  to 

control end devices (such as the damper) until calibration of 

the air velocity sensor is finished. 

• 

Add the TEC to your job database and select one of the 

following applications from 

Table 1

Table 1: Daikin BACnet Actuator—Electronic Output 

Applications

Application Description

Application Number

VAV Cooling Only

2560

VAV Cooling or Heating

2561

VAV with Electric Reheat or Baseboard Radiation

2562

VAV with Hot Water Reheat

2563

VAV Series Fan Powered with Electric Heat

2564

VAV Series Fan Powered with Hot Water Reheat

2565

VAV Parallel Fan Powered with Electric Heat

2566

VAV Parallel Fan Powered with Hot Water Reheat

2567

VAV Slave Mode

2597

After you set the application, the controller goes through a 

shut-down/load sequence as it switches from slave mode 

to the application selected. When the application loads, the 

calibration cycle begins.
At the start of the calibration cycle, the controller 

automatically sets CAL AIR to YES. CAL AIR returns to NO 

when the cycle is complete.
The air velocity sensor calibration cycle begins within three 

minutes of an application start-up or initialization, depending on 

the controller’s address. The calibration cycle takes from two to 

five minutes to complete after this delay. The air damper closes 

during the first calibration.

Summary of Contents for BACnet

Page 1: ...Installation and Maintenance Manual IM 1040 Group Controls Part Number IM 1040 Date April 2015 BACnet VAV Actuator Electronic Output Start up Procedures ...

Page 2: ...ors 4 Setting controller address 4 Setting the application 4 Enabling actuators 5 Specifying motor setup 5 Verifying actuator setup 5 Setting the number of heat stages or valves 5 Selecting automatic calibration option 6 Setting room temperature setpoints 6 Setting override time 6 Enabling Wall Switch 6 Setting Duct Area 6 Setting flow coefficient 7 Setting airflow setpoints 7 Setting room tempera...

Page 3: ...f not avoided CAUTION Cautions indicate potentially hazardous situations which can result in personal injury or equipment damage if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes DANGER Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to...

Page 4: ...appropriate number see Configuring BACnet Parameters The start up is complete Setting the application NOTICE You can continue the startup procedure while calibration is underway However the controller will ignore commands to control end devices such as the damper until calibration of the air velocity sensor is finished Add the TEC to your job database and select one of the following applications f...

Page 5: ...ating before continuing MTRSETUP determines which actuators are controlled by the application and whether they are direct or reverse acting Set MTRSETUP according to Table 4 Table 4 Motor Enable Reverse Values for MTR SETUP Point 58 Enabled Enabled and Reversed Motor 1 damper Motor 2 Not used 1 default 3 Enabled 5 7 Enabled and Reversed 13 15 Verifying actuator setup Command all actuators closed V...

Page 6: ...er the override switch is depressed 4 factory default value Calibration occurs on the time interval set in the point CAL TIMER Point 96 For example if CAL TIMER 12 then the calibration period is12 hours Actual calibration is subject to a time delay based on the value of CTLR ADDRESS See the example in Option 1 This is the recommended option when using a controller with an Autozero Module Setting r...

Page 7: ... MIN to 0 zero Equipment damage may occur at 0 zero CFM with electric heat ON NOTICE Maximum flow s must be set minimum flow s NOTICE For Applications 2562 2563 2564 and 2566 HTG FLOW MAX should be less than CLG FLOW MAX Otherwise cold supply air may cool rather than heat the space in heating mode A typical setting for HTG FLOW MAX is 50 or less of CLG FLOW MAX 1 Set CLG FLOW MIN to the desired mi...

Page 8: ... configure Daikin BACnet MS TP TEC s Do not check the Metric checkbox in the Device Properties dialogue box if the controller is communicating through the MS TP driver in the Field Panel Metric can be checked only if the controller is communicating through a router If you need metric and the controller is communicating through the MS TP driver in the Field Panel then the Metric checkbox in the Dev...

Page 9: ......

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...

Reviews: