8 Technical data

Installation manual

19

ARXM50~71+RXM42~71N2V1B(9) + RXP50~7
RXA42+50+RXF50+6 RXF7 RXJ50N2V1B
R32 split series
3P512025-6M – 2018.11

8

Technical data

subset

  of  the  latest  technical  data  is  available  on  the  regional  Daikin  website  (publicly  accessible).  The 

full  set

  of  latest  technical  data  is

available on the Daikin Business Portal (authentication required).

8.1

Wiring diagram

The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).

,

A

INDOOR

OUTDOOR

For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part 

and is represented in the overview below by symbol “*” in the part code.

Unified Wiring Diagram Legend

CIRCUIT BREAKER

: CONNECTION

: CONNECTOR

: EARTH

FIELD WIRING

: FUSE

INDOOR UNIT

OUTDOOR UNIT

PROTECTIVE EARTH

PROTECTIVE EARTH (SCREW)

: RECTIFIER

RELAY CONNECTOR

SHORT-CIRCUIT CONNECTOR

: TERMINAL

TERMINAL STRIP

WIRE CLAMP

WHT : WHITE
YLW : YELLOW

PNK 

: PINK

PRP, PPL :  PURPLE
RED  : RED

GRN : GREEN
GRY : GREY
ORG : ORANGE

BLK  : BLACK
BLU  : BLUE
BRN : BROWN

A*P 

PRINTED CIRCUIT BOARD

BS* 

PUSHBUTTON ON/OFF, OPERATION SWITCH

BZ, H*O 

BUZZER

C* 

: CAPACITOR

AC*, CN*, E*, HA*, HE*, HL*, HN*, : 

CONNECTION, CONNECTOR

HR*, MR*_A, MR*_B, S*, U, V,
W, X*A, K*R_*
D*, V*D 

DIODE

DB* 

DIODE BRIDGE

DS* 

DIP SWITCH

E*H 

: HEATER

F*U, FU* (FOR CHARACTERISTICS,  :  FUSE
REFER TO PCB INSIDE YOUR UNIT)
FG* 

CONNECTOR (FRAME GROUND)

H* 

: HARNESS

H*P, LED*, V*L 

PILOT LAMP, LIGHT EMITTING DIODE

HAP 

LIGHT EMITTING DIODE (SERVICE MONITOR GREEN)

HIGH VOLTAGE 

HIGH VOLTAGE

IES 

INTELLIGENT EYE SENSOR

IPM* 

INTELLIGENT POWER MODULE

K*R, KCR, KFR, KHuR, K*M 

MAGNETIC RELAY

: LIVE

L* 

: COIL

L*R 

: REACTOR

M* 

STEPPER MOTOR

M*C 

COMPRESSOR MOTOR

M*F 

FAN MOTOR

M*P 

DRAIN PUMP MOTOR

M*S 

SWING MOTOR

MR*, MRCW*, MRM*, MRN* 

MAGNETIC RELAY

: NEUTRAL

n=*, N=* 

NUMBER OF PASSES THROUGH FERRITE CORE

PAM 

PULSE-AMPLITUDE MODULATION

PCB* 

PRINTED CIRCUIT BOARD

PM* 

POWER MODULE

PS 

SWITCHING POWER SUPPLY

PTC* 

THERMISTOR PTC

Q* 

INSULATED GATE BIPOLAR TRANSISTOR 
(IGBT)

Q*DI 

EARTH LEAK CIRCUIT BREAKER

Q*L 

OVERLOAD PROTECTOR

Q*M 

THERMO SWITCH

R* 

: RESISTOR

R*T 

: THERMISTOR

RC 

: RECEIVER

S*C 

LIMIT SWITCH

S*L 

FLOAT SWITCH

S*NPH 

PRESSURE SENSOR (HIGH)

S*NPL 

PRESSURE SENSOR (LOW)

S*PH, HPS* 

PRESSURE SWITCH (HIGH)

S*PL 

PRESSURE SWITCH (LOW)

S*T 

: THERMOSTAT

S*RH 

HUMIDITY SENSOR

S*W, SW* 

OPERATION SWITCH

SA*, F1S 

SURGE ARRESTOR

SR*, WLU 

SIGNAL RECEIVER

SS* 

SELECTOR SWITCH

SHEET METAL  : 

TERMINAL STRIP FIXED PLATE

T*R 

: TRANSFORMER

TC, TRC 

TRANSMITTER

V*, R*V 

VARISTOR

V*R 

DIODE BRIDGE

WRC 

WIRELESS REMOTE CONTROLLER

X* 

: TERMINAL

X*M 

TERMINAL STRIP (BLOCK)

Y*E 

ELECTRONIC EXPANSION VALVE COIL

Y*R, Y*S 

REVERSING SOLENOID VALVE COIL

Z*C 

FERRITE CORE

ZF, Z*F 

NOISE FILTER

Summary of Contents for ARXM50N2V1B9

Page 1: ...ies English Installation manual R32 split series ARXM50N2V1B9 ARXM60N2V1B9 ARXM71N2V1B9 RXM42N2V1B9 RXM50N2V1B9 RXM60N2V1B9 RXM71N2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B RXA42B2V1B RXA50B2V1B RXF50B2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...dringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directiv...

Page 5: ...a kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentel...

Page 7: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 8: ...na kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respec...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...uin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective...

Page 11: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 12: ...CB 18 7 Disposal 18 8 Technical data 19 8 1 Wiring diagram 19 8 2 Piping diagram 20 8 2 1 Piping diagram Outdoor unit 20 1 About the documentation 1 1 About this document INFORMATION Make sure that th...

Page 13: ...destal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expecte...

Page 14: ...rain cap 1 c Drain hole for drain socket 4 2 Connecting the refrigerant piping DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as sho...

Page 15: ...piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant...

Page 16: ...nected and checked leak test and vacuum drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 4 6 To fix the fluorinated...

Page 17: ...Phase 1 Frequency 50 Hz Wire sizes 3 core cable 2 5 mm2 4 0 mm2 H05RN F 60245 IEC 57 Interconnection cable indoor outdoor 4 core cable 1 5 mm2 2 5 mm2 and applicable for 220 240 V H05RN F 60245 IEC 5...

Page 18: ...ypassed 5 2 Checklist during commissioning To perform an air purge To perform a test run 5 3 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be...

Page 19: ...NNECTOR HR MR _A MR _B S U V W X A K R_ D V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V...

Page 20: ...tor Outdoor temperature Thermistor Refrigerant flow Cooling Heating PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXP60M RX...

Page 21: ...ual reset Automatic reset High pressure switch Muf er PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXM42N RXM50N RXM60N AR...

Page 22: ...T 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Compressor Accumulator Muffler Muffler Gas stop valve Liquid st...