background image

IM 1040 • VAV ACTUATOR

6

www.DaikinApplied.com

s

TarT

-u

p

 p

roCedures

Enabling autozero module

 CAUTION

If an Autozero Module is used, do not enable MTR3 (valve 2).

 NOTICE

For  a  controller  without  an  Autozero  Module,  the  damper 

is  commanded  closed  to  get  a  zero  airflow  reading  during 

calibration.  For  a  controller  with  an  Autozero  Module,  the 

damper is closed only for the first calibration after controller 

initialization or power up. 

If an Autozero Module is used, enable it by setting CAL 

MODULE to Y.

Selecting automatic calibration option

 NOTICE

The air velocity sensor must be calibrated at least once every 

24  hours.  Make  sure  that  the  sensor  has  been  calibrated 

before balancing takes place, as this will affect the balancer’s 

results.

 NOTICE

Options  can  be  combined  by  summing  their  numbers.  For 

example, to calibrate as in Options 1 and 2, set CAL SETUP 

to 3. 

Using 

Table 5

 set CAL SETUP to the value that best meets 

your job requirements.
If appropriate, change CAL TIMER from the default of 12 

hours. This setting applies only if your choice for CAL SETUP 

includes Option 4.

Table 5: CAL SETUP Values

CAL SETUP (Point 95)

Description

0

Calibration occurs ONLY when the point CAL AIR 

(Point 94) is set to YES

1

Calibration occurs when the field panel commands 

a day/night mode changeover. Actual calibration is 

subject to a time delay of 0, 1, 2, or 3 minutes. This 

delay is determined by the point CTLR ADDRESS 

(Point 1) divided by 4. The remainder is the time 

delay in minutes. 

Example: If CTLR ADDRESS = 11, then the 

controller will wait 3 minutes (11 ÷ 4 = 2 R3) after it 

receives the day/night mode changeover command 

before beginning the calibration routine.

2

Calibration occurs immediately after the override 

switch is depressed.

4

(factory default value)

Calibration occurs on the time interval set in the 

point CAL TIMER (Point 96). 
For example, if CAL TIMER = 12, then the 

calibration period is12 hours. Actual calibration is 

subject to a time delay based on the value of CTLR 

ADDRESS. 

See the example in Option 1. This is the 

recommended option when using a controller with 

an Autozero Module.

Setting room temperature setpoints

 NOTICE

If  STPT  DIAL  is  set  to  YES,  do  not  set  the  DAY  (or  OCC) 

setpoints; the value of RM STPT DIAL will be used for these 

points.

DAY (or OCC) cooling setpoint

DAY (or OCC) heating setpoint

NGT (or UOC) cooling setpoint

NGT (or UOC) heating setpoint

If the room temperature sensor has a setpoint dial that will be 

used, set STPT DIAL to YES. Otherwise, set STPT DIAL to NO.
Set the room temperature setpoints to the desired values 

(some points are not present in certain cooling only 

applications).
Set RM STPT MIN and RM STPT MAX for the minimum and 

maximum allowable room temperature setpoints, respectively. 

Valid values range from 55°F to 95°F (13°C to 35°C). Default 

values are 55°F (13°C) for RM STPT MIN and 90°F (32°C) for 

RM STPT MAX.

Setting override time

If using night/unoccupied override, set OVRD TIME to the 

number of whole hours that an override should last. If OVRD 

TIME equals 0 (default), then this feature is disabled.

Enabling Wall Switch

If a wall switch is used for day/night (Occ/Unocc) control, 

enable it by setting WALL SWITCH to YES.

Setting Duct Area

If provided, enter the duct area (sq ft or sq m) into DUCT 

AREA (and also into HTGDUCT AREA, where applicable) and 

continue to 

Setting flow coefficient on page 7

.

If you do not know the duct area, use 

Table 6

:

Table 6: Duct Area Calculation

Area =

Round Duct

Rectangular Duct

Area in Sq. Ft.

(Dimensions in inches)

(π x R2)/144

Width × Height/144

Area in Sq. M.

(Dimensions in centimeters)

(π × R2)/10,000

Width × Height/10,000

Summary of Contents for BACnet

Page 1: ...Installation and Maintenance Manual IM 1040 Group Controls Part Number IM 1040 Date April 2015 BACnet VAV Actuator Electronic Output Start up Procedures ...

Page 2: ...ors 4 Setting controller address 4 Setting the application 4 Enabling actuators 5 Specifying motor setup 5 Verifying actuator setup 5 Setting the number of heat stages or valves 5 Selecting automatic calibration option 6 Setting room temperature setpoints 6 Setting override time 6 Enabling Wall Switch 6 Setting Duct Area 6 Setting flow coefficient 7 Setting airflow setpoints 7 Setting room tempera...

Page 3: ...f not avoided CAUTION Cautions indicate potentially hazardous situations which can result in personal injury or equipment damage if not avoided NOTICE Notices give important information concerning a process procedure special handling or equipment attributes DANGER Electric shock hazard Can cause personal injury or equipment damage This equipment must be properly grounded Connections and service to...

Page 4: ...appropriate number see Configuring BACnet Parameters The start up is complete Setting the application NOTICE You can continue the startup procedure while calibration is underway However the controller will ignore commands to control end devices such as the damper until calibration of the air velocity sensor is finished Add the TEC to your job database and select one of the following applications f...

Page 5: ...ating before continuing MTRSETUP determines which actuators are controlled by the application and whether they are direct or reverse acting Set MTRSETUP according to Table 4 Table 4 Motor Enable Reverse Values for MTR SETUP Point 58 Enabled Enabled and Reversed Motor 1 damper Motor 2 Not used 1 default 3 Enabled 5 7 Enabled and Reversed 13 15 Verifying actuator setup Command all actuators closed V...

Page 6: ...er the override switch is depressed 4 factory default value Calibration occurs on the time interval set in the point CAL TIMER Point 96 For example if CAL TIMER 12 then the calibration period is12 hours Actual calibration is subject to a time delay based on the value of CTLR ADDRESS See the example in Option 1 This is the recommended option when using a controller with an Autozero Module Setting r...

Page 7: ... MIN to 0 zero Equipment damage may occur at 0 zero CFM with electric heat ON NOTICE Maximum flow s must be set minimum flow s NOTICE For Applications 2562 2563 2564 and 2566 HTG FLOW MAX should be less than CLG FLOW MAX Otherwise cold supply air may cool rather than heat the space in heating mode A typical setting for HTG FLOW MAX is 50 or less of CLG FLOW MAX 1 Set CLG FLOW MIN to the desired mi...

Page 8: ... configure Daikin BACnet MS TP TEC s Do not check the Metric checkbox in the Device Properties dialogue box if the controller is communicating through the MS TP driver in the Field Panel Metric can be checked only if the controller is communicating through a router If you need metric and the controller is communicating through the MS TP driver in the Field Panel then the Metric checkbox in the Dev...

Page 9: ......

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinApplie...

Reviews: