5 Commissioning

Installation manual

18

ARXM50~71+RXM42~71N2V1B(9) + RXP50~7

RXA42+50+RXF50+6 RXF7 RXJ50N2V1B

R32 split series

3P512025-6M – 2018.11

5

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

5.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The 

refrigerant  pipes

  (gas  and  liquid)  are  thermally

insulated.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

The following 

field wiring

 has been carried out according

to  this  document  and  the  applicable  legislation  between
the outdoor unit and the indoor unit.

Drainage

Make sure drainage flows smoothly.

Possible consequence: 

Condensate water might drip.

The indoor unit receives the signals of the 

user interface

.

The  specified  wires  are  used  for  the 

interconnection

cable

.

The 

fuses, circuit breakers,

 or locally installed protection

devices  are  installed  according  to  this  document,  and
have NOT been bypassed.

5.2

Checklist during commissioning

To perform an 

air purge

.

To perform a 

test run

.

5.3

To perform a test run

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test  run  may  be  performed  in  cooling  or  heating

mode.

Prerequisite: 

Test run should be performed in accordance with the

operation  manual  of  the  indoor  unit  to  make  sure  that  all  functions
and parts are working properly.

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.

2

When  the  test  run  is  finished,  set  the  temperature  to  a  normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

The  system  stops  operating  3  minutes  after  the  unit  is  turned
OFF.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.

▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

6

Troubleshooting

6.1

Fault diagnosis using LED on
outdoor unit PCB

LED is…

Diagnosis

flashing

Normal.

▪ Check the indoor unit.

ON

▪ Turn  the  power  OFF  and  back  ON,  and

check  the  LED  within  approximately  3
minutes.
If  the  LED  is  ON  again,  the  outdoor  unit
PCB is faulty.

OFF

1

Supply voltage (for power saving).

2

Power supply fault.

3

Turn  the  power  OFF  and  back  ON,  and
check  the  LED  within  approximately  3
minutes.
If the LED is ON again, the outdoor unit
PCB is faulty.

DANGER: RISK OF ELECTROCUTION

▪ When  the  unit  is  not  operating,  the  LEDs  on  the  PCB

are turned off in order to save power.

▪ Even when the LEDs are off, the terminal block and the

PCB may be powered.

7

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Summary of Contents for ARXM50N2V1B9

Page 1: ...ies English Installation manual R32 split series ARXM50N2V1B9 ARXM60N2V1B9 ARXM71N2V1B9 RXM42N2V1B9 RXM50N2V1B9 RXM60N2V1B9 RXM71N2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B RXA42B2V1B RXA50B2V1B RXF50B2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...dringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directiv...

Page 5: ...a kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentel...

Page 7: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 8: ...na kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respec...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...uin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective...

Page 11: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 12: ...CB 18 7 Disposal 18 8 Technical data 19 8 1 Wiring diagram 19 8 2 Piping diagram 20 8 2 1 Piping diagram Outdoor unit 20 1 About the documentation 1 1 About this document INFORMATION Make sure that th...

Page 13: ...destal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expecte...

Page 14: ...rain cap 1 c Drain hole for drain socket 4 2 Connecting the refrigerant piping DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as sho...

Page 15: ...piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant...

Page 16: ...nected and checked leak test and vacuum drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 4 6 To fix the fluorinated...

Page 17: ...Phase 1 Frequency 50 Hz Wire sizes 3 core cable 2 5 mm2 4 0 mm2 H05RN F 60245 IEC 57 Interconnection cable indoor outdoor 4 core cable 1 5 mm2 2 5 mm2 and applicable for 220 240 V H05RN F 60245 IEC 5...

Page 18: ...ypassed 5 2 Checklist during commissioning To perform an air purge To perform a test run 5 3 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be...

Page 19: ...NNECTOR HR MR _A MR _B S U V W X A K R_ D V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V...

Page 20: ...tor Outdoor temperature Thermistor Refrigerant flow Cooling Heating PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXP60M RX...

Page 21: ...ual reset Automatic reset High pressure switch Muf er PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXM42N RXM50N RXM60N AR...

Page 22: ...T 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Compressor Accumulator Muffler Muffler Gas stop valve Liquid st...

Page 23: ......

Page 24: ...3P512025 6M 2018 11 Copyright 2018 Daikin...