background image

4 Installation

Installation manual

15

ARXM50~71+RXM42~71N2V1B(9) + RXP50~7
RXA42+50+RXF50+6 RXF7 RXJ50N2V1B
R32 split series
3P512025-6M – 2018.11

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

4.3.2

To perform vacuum drying

DANGER: RISK OF EXPLOSION

Do NOT start the unit if it is vacuumed.

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

4.4

Charging refrigerant

4.4.1

About charging refrigerant

The  outdoor  unit  is  factory  charged  with  refrigerant,  but  in  some
cases the following might be necessary:

What

When

Charging additional refrigerant

When the total liquid piping
length is more than specified
(see later).

Completely recharging refrigerant

Example: 

▪ When relocating the system.

▪ After a leak.

Charging additional refrigerant

Before  charging  additional  refrigerant,  make  sure  the  outdoor  unit's

external

 refrigerant piping is checked (leak test, vacuum drying).

INFORMATION

Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.

Typical  workflow  –  Charging  additional  refrigerant  typically  consists
of the following stages:

1 Determining if and how much you have to charge additionally.

2 If necessary, charging additional refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

Completely recharging refrigerant

Before completely recharging refrigerant, make sure the following is
done:

1 All refrigerant is recovered from the system.

2 The outdoor unit's 

external

 refrigerant piping is checked (leak

test, vacuum drying).

3 Vacuum drying on the outdoor unit's 

internal

 refrigerant piping is

performed.

NOTICE

Before  completely  recharging,  perform  vacuum  drying  on
the outdoor unit's 

internal

 refrigerant piping as well.

Typical  workflow  –  Completely  recharging  refrigerant  typically
consists of the following stages:

1 Determining how much refrigerant to charge.

2 Charging refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

4.4.2

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

Summary of Contents for ARXM50N2V1B9

Page 1: ...ies English Installation manual R32 split series ARXM50N2V1B9 ARXM60N2V1B9 ARXM71N2V1B9 RXM42N2V1B9 RXM50N2V1B9 RXM60N2V1B9 RXM71N2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B RXA42B2V1B RXA50B2V1B RXF50B2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...dringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directiv...

Page 5: ...a kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentel...

Page 7: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 8: ...na kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respec...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...uin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective...

Page 11: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 12: ...CB 18 7 Disposal 18 8 Technical data 19 8 1 Wiring diagram 19 8 2 Piping diagram 20 8 2 1 Piping diagram Outdoor unit 20 1 About the documentation 1 1 About this document INFORMATION Make sure that th...

Page 13: ...destal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expecte...

Page 14: ...rain cap 1 c Drain hole for drain socket 4 2 Connecting the refrigerant piping DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as sho...

Page 15: ...piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant...

Page 16: ...nected and checked leak test and vacuum drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 4 6 To fix the fluorinated...

Page 17: ...Phase 1 Frequency 50 Hz Wire sizes 3 core cable 2 5 mm2 4 0 mm2 H05RN F 60245 IEC 57 Interconnection cable indoor outdoor 4 core cable 1 5 mm2 2 5 mm2 and applicable for 220 240 V H05RN F 60245 IEC 5...

Page 18: ...ypassed 5 2 Checklist during commissioning To perform an air purge To perform a test run 5 3 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be...

Page 19: ...NNECTOR HR MR _A MR _B S U V W X A K R_ D V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V...

Page 20: ...tor Outdoor temperature Thermistor Refrigerant flow Cooling Heating PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXP60M RX...

Page 21: ...ual reset Automatic reset High pressure switch Muf er PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXM42N RXM50N RXM60N AR...

Page 22: ...T 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Compressor Accumulator Muffler Muffler Gas stop valve Liquid st...

Page 23: ......

Page 24: ...3P512025 6M 2018 11 Copyright 2018 Daikin...

Reviews: