4 Installation

Installation manual

13

ARXM50~71+RXM42~71N2V1B(9) + RXP50~7
RXA42+50+RXF50+6 RXF7 RXJ50N2V1B
R32 split series
3P512025-6M – 2018.11

3.1.1

Installation site requirements of the
outdoor unit

Mind the following spacing guidelines:

>100

>50

>350

(mm)

b

a

>100

>50

b

a

>100

b

a

b

a

>350

>350

>50

b

a

a

Air outlet

b

Air inlet

NOTICE

The height of the wall on the outlet side of the outdoor unit
MUST be ≤1200 mm.

Do  NOT  install  the  unit  in  sound  sensitive  areas  (e.g.  near  a
bedroom), so that the operation noise will cause no trouble.

Note: 

If  the  sound  is  measured  under  actual  installation  conditions,

the  measured  value  might  be  higher  than  the  sound  pressure  level
mentioned  in  "Sound  spectrum"  in  the  data  book  due  to
environmental noise and sound reflections.

INFORMATION

The sound pressure level is less than 70 dBA.

3.1.2

Additional installation site requirements
of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.

a

b

c

c

d

a

Snow cover or shed

b

Pedestal

c

Prevailing wind direction

d

Air outlet

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  See 

"4.1  Mounting  the

outdoor unit" on page 13

 for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

3.1.3

Refrigerant piping length and height
difference

What?

Distance

Maximum allowable pipe length

30 m

Minimum allowable pipe length

3 m

Maximum allowable height distance

20 m

4

Installation

4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

353

600

240

(mm)

240

>300

In  any  case,  provide  at  least  300  mm  of  free  space  below  the  unit.
Additionally, make sure the unit is positioned at least 100 mm above
the  maximum  expected  level  of  snow.  In  this  case,  it  is
recommended to construct a pedestal.

Summary of Contents for ARXM50N2V1B9

Page 1: ...ies English Installation manual R32 split series ARXM50N2V1B9 ARXM60N2V1B9 ARXM71N2V1B9 RXM42N2V1B9 RXM50N2V1B9 RXM60N2V1B9 RXM71N2V1B RXP50M2V1B RXP60M2V1B RXP71M2V1B RXA42B2V1B RXA50B2V1B RXF50B2V1B...

Page 2: ...tiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amend...

Page 3: ...aava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS T...

Page 4: ...dringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directiv...

Page 5: ...a kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentel...

Page 7: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 8: ...na kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respec...

Page 9: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 10: ...uin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective...

Page 11: ...va kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSm...

Page 12: ...CB 18 7 Disposal 18 8 Technical data 19 8 1 Wiring diagram 19 8 2 Piping diagram 20 8 2 1 Piping diagram Outdoor unit 20 1 About the documentation 1 1 About this document INFORMATION Make sure that th...

Page 13: ...destal c Prevailing wind direction d Air outlet In any case provide at least 300 mm of free space below the unit Additionally make sure the unit is positioned at least 100 mm above the maximum expecte...

Page 14: ...rain cap 1 c Drain hole for drain socket 4 2 Connecting the refrigerant piping DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit Piping length Keep field piping as sho...

Page 15: ...piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional refrigerant...

Page 16: ...nected and checked leak test and vacuum drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 4 4 6 To fix the fluorinated...

Page 17: ...Phase 1 Frequency 50 Hz Wire sizes 3 core cable 2 5 mm2 4 0 mm2 H05RN F 60245 IEC 57 Interconnection cable indoor outdoor 4 core cable 1 5 mm2 2 5 mm2 and applicable for 220 240 V H05RN F 60245 IEC 5...

Page 18: ...ypassed 5 2 Checklist during commissioning To perform an air purge To perform a test run 5 3 To perform a test run Prerequisite Power supply MUST be in the specified range Prerequisite Test run may be...

Page 19: ...NNECTOR HR MR _A MR _B S U V W X A K R_ D V D DIODE DB DIODE BRIDGE DS DIP SWITCH E H HEATER F U FU FOR CHARACTERISTICS FUSE REFER TO PCB INSIDE YOUR UNIT FG CONNECTOR FRAME GROUND H HARNESS H P LED V...

Page 20: ...tor Outdoor temperature Thermistor Refrigerant flow Cooling Heating PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXP60M RX...

Page 21: ...ual reset Automatic reset High pressure switch Muf er PED categories of equipment High pressure switch category IV Compressor category II Other equipment art 4 3 Applicable for RXM42N RXM50N RXM60N AR...

Page 22: ...T 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 4 0 CuT 9 5 CuT 9 5 CuT 6 4 CuT 4 way valve ON heating Propeller fan Discharge pipe thermistor Muffler Compressor Accumulator Muffler Muffler Gas stop valve Liquid st...

Page 23: ......

Page 24: ...3P512025 6M 2018 11 Copyright 2018 Daikin...

Reviews: