4 Installation

Installation manual

14

ARXM50~71+RXM42~71N2V1B(9) + RXP50~7

RXA42+50+RXF50+6 RXF7 RXJ50N2V1B

R32 split series

3P512025-6M – 2018.11

4.1.2

To install the outdoor unit

4× M8/M10

4.1.3

To provide drainage

NOTICE

If  the  unit  is  installed  in  a  cold  climate,  take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

INFORMATION

For  information  on  the  available  options,  contact  your
dealer.

NOTICE

Provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally,  make  sure  the  unit  is  positioned  at  least
100 mm above the expected level of snow.

1

Use a drain plug for drainage.

2

Use a Ø16 mm hose (field supply).

b

c

d

a

a

Drain port

b

Bottom frame

c

Drain plug

d

Hose (field supply)

To close the drain holes and attach the drain
socket

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(1,  2)  with  the  outdoor  unit.  Take  adequate  measures  so
that the evacuated condensate CANNOT freeze.

1

Install drain caps 1 and 2 (accessory). Make sure the edges of
the drain caps close off the holes completely.

a

b

a

Bottom frame

b

Drain cap

2

Install the drain socket.

a

c

b

b

b

a

a

a

Drain hole. Install a drain cap (2).

b

Drain hole. Install a drain cap (1).

c

Drain hole for drain socket

4.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.2.1

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

CAUTION

▪ Use the flare nut fixed to the unit.

▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

4.3

Checking the refrigerant piping

4.3.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

Summary of Contents for ARXM50N2V1B9

Page 1: ...ies English Installation manual R32 split series ARXM50N2V1B9 ARXM60N2V1B9 ARXM71N2V1B9 RXM42N2V1B9 RXM50N2V1B9 RXM60N2V1B9 RXM71N2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B RXA42B2V1B RXA50B2V1B RXF50B2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...dringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directiv...

Page 5: ...a kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentel...

Page 7: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 8: ...na kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respec...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...uin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective...

Page 11: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 12: ...CB 18 7 Disposal 18 8 Technical data 19 8 1 Wiring diagram 19 8 2 Piping diagram 20 8 2 1 Piping diagram Outdoor unit 20 1 About the documentation 1 1 About this document INFORMATION Make sure that th...

Page 13: ...destal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expecte...

Page 14: ...rain cap 1 c Drain hole for drain socket 4 2 Connecting the refrigerant piping DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as sho...

Page 15: ...piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant...

Page 16: ...nected and checked leak test and vacuum drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 4 6 To fix the fluorinated...

Page 17: ...Phase 1 Frequency 50 Hz Wire sizes 3 core cable 2 5 mm2 4 0 mm2 H05RN F 60245 IEC 57 Interconnection cable indoor outdoor 4 core cable 1 5 mm2 2 5 mm2 and applicable for 220 240 V H05RN F 60245 IEC 5...

Page 18: ...ypassed 5 2 Checklist during commissioning To perform an air purge To perform a test run 5 3 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be...

Page 19: ...NNECTOR HR MR _A MR _B S U V W X A K R_ D V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V...

Page 20: ...tor Outdoor temperature Thermistor Refrigerant flow Cooling Heating PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXP60M RX...

Page 21: ...ual reset Automatic reset High pressure switch Muf er PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXM42N RXM50N RXM60N AR...

Page 22: ...T 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Compressor Accumulator Muffler Muffler Gas stop valve Liquid st...

Page 23: ......

Page 24: ...3P512025 6M 2018 11 Copyright 2018 Daikin...

Reviews: